Greenheck FSD-311V Скачать руководство пользователя страница 3

These instructions apply to 1

1

/

2

 hour rated combination fire smoke dampers mounted (blades must be vertical) in: masonry, 

block, or stud walls. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with 
these instructions to meet the requirements of UL555 and UL555S. The installation of the damper and all duct connections 
to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning 
and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications 
R13317.

Installation -

 

Failure to follow these instructions will void all warranties.

Example: A 12 in. x 12 in. (305mm x 305mm) damper 

would require a minimum clearance of 

1

/

4

 in. (6mm.)

 A 36 in. x 12 in. (914mm x 350mm) damper would require 
a minimum clearance of 

1

/

2

 in.  (13mm) on width and 

1

/

4

 in. 

(6mm) on height.

Clearance for Expansion
(1/4in. Min, 1 1/2in. Max.)

Retaining Angles
(See Section 4)

6 in. max.

Detail 1

(Located on Bottom of Damper)

Airlfow

Sleeve Length (L)

16 in. max

"A" Dim.

(Distance from

end of Sleeve to

Face of Damper)

Actuator

Damper

Sleeve

Standard RRL Control Device

with Optional Blade Indication

Jackshaft

Tw

Line of Wall

Do not install screws
between these lines
around entire damper

Fig. 1

1.  

CLEARANCES REQUIRED BETWEEN FIRE DAMPER 
SLEEVES AND WALL/FLOOR OPENINGS

   Fire damper and sleeve assemblies expand during 

periods of intense heat. Therefore, it is essential that 
openings in walls or floors be larger than the fire damper 
and sleeve assembly to allow for this expansion. 
Minimum clearances required between the outside of fire 
damper sleeve assemblies and wall/floor openings are:

 

•  Galvanized steel fire dampers and sleeves: 

1

8

 in. 

(3mm) per foot of damper width and height with a 
minimum clearance of 

1

4

 in. (6mm), maximum of 1 

1

2

 

in. (38mm).

 

 Recommended

 clearances, for width and/or height 

dimensions of:

 

1) 36 in. (914mm) or less: 

1

2

 in. (13mm) clearance

These are total clearances (ignoring fastener heads) and do 
not need to be equally spaced around the damper.

2. SLEEVE LENGTH AND WALL THICKNESS
  

Insert the sleeved damper assembly into the prepared 
opening, to appropriate depth (refer to label on outside 
of sleeve for location of damper in wall; see Dimension A 
and Detail 1, 

Fig. 1

).

   Recommended maximum and minimum insertion depth 

can be exceeded if:

  1) The operation of the damper is not impeded and
 

2)   The  CL of the damper frame remains within the plane of 

the wall and

  3)  Attachments made through the retaining angle do 

not penetrate the ‘No Screw’ area designated on the 
damper sleeve.

   IMPORTANT SAFETY DANGER! :

 To avoid causing 

death or serious bodily harm to building occupants, do 
not penetrate the ‘No Screw’ area designated on the 
damper sleeve or the damper may not close properly.

   The sleeve may extend a maximum of 16 in. beyond the 

wall on the actuator side of the damper and a maximum 
of 6 in. on the opposite side. Recommended standard 
sleeve lengths for various wall thicknesses are:

Clearance for Expansion
(1/4in. Min, 1 1/2in. Max.)

Retaining Angles
(See Section 4)

6 in. max.

Detail 1

(Located on Bottom of Damper)

Airlfow

Sleeve Length (L)

16 in. max

"A" Dim.

(Distance from

end of Sleeve to

Face of Damper)

Actuator

Damper

Sleeve

Standard RRL Control Device

with Optional Blade Indication

Jackshaft

Tw

Line of Wall

Do not install screws
between these lines
around entire damper

3

Wall Thickness  
Dimension (T

W

)

Sleeve Length

Dimension (L)

4 - 6 in. 

 (102mm - 152mm)

16 in.

(406mm)

7 - 10 in.

(178mm - 254mm)

21 in.

(533mm)

11 - 13 in.

(279mm - 330mm)

24 in.

(610mm)

3. DUCT TO SLEEVE CONNECTIONS

  

Dampers are supplied with sleeves and actuators from 
the factory and can be installed without the need for 
additional field installed sleeves.

   Gauge of factory furnished sleeve determines the type 

of duct to sleeve connections required (see table below). 
Any duct connection other than those breakaway 
connections described on page 6 are considered rigid. 
Factory furnished duct collars, type R and O, are also 
considered breakaway (see 

Fig. 2

).

 

Содержание FSD-311V

Страница 1: ...n in accordance with combination fire smoke damper requirements established by National Fire Protection Association NFPA Standards 80 90A 92A 92B 101 105 IBC International Building Codes New York City MEA listing 260 91 M California State Fire Marshal Listing 3225 0981 103 and 3230 0981 104 Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found re...

Страница 2: ...installed into duct or opening square and free of twist or other misalignment Damper must not be squeezed or stretched into duct or opening Out of square racked twisted or misaligned installations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and afte...

Страница 3: ...s of 1 36 in 914mm or less 1 2 in 13mm clearance These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper 2 SLEEVE LENGTH AND WALL THICKNESS Insert the sleeved damper assembly into the prepared opening to appropriate depth refer to label on outside of sleeve for location of damper in wall see Dimension A and Detail 1 Fig 1 Recommended maximum and mi...

Страница 4: ...Type R and O Factory Furnished Duct Collars Qualify As Breakaway Connections Duct Damper Sleeve Wall or Floor Type C O R Fig 2 Damper with type R or O transition factory furnished 2 in Max 6 in Max Sleeve Retaining Angle Damper Duct Min 1 in Overlap Wall or Floor Retaining Angle only applicable for damper sizes above 36 in x 36 in 6 in Max 2 in Max Both vertical and horizontal damper installations...

Страница 5: ...I option TOR The TOR temperature override device option incorporates two thermostats with fixed settings usually 165 F 74 C and 350 F 177 The primary sensor the sensor with the lower temperature setting can be bypassed by an external electrical signal allowing the damper to reopen until the temperature reaches the setting of the secondary sensor the sensor with the higher temperature setting When ...

Страница 6: ...al Stud Construction Wooden Stud Construction In wood stud construction gypsum wallboard must cover all wood stud surfaces Gypsum Wallboard Stud or Runner Retaining Angle 1 in Min Damper Sleeve In metal stud construction exposed steel surfaces need not be covered with gypsum wallboard Gypsum Wallboard Stud or Runner Retaining Angle 1 in Min Damper Sleeve Fig 8 7 RECOMMENDED PREPARATION OF OPENINGS...

Страница 7: ...ce with SMACNA recommendations Drive Slip Joint Fig 11 Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Fig 12 Fire Damper Sleeve Neoprene gasket between all angles Flanged system angles Attach per manufacturer s instructions Duct Do not bolt corners 6 in long 1 16in max thickness plastic cleat...

Страница 8: ...causing blades to bind on jamb seals Adjust frame such that it is square and plumb Actuator linkage loose Close damper disconnect power adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance RRL or TOR sensor tripped...

Отзывы: