When a combination fire smoke damper is being used in conjunction with round or oval ductwork, the FSD-212 can be 
supplied in a factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the 
duct dimensions. Drawings below show overall damper size.

*

These dimensions are furnished approximately 

1

/

4

 in. (6mm) 

undersize, except round and oval  dimensions which are 
approximately 

1

/

8

 in.(3mm) undersize.

Ts = (2)(Sleeve Thickness)

D* + 2 in. (51mm) +Ts

D*

TYPE  R

16 in.

 (406mm) 

Minimum

16 in.

 (406mm) 

Minimum

16 in.

 (406mm) 

Minimum

D* +  2 in. (51mm)+Ts

TYPE  O

W*

H*

W*

 

+ 2 in. (51mm)+Ts

H* + 2 in. (51mm)+T

s

W*

H*

TYPE  C

 

H* + 2 in. (51mm)+Ts

W* + 2 in. (51mm)+Ts

2 1/8 in.

(54mm)

2 1/8 in.

(54mm)

2 1/8 in.

(54mm)

Transitioned Damper Dimensions 

FSD-212

Combination Fire Smoke Dampers meeting the following 
specifications shall be furnished and installed where 
shown on plans and/or as described in schedules. 
Dampers shall meet the requirements of NFPA 80, 90A, 
92A, 92B, 101 & 105 and further shall be tested, rated 
and labeled in accordance with the latest edition of UL 
Standards 555 and 555S.  Dampers shall have a UL555 
fire rating of 1½ hours and be of low leakage design 
qualified to UL 555S Leakage Class II.
Each damper /actuator combination shall have a UL555S 
elevated temperature rating of 250°F (121°C) minimum 
and shall be operational and dynamic rated to operate 
at maximum design air flow at its installed location. Each 
damper shall be supplied with an appropriate actuator 
installed by the damper manufacturer at the time of 
damper fabrication. Damper actuator shall be (specifier 
select one of the following) electric type for 120, 24, or 
230 volt operation or pneumatic type for 25 psi minimum 
(30 psi maximum) operation.
Damper blades shall be 16 ga. (1.5mm) galvanized steel 
3V type with three longitudinal grooves for reinforcement. 
Damper frame shall be galvanized steel formed into a 
structural hat channel shape with reinforced corners. 

Bearings shall be 304SS type rotating in extruded holes 
in the damper frame. Blade edge seals shall be silicone 
rubber designed to inflate and provide a tighter seal 
against leakage as pressure on either side of the damper 
increases. Jamb seals shall be stainless steel compression 
type. Blades shall be completely symmetrical relative to 
their axle pivot point, presenting identical resistance to 
airflow in either direction or pressure on either side of the 
damper.
The Damper Manufacturer's submittal data shall certify 
all air performance pressure drop data is licensed in 
accordance with the AMCA Certified Ratings Program for 
Test Figures 5.2, 5.3, and 5.5. Damper air performance 
data shall be developed in accordance with the latest 
edition of AMCA Standard 500-D. Dampers shall be 
labeled with the AMCA Air Performance Seal.
Damper must be rated for mounting vertically (with blades 
running horizontal) or horizontally and be UL 555S rated 
for leakage and airflow in either direction through the 
damper. Each damper shall be supplied with a 165°F 
(74°C) RRL.
The basis of design is Greenheck Model FSD-212.

Specifications

Содержание FSD-212

Страница 1: ... out of airstream concealed in jamb Axle Bearings 304SS Axle Material Plated steel Blade Seals Silicone Jamb Seals 304SS Closure Device RRL RRL OCI TOR PRV or Fusible Link Closure Temperature 165 F 74 C 212 F 100 C 250 F 121 C 350 F 177 C Features Frames are constructed with reinforced corners Low profile head and sill are used on sizes less than 17 in high 432mm Blades are a double skin airfoil w...

Страница 2: ...eam and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because entrance losses are minimized by a straight duct run upstream of the damper Figure 5 5 Illustrates a plenum mounted damper This configuration has the highest pressure drop because of extremely high entrance and exit losses due...

Страница 3: ... 14 Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 02 500 0 01 500 0 01 500 0 01 1000 0 09 1000 0 04 1000 0 03 1000 0 04 1500 0 20 1500 0 09 1500 0 06 1500 0 10 2000 0 36 2000 0 16 2000 0 11 2000 0 17 2500 0 56 2500 0 25 2500 0 17 2500 0 27 3000 0 81 3000 0 35 3000 0 24 3000 0 39 3500 1 10 3500 0 48 3500 0 3...

Страница 4: ...120 S Belimo 31 2 in 89mm 0 6 in 152mm NA ML4XXX Series Honeywell 43 4 in 121mm 0 6 in 152mm NA MS4X09 Series Honeywell 43 4 in 121mm 0 6 in 152mm NA MS4120 Series Honeywell 123 4 in 324mm 0 6 in 152mm 9 in 229mm GND 22X 1 Siemens 123 4 in 324mm 0 6 in 152mm NA 24 Volt AC FSAF24 S Belimo 123 4 in 324mm 0 6 in 152mm NA FSLF24 S Belimo 31 2 in 89mm 0 6 in 152mm NA FSNF24 S Belimo 123 4 in 324mm 0 6 ...

Страница 5: ... within a range of 6 in 152mm to 12 in 305mm for the A dimension Application Data FSD 212 50 in 32 in 813mm 32 in 813mm 64 in 1626mm 50 in 1270mm 1270mm 50 in 1270mm Single Section Double Section Damper Sizing Information Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size The following figures show maximum damper section size an...

Страница 6: ...ocation Each damper shall be supplied with an appropriate actuator installed by the damper manufacturer at the time of damper fabrication Damper actuator shall be specifier select one of the following electric type for 120 24 or 230 volt operation or pneumatic type for 25 psi minimum 30 psi maximum operation Damper blades shall be 16 ga 1 5mm galvanized steel 3V type with three longitudinal groove...