Mixed Flow FumeJet

3

®

Additional Spring Hanging Isolator

If a hanging spring isolator such as a Kinetics SH is 
needed, a section of the hanging rod, as illustrated 
in the section above, can be replaced with the 
spring isolator housing. Follow the manufacturer’s 
recommended installation procedures.

Electrical and Controls Connections

NOTE

Verify blower motor voltage matches line voltage 110-
120V 50/60 Hz, 208-230/277V 50/60 Hz.

Soft start

All motors feature soft-start technology which eliminates 
inrush current at start-up. The motors will reliably start 
at any speed setting.

Overload protection

If the motor becomes overloaded, it will automatically 
reduce its speed until it is no longer overloaded. This 
means that the motor will never operate in the “service 
factor” which is possible with many AC motors.

Installation Instructions

Fig. 1 Both ends of the 
strip are bent over 8-10 cm. 

Protect your hands with 
gloves.

Fig. 2 Hook the ends 

through the slots in the 
bracket.

Fig. 3 Hang on threaded rod 
or ceiling bracket.

Note 1   The speed control dial is located on junction box. Turn dial for speed adjustments to motor.
Note 2    0-10 VDC fan motor control by others for 0-10 input, speed control dial must be set to 0.

•  0-1.9 VDC fan motors are off
•  2 VDC - minimum speed

 

ƒ

ON threshold (from previous OFF) - 2 VDC

 

ƒ

OFF threshold (from previous ON) - 1.5 VDC

•  10 VDC - Maximum speed

Vari-Green

®

 Motor

The QEID FJ utilizes a Vari-Green

®

 motor. The Vari-

Green motor is an electronically commutated (EC) motor 
that uses AC input power and internally converts it to 
a DC power supply which provides an 80% turndown 
capability and increased energy savings.

Содержание QEID FJ

Страница 1: ...an Electrical Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan rpm Adjustments to fan speed significantly effects motor load 5 Do not allow the power cable to kink or come in contact with oil grease hot surface...

Страница 2: ... packages use a portable electric heater to get rid of any moisture build up The unit should be stored at least 3 1 2 inches 89 mm off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing Leave coverings loose to permit air circulation and to allow for periodic inspection Aisles between parts and along all walls should be provided to permit air circulation and spa...

Страница 3: ...ns that the motor will never operate in the service factor which is possible with many AC motors Installation Instructions Fig 1 Both ends of the strip are bent over 8 10 cm Protect your hands with gloves Fig 2 Hook the ends through the slots in the bracket Fig 3 Hang on threaded rod or ceiling bracket Note 1 The speed control dial is located on junction box Turn dial for speed adjustments to moto...

Страница 4: ...per wire is disconnected and capped the motor operates at 208 230 277V see Fig 5 Fig 4 115V Operation Fig 5 208 230 277V Operation Speed Control Dial The speed control dial is mounted on the power pack bracket and is to be plugged into the 9 pin connector on the motor To increase speed rotate the dial clockwise To decrease speed rotate the dial counterclockwise From 0 1 9V the motor will be off an...

Отзывы: