Microprocessor Controller for MUA
37
®
Appendix E: Points List
Alarm Table - Latest Alarm
0
No Active Alarms
1
Supply Fan Run Status Not Proven
2
Exhaust Fan Run Status Not Proven
3
Filters are Dirty Replace Filters
4
Cond Drain Pan Full Check Drain
5
High Supply Duct Static Pressure
6
Outside Air Temp Sensor Value Not Valid
7
Space Temperature Sensor Value Not Valid
8
Supply Air Temperature Sensor Value Not Valid
9
Outside Air Greentrol Offline or Flow Error
10
Hi/Low Pressure Switch Circuit A
11
Hi/Low Pressure Switch Circuit B
12
Space CO2 Sensor Value Not Valid
13
Return CO2 Sensor Value Not Valid
14
Space Static Pressure Sensor Value Not Valid
15
Supply Duct Stat Press Sensor Value Not Valid
16
Supply Air Temperature Low Limit Shutdown
17
Supply Air Temperature High Limit Shutdown
18
Space High Static Pres Shutdown
19
BMS Offline Watchdog is FALSE
20
BACnet License Not Installed
21
Space Thermostat 1 Sensor Offline
22
Space Thermostat 2 Sensor Offline
23
Space Thermostat 3 Sensor Offline
24
Space Thermostat 4 Sensor Offline
25
IG Furnace 1-No Flame Alarm After 3 Tries
26
IG Furnace 1 - Large No Flame After 3 Tries
Alarm Table - Latest Alarm
(cont.)
27
IG Furnace 1 Combust Fan High Pressure Sw
28
IG Furnace 1 Ignition Controller Alarm
29
IG Furnace 1 Pressure Switch Fault Alarm
30
IG Furnace 1 Combust Fan Proving Alarm
31
IG Furnace 1 Max Retrys
32
IG Furnace 1 High Limit Trip
33
IG Furnace pCOe 1 Offline
34
IG Furnace 1 IC Fault Check IC->pCOe Wiring
35
IG Furnace 1 Combustion Fan Alarm
36
IG Furnace pCOe 2 Offline
37
IG Furnace 2-No Flame Alarm After 3 Tries
38
IG Furnace 2 Max Retrys
39
IG Furnace 2 Ignition Controller Alarm
40
IG Furnace 3-No Flame Alarm After 3 Tries
41
IG Furnace 3 Max Retrys
42
IG Furnace 3 Ignition Controller Alarm
43
DG Flame Safeguard General Reference
44
DG Flame Safeguard Manual Reset at FSG
45
DG Pilot Flame Alarm Did Not Prove
46
DG Heating Safety Check Circuit
47
DG Flame Safeguard Check Functionality
48
DG Burner Differential Check Pressure
51
Multi Devices per Ch Contact Tech Support
52
Comp Maint Alarm Run Hours Spt Reached
54
Non-Volatile Memory Er Contact Tech Support
55
Cooling Exp Board pCOe 3 Offline
59
Exp Board 4 Status Board is Offline