Combination Fire Smoke Dampers meeting the following 

specifications shall be furnished and installed where shown on 

plans and/or as described in schedules. Dampers shall meet the 

requirements of NFPA 80, 90A, 92A, 92B, 101, and 105 and further 

shall be tested

, rated and labeled in accordance with the latest 

edition of UL Standards 555 and 555S.  Dampers shall have a UL555 

fire rating of 3 hours and be of low leakage design qualified to 

UL 555S Leakage Class I.
Each damper /actuator combination shall have a UL555S elevated 

temperature rating of 350° F (177°C) minimum and shall be 

operational and dynamic rated to operate at maximum design air 

flow at its installed location. Each damper shall be supplied with 

an appropriate actuator installed by the damper manufacturer at 

the time of damper fabrication. Damper actuator shall be (specifier 

select one of the following) electric type for 120 (24 or 230) volt 

operation or pneumatic type for 25 psi minimum (30 psi maximum) 

operation.

Damper blades shall be of the double skin airfoil type and shall 

have an equivalent thickness of 14 ga. (2mm) . Damper frame shall 

be galvanized steel formed into a structural hat channel shape with 

reinforced corners. Bearings shall be sintered bronze sleeve type 

rotating in extruded holes in the damper frame. Blade edge seals 

shall be silicone rubber designed to inflate and provide a tighter 

seal against leakage as pressure on either side of the damper 

increases. Jamb seals shall be stainless steel compression type. 

Blades shall be completely symmetrical relative to their axle pivot 

point, presenting identical resistance to airflow in either direction or 

pressure on either side of the damper.
Damper must be rated for mounting vertically (with blades running 

horizontal) and be UL 555S rated for leakage and airflow in either 

direction through the damper. Each damper shall be supplied with 

a 165°F (74°C) RRL. Testing and ratings to be in accordance with 

AMCA standard 500-D.
The basis of design is Greenheck Model FSD-331.

damper sizing Information

Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The 

following figures show maximum damper section size and assembly configurations for multi-section dampers.

specifications

Transitioned damper 

dimensions

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the

 

FSD-331 can be supplied in a factory sleeve with round or oval transitions on both ends 

of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show 

overall damper size.

These dimensions are furnished 

approximately 

1

/

4

 in. (6mm) undersize, 

except round and oval  dimensions  

which are approximately 

1

/

8

 in.(3mm) 

undersize. 
Ts = (2)(Sleeve Thickness)

D*  +  2 in. (51mm) +T  s 

D* 

TYPE  R 

 

16 in. (406mm) 

Min. 

8

 in.

D*  +  2 in. (51mm)+T  s 

TYPE  O 

H* 

W* 

  

+  2 in. (51mm)+T s 

H*  +  2 in. (51mm)+T s 

W* 

H* 

TYPE  C 

  

H*  +  2 in. (51mm)+T s 

 

(54mm)

16 in. (406mm) 

Min. 

8

 in. 

(54mm)

16 in. (406mm) 

Min. 

W* +  2 in. (51mm)+T s 

(54mm)

8

 in.

Copyright © 2008 Greenheck Fan

 

Corporation

FSD-331 Rev 1 March 2008

Содержание Steel Airfoil Blades FSD-331

Страница 1: ...tures RRL OCI Open closed indication switches 165ºF 74 C 212ºF 100 C 250ºF 121 C 350ºF 177 C RRL s available TOR remote override closure allows damper to perform smoke management functions during a fire emergency Electric or pneumatic actuators to accomplish smoke management and system functions POC retaining angles Smoke detectors Momentary Switch Transitions R C O PRV pneumatic relief valve Secu...

Страница 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because entrance losses are minimized by a straig...

Страница 3: ...500 0 34 2500 0 34 2500 0 33 2500 0 51 3000 1 04 3000 0 49 3000 0 49 3000 0 48 3000 0 74 3500 1 41 3500 0 67 3500 0 67 3500 0 65 3500 1 00 4000 1 84 4000 0 87 4000 0 88 4000 0 85 4000 1 31 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12 in x 12 in 305mm x 305mm R Greenheck Fan Corporation certifies that the model FSD 331 shown here...

Страница 4: ...00 0 21 3000 0 24 3000 0 42 3500 0 73 3500 0 32 3500 0 29 3500 0 33 3500 0 57 4000 0 95 4000 0 42 4000 0 38 4000 0 43 4000 0 74 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 12 in x 12 in 305mm x 305mm 1 2 x 1 2 4 8 x 1 2 1 2 x 4 8 24x24 3 6 x 3 6 Sizes are in inches R Greenheck Fan Corporation certifies that the model FSD 331 shown...

Страница 5: ...0 81 2500 0 75 2500 0 77 2500 0 89 3000 1 68 3000 1 17 3000 1 08 3000 1 11 3000 1 28 3500 2 29 3500 1 60 3500 1 48 3500 1 51 3500 1 75 4000 2 09 4000 2 14 4000 1 93 4000 1 97 4000 2 29 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 12 in x 12 in 305mm x 305mm R Greenheck Fan Corporation certifies that the model FSD 331 shown herein i...

Страница 6: ...ire these worst case clearances If space availability above or below the damper sleeve is limited each damper size should be individually evaluated Application Data 53 8 5 Right hand drive is shown Left hand drive available upon request LH RH A Sleeve Length Varies 6 33 4 11 2 max B S T With the exception of dampers 10 in high 254mm or less NOTE Entire damper frame is not required to be installed ...

Страница 7: ... designed to inflate and provide a tighter seal against leakage as pressure on either side of the damper increases Jamb seals shall be stainless steel compression type Blades shall be completely symmetrical relative to their axle pivot point presenting identical resistance to airflow in either direction or pressure on either side of the damper Damper must be rated for mounting vertically with blad...

Отзывы: