background image

10

MAINTENANCE

Greenheck recommends these procedures to insure trouble free operation of this unit. It is especially important to
maintain heater units for clean and efficient operation. Most unit failures can be attributed to poor setup or poor
maintenance.

A record of maintenance performed on this unit should be kept. This information will provide essential information
if problems are encountered. A section at the back of this manual is provided for recording the unit's maintenance
history.

CAUTION: When performing any maintenance on this unit be
sure that the power is disconnected and cannot be
accidentally turned on. The control center disconnect can be
locked in the off position.

2 weeks after startup 

Check belt tension

- Belts tend to stretch after a period of time.

They should be periodically checked for wear and tightness.

Approximately 

3

8

in. of deflection per ft. of span between

sheaves is standard for belt tightness.

When replacing belts,

use the same type as supplied with the unit. Matched belts should
always be used on units with multigroove pulleys. 

Replacement of belts

- should be accomplished by loosening the motor to the point where the belts can be

removed by hand. Do not force belts on or off as this may cause breakage of cords leading to premature belt
failure. Belts should be adjusted as above.

Every 3 Months

The filter in the unit should be inspected at least every 3 months. Depending on the environment filters could
require changing or cleaning more or less often. The filters can be slid out of either side of the unit. 

If 

washable filters

are installed, they can be washed in warm soapy water. An adhesive spray can be applied to

increase filter efficiency.

If 

disposable filters

are installed, check by holding up to a light source. If light cannot pass through the filter, it

should be replaced. Replacement filters should be of the same manufacturer and size.  When reinstalling filters, be
sure to install with the airflow in the correct direction indicated on the filter.

Yearly

Most 

bearings

are permanently lubricated and require no further lubrication under normal use. Normal use being

considered -20°F to 120°F and in a relatively clean environment. Some bearings are re-lubricatable and will need
to be regreased depending on fan use. Check you bearings for grease zert to find out what type of bearing you
have. If your fan is not being operated under normal use, bearings should be checked monthly for lubrication.

Motor

maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited

to the exterior surfaces only. Removing dust and grease build-up on motor housing assures proper motor cooling.
Greasing of motors is intended only when grease fittings are provided. Many fractional motors are permanently
lubricated and require no further lubrication. Motors supplied with grease fittings should be greased in
accordance with manufacturer's recommendations. When motor temperature does not exceed 104°F (40°C), the
grease should be replaced after 2000 hours of running time as a general rule.

Wheels

require very little attention when moving clean air. Occasionally oil and dust may accumulate on the wheel

causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and safe
operation. Inspect fan impeller and housing for fatigue, corrosion or wear

Routinely check all

fasteners, set screws and locking collars on the fan, bearing, drive, motor base and

accessories 

for tightness.

Belt Span

Deflection = 

Belt Span

64

NOTE: For motors of 1 hp or less a smaller sliding base

bracket is used to attach to blower.

10

Содержание MSCF

Страница 1: ...items are stored inside the unit during shipping Care must be taken during installation to prevent damage to units MODEL MSCF Modular Small Cabinet Fan Installation Operation and Maintenance Manual W...

Страница 2: ...ows panels removed 9 1 1 4 in knockout for recommended electrical wiring penetration or disconnect switch 8 8 8 8 8 7 9 Table of Contents Unit Layout Table of Parts Lifting Hanging Instructions Modula...

Страница 3: ...to avoid damage see figure 1 Figure 1 3 Frame Rails By others Spreader bar Lifting lugs The MSCF should be hung by the factory supplied lifting lugs or field supplied frame rails as shown respectivel...

Страница 4: ...26 38 2 5 3 5 43 45 6 75 26 18 5 6 75 6 75 26 6 6 75 26 50 2 5 3 5 55 50 6 75 26 18 5 6 75 6 75 26 6 6 75 32 50 2 5 3 5 55 65 6 75 32 18 5 6 75 6 75 28 6 6 75 36 50 2 5 3 5 55 85 6 75 32 18 5 6 75 6...

Страница 5: ...nit A B C D E F Size w o Filter w Filter 12 in 24 in Vertical Sloped Hot Water CW DX Fan Motor Total 15 80 107 31 57 34 61 61 145 94 50 144 20 95 126 36 68 41 72 72 171 111 50 161 25 105 140 40 75 45...

Страница 6: ...same as 4 row chilled water coil data see below Fluid enters the coil from the bottom connection In and exits from the top Out In Out Out In NOTE With airflow from left to right the fluid enters the...

Страница 7: ...nnection between the scroll and the discharge of the fan If noise is an issue we recommend using heavy canvas connections on the inlet of the fan Refer to the Troubleshooting section of this manual if...

Страница 8: ...g good duct practices Blower speed too low Check for correct drives and RPMs with catalog data Mixing box dampers closed Open and adjust Dirty or clogged filters Clean or replace Leaks in ductwork Rep...

Страница 9: ...n of water coils with low entering air conditions CONTINUOUS WATER CIRCULATION THROUGH THE COIL AT ALL TIMES IS HIGHLY RECOMMENDED 5 Pipe sizes for the system must be selected on the basis of the head...

Страница 10: ...ilters are installed check by holding up to a light source If light cannot pass through the filter it should be replaced Replacement filters should be of the same manufacturer and size When reinstalli...

Страница 11: ...build up from plugging the drain and causing the drain pan to overflow Inspect twice a year to avoid the possibility of overflow Also drain pans should be kept clean to prevent the spread of disease C...

Страница 12: ...Up Documentation Actual Voltage Hertz Phase Actual Amperage Blower Rotation Correct Air Volume Design cfm Actual cfm Drive Level of fan L or H Fan RPM Range min max 462888 MSCF IOM APRIL 2003 Warrant...

Отзывы: