Pressure Drop Data 

SMD-302

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 

data has been corrected to represent standard air at a density of .075 lb/ft

3

 

 (1.201 kg/m

3

).  

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an 

analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC 

system.

AMCA Test Figures

Figure 5.3 

Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations 

because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper. 

Figure 5.2

 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than 

Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5

 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high 

entrance and exit losses due to the sudden changes of area in the system.

5D

6D

5D

D

4 (W) (H)

3.14

Figure 5.3

5D

6D

5D

D

4 (W) (H)

3.14

Figure 5.5

Figure 5.2

5D

6D

5D

D

4 (W) (H)

3.14

Содержание SMD-302

Страница 1: ...eel jamb seals Linkage Concealed in jamb Axles 1 2 in 13mm dia plated steel Bearings Bronze sleeve type Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 32 i...

Страница 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstr...

Страница 3: ...ity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 03 500 0 01 500 0 01 500 0 01 500 0 02 1000 0 12 1000 0 06 1000 0 0...

Страница 4: ...Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 01 500 0 01 500 0 01 500 0 01 500 0 01 100...

Страница 5: ...wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 04 500 0 03 500 0 03 500 0 03 500 0 03 1000 0 18 1000 0 13...

Страница 6: ...02 The standard A dimen sions listed in the table provide adequate space for the mounting of actuators and controls If space constraints are a problem the A dimension can be varied between 53 8 in 136...

Страница 7: ...r pneumatic type for 25 psi minimum 30 psi maximum operation Damper blades shall be of the double skin airfoil type and shall have an equivalent metal thickness of 14 ga 2mm Damper frame shall be galv...

Отзывы: