Greenheck FSD-311V Скачать руководство пользователя страница 2

Table of Contents

Pre-Installation Guidelines ................................................................................................................................ 2 
Electrical Guidelines .......................................................................................................................................... 2 
Installation ......................................................................................................................................................3-7
 

• Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ............................ 3 

 

• Sleeve Length and Wall Thickness ................................................................................................... 3 

 

• Duct to Sleeve Connections ...........................................................................................................3-4 

 

• Securing the Damper/Sleeve Assembly to Wall and Floor Openings ............................................ .4 

 

• Actuator Connections ..................................... ...................................................................................4 

 

• Connection and Operation of Temperature Control Devices .......................................................... 5 

 

• Recommended Preparation of Openings in Wood and Metal Stud Walls ...................................... 6 

 

• Breakaway Connections ................................................................................................................... 7

Maintenance ...................................................................................................................................................... 8
Troubleshooting ................................................................................................................................................. 8

Pre-Installation Guidelines

The basic intent of a proper installation is to secure the 
fire or fire smoke damper in, not to, the opening in such a 
manner as to prevent distortion and disruption of damper 
operation. This is accomplished by allowing the fire or fire 
smoke damper in rated separation openings to expand 
and for the connecting duct to separate in the event of the 
collapse of the hanging system. The following items will 
aid in completing the damper installation in a timely and 
effective manner.
1)   Check the schedules for proper damper locations 

within the building. Visually inspect the damper for 
damage and verify that the Reusable Resettable Link 
(RRL) is in place or has not activated. Never install a 
fire damper without the proper UL approved RRL in 
place. (RRL is standard control option. These electric 
links have a button for resetting.) If damper is furnished 
with fusible link, visually inspect the link to verify its not 
missing or broken. Replace link as necessary.

2)   Lift or handle damper using sleeve or frame. Do not lift 

damper using blades or actuators.

3)   Damper has label on outside of sleeve indicating a 

‘No Screw’ area. Do not install screws into this area as 
screws may interfere with unexposed blade linkage and 
prevent damper blades from opening and/or closing.

4)   Damper has label indicating position of damper 

and sleeve assembly in the wall. Install accordingly 
to comply with manufacturer’s appropriate UL 
Classification file number.

5)   Damper must be installed into duct or opening square 

and free of twist or other misalignment. Damper must 
not be squeezed or stretched into duct or 

opening. Out of square, racked, twisted or misaligned 
installations can cause excessive leakage and/or torque 
requirements to exceed damper/actuator design.
6)   Damper and actuator must be kept clean and protected 

from dirt, dust and other foreign materials prior to and 
after installation. Examples of such foreign materials 
include but are not limited to:

 

a) Mortar dust 

 

b) Drywall dust 

 

c) Firesafing materials 

 

d) Wall texture 

 

e) Paint overspray

7)   Damper should be sufficiently covered as to prevent 

overspray if wall texturing or spray painting will be 
performed within 5 feet of the damper. Excessive dirt 
or foreign material deposits on damper can cause 
excessive leakage and/or torque requirements to 
exceed damper/actuator design.

8)   Caulking is not necessary, nor is it allowed, between the 

damper sleeve and the wall or floor opening (annular 
space). However, caulking may be applied to the 
retaining angles.

9)   ACCESS: Suitable access (such that RRL’s and 

actuators can be maintained, etc.) must be provided 
for damper inspection and servicing. Where it is not 
possible to achieve sufficient size access, it will be 
necessary to install a removable section of duct. (Refer 
to NFPA 90A).

10)   The Code Authority Having Jurisdiction (AHJ) must 

evaluate and provide approval of final installation where 
variations to these instructions are necessary.

Electrical Guidelines

All wiring shall be done in accordance with the National 
Electrical Code ANSI/NFPA-70 latest edition, any local 
codes that may apply, and wiring diagrams developed 
in compliance with the job or project design and 
specifications. 

Safety Caution!

Electrical input may be needed for this equipment. This 
work should be performed by a qualified electrician. 
Verify power before wiring actuator. Greenheck is not 
responsible for any damage to, or failure of the unit 
caused by incorrect field wiring. To avoid causing death 
or serious bodily harm to building occupants, follow all 
instructions carefully. Dampers must close completely to 
preserve the integrity of the fire smoke separation.

Electrical Guidelines

2

Содержание FSD-311V

Страница 1: ...n in accordance with combination fire smoke damper requirements established by National Fire Protection Association NFPA Standards 80 90A 92A 92B 101 105 IBC International Building Codes New York City MEA listing 260 91 M California State Fire Marshal Listing 3225 0981 103 and 3230 0981 104 Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found re...

Страница 2: ...installed into duct or opening square and free of twist or other misalignment Damper must not be squeezed or stretched into duct or opening Out of square racked twisted or misaligned installations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and afte...

Страница 3: ...s of 1 36 in 914mm or less 1 2 in 13mm clearance These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper 2 SLEEVE LENGTH AND WALL THICKNESS Insert the sleeved damper assembly into the prepared opening to appropriate depth refer to label on outside of sleeve for location of damper in wall see Dimension A and Detail 1 Fig 1 Recommended maximum and mi...

Страница 4: ...Type R and O Factory Furnished Duct Collars Qualify As Breakaway Connections Duct Damper Sleeve Wall or Floor Type C O R Fig 2 Damper with type R or O transition factory furnished 2 in Max 6 in Max Sleeve Retaining Angle Damper Duct Min 1 in Overlap Wall or Floor Retaining Angle only applicable for damper sizes above 36 in x 36 in 6 in Max 2 in Max Both vertical and horizontal damper installations...

Страница 5: ...I option TOR The TOR temperature override device option incorporates two thermostats with fixed settings usually 165 F 74 C and 350 F 177 The primary sensor the sensor with the lower temperature setting can be bypassed by an external electrical signal allowing the damper to reopen until the temperature reaches the setting of the secondary sensor the sensor with the higher temperature setting When ...

Страница 6: ...al Stud Construction Wooden Stud Construction In wood stud construction gypsum wallboard must cover all wood stud surfaces Gypsum Wallboard Stud or Runner Retaining Angle 1 in Min Damper Sleeve In metal stud construction exposed steel surfaces need not be covered with gypsum wallboard Gypsum Wallboard Stud or Runner Retaining Angle 1 in Min Damper Sleeve Fig 8 7 RECOMMENDED PREPARATION OF OPENINGS...

Страница 7: ...ce with SMACNA recommendations Drive Slip Joint Fig 11 Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Fig 12 Fire Damper Sleeve Neoprene gasket between all angles Flanged system angles Attach per manufacturer s instructions Duct Do not bolt corners 6 in long 1 16in max thickness plastic cleat...

Страница 8: ...causing blades to bind on jamb seals Adjust frame such that it is square and plumb Actuator linkage loose Close damper disconnect power adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance RRL or TOR sensor tripped...

Отзывы: