AMCA 5.5 Pressure Drop 

SMD-203

R

Greenheck Fan Corporation certifies that the 

model SMD-203 shown herein is licensed to bear 
the AMCA Seal. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 511 and comply with 

the requirements of the AMCA Certified Ratings 
Programs. The AMCA Certified Ratings Seal 

applies to air performance ratings only. 

5D

6D

5D

D

4 (W) (H)

3.14

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.06

500

0.03

500

0.03 

500

0.03 

1000

0.22 

1000

0.14 

1000

0.12 

1000

0.13 

1500

0.50

1500

0.31

1500

0.26

1500

0.30 

2000 

0.89 

2000

0.54

2000

0.46

2000

0.53

2500

1.39

2500

0.85

2500

0.73

2500

0.83

3000

2.00

3000

1.22

3000

1.05

3000

1.19

3500

2.72

3500

1.66

3500

1.42 

3500

1.62

4000

3.55

4000

2.17

4000

1.86

4000

2.11

12 in. x 12 in. (305mm x 305mm) 

24 in. x 24 in. (610mm x 610mm) 

36 in. x 36 in. (914mm x 914mm) 

12 in. x 48 in. (305mm x 1219mm) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.04 

1000

0.17 

1500

0.38 

2000

0.67

2500

1.04

3000

1.50

3500

2.05

4000

2.67 

48 in. x 12 in. (1219mm x 305mm) 

Содержание Smoke Dampers SMD-203

Страница 1: ...mb seals Linkage Concealed in jamb Axles 1 2 in 13mm dia plated steel Bearings Bronze sleeve type Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 32 in W x 50 in H 813mm W x 1270mm H 36 in W x 48 in H 914mm W x 1219mm H Multiple Section 144 in W x 100 in H 3658mm W x 2540mm H 288 in W x 50 in H 7315 mm W x 1270mm H Optional Features Galvanized steel slee...

Страница 2: ...stem AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because ent...

Страница 3: ...ureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 04 500 0 02 500 0 01 500 0 01 1000 0 14 1000 0 07 1000 0 04 1000 0 06 1500 0 31 1500 0 16 1500 0 09 1500 0 13 2000 0 55 2000 0 29 2000 0 16 2000 0 23 2500 0 86 2500 0 45 2500 0 25 2500 0 36 3000 1 24 3000 0 65 3000 0 36 3000 0 52 3500 1 69 3500 0 89 3500 0 49 3500 0 70 4000 2 20 4000...

Страница 4: ...00 0 48 3500 0 33 3500 0 53 4000 1 44 4000 0 63 4000 0 42 4000 0 70 12in x12in 305mm x 305mm 24in x24in 610mm x 610mm 36in x36in 914mm x 914mm 12in x48in 305mm x 1219mm Velocity fpm Pressure Drop in wg 500 0 02 1000 0 07 1500 0 16 2000 0 29 2500 0 45 3000 0 64 3500 0 88 4000 1 14 48 in x 12 in 1219mm x 305mm R Greenheck Fan Corporation certifies that the model SMD 203 shown herein is licensed to b...

Страница 5: ...m PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 06 500 0 03 500 0 03 500 0 03 1000 0 22 1000 0 14 1000 0 12 1000 0 13 1500 0 50 1500 0 31 1500 0 26 1500 0 30 2000 0 89 2000 0 54 2000 0 46 2000 0 53 2500 1 39 2500 0 85 2500 0 73 2500 0 83 3000 2 00 3000 1 22 3000 1 05 3000 1 19 3500 2 72 3500 1 66 3500 1 42 3500 1 62 4000 3 55 4000 2 17 4000 1 86 4000 2 11...

Страница 6: ...e of 6 in 152mm to 12 in 305mm for the A dimension Application Data 53 8 in 5 in Right hand drive is shown Left hand drive available upon request LH RH A Sleeve Length Varies 6 in 33 4 11 2 in max B S T in 53 8 in 5 in Right hand drive is shown Left hand drive available upon request LH RH A Sleeve Length Varies 6 in 33 4 11 2 in max B S T in With the exception of dampers 10 in high 254mm or less N...

Страница 7: ...ical relative to their axle pivot point presenting identical resistance to airflow in either direction or pressure on either side of the damper The Damper Manufacturer s submittal data shall certify all air perfor mance pressure drop data is licensed in accordance with the AMCA Certified Ratings Program for Test Figures 5 2 5 3 and 5 5 Damper air performance data shall be developed in accordance w...

Отзывы: