background image

485229 • QEID FJ, Rev. 1, September 2021 

Copyright 2021 © Greenheck Fan Corporation

4

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications 
without notice.

Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature 
section of the website at Greenheck.com/Resources/Library/Literature.

®

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

AMCA Publication 410-96, Safety Practices for Users and 

Installers of Industrial and Commercial Fans, provides 

additional safety information. This publication can be obtained 

from AMCA International, Inc. at www.amca.org.

Greenheck models QEI and QEID catalog provides additional 

information describing the equipment and available 

accessories.

Tri-Voltage: 115V or 208-230/277V

The tri-voltage feature allows the motor to operate at 
115/208-230/277V. The operating voltage is selected via 
the voltage jumper wire.
When the jumper wire is 

connected

, the motor operates 

at 115V, see Fig 4.
When the jumper wire is 

disconnected and capped

the motor operates at 208-230/277V, see Fig. 5.

Fig. 4
115V Operation

Fig. 5 
208-230/277V Operation

Speed Control Dial

The speed control dial is mounted on the power 
pack bracket and is to be plugged into the 9-pin 
connector on the motor. To increase speed, rotate 
the dial clockwise. To decrease speed, rotate the dial 
counterclockwise. From 0-1.9V the motor will be off and 
will operate in the 2-10V range.

Troubleshooting

Motor does not operate.

1.  Check all wiring connections to ensure they are correct and secure.
2.  Verify that all voltages are present at the motor, including 0-10 VDC, if applicable.
3.  Make sure that the fan wheel will rotate freely and there are no foreign objects in the wheel. If fan wheel does not 

rotate freely, contact factory.

4.  If motor has both the dial on the motor and 0-10 VDC control option, control wiring issues can be tested by 

disconnecting the control wires from the motor. The motor should then operate using the dial on the motor for 
speed control.

Motor will not reach maximum speed.

1.  Make sure dial is rotated full clockwise, if applicable.
2.  Make sure motor is receiving 10 VDC, if applicable.

Maintenance

QEID FJ motor uses sealed bearings. No lubrication is required. This fan is not designed to be disassembled. 
Consult the factory with issues.

Содержание QEID FJ

Страница 1: ...an Electrical Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan rpm Adjustments to fan speed significantly effects motor load 5 Do not allow the power cable to kink or come in contact with oil grease hot surface...

Страница 2: ... packages use a portable electric heater to get rid of any moisture build up The unit should be stored at least 3 1 2 inches 89 mm off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing Leave coverings loose to permit air circulation and to allow for periodic inspection Aisles between parts and along all walls should be provided to permit air circulation and spa...

Страница 3: ...ns that the motor will never operate in the service factor which is possible with many AC motors Installation Instructions Fig 1 Both ends of the strip are bent over 8 10 cm Protect your hands with gloves Fig 2 Hook the ends through the slots in the bracket Fig 3 Hang on threaded rod or ceiling bracket Note 1 The speed control dial is located on junction box Turn dial for speed adjustments to moto...

Страница 4: ...per wire is disconnected and capped the motor operates at 208 230 277V see Fig 5 Fig 4 115V Operation Fig 5 208 230 277V Operation Speed Control Dial The speed control dial is mounted on the power pack bracket and is to be plugged into the 9 pin connector on the motor To increase speed rotate the dial clockwise To decrease speed rotate the dial counterclockwise From 0 1 9V the motor will be off an...