Greenheck FSD-212 Скачать руководство пользователя страница 3

Pressure Drop 

FSD-212

5D

6D

5D

Figure 5.3

Figure 5.2

Figure 5.5

D=

4 (W) (H)

3.14

R

Greenheck Fan Corporation certifies that the 
model FSD-212 shown herein is licensed to bear 
the AMCA Seal. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 511 and comply with the 
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to 
air performance ratings only. 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.04 

500

0.02 

500

0.01 

500

0.01 

1000 

0.14 

1000

0.07 

1000

0.04 

1000

0.06 

1500

0.31

1500

0.16

1500

0.09 

1500

0.13 

2000

0.55

2000

0.29

2000

0.16

2000

0.23 

2500 

 

0.86

2500

0.45

2500

0.25

2500

0.36 

3000

1.24

3000

0.65 

3000

0.36

3000

0.52

3500

1.69

3500

0.89

3500

0.49

3500

0.70 

4000

2.20

4000

1.16

4000

0.64

4000

0.92

12 in. x 12 in. (305mm x 305mm) 

24 in. x 24 in. (610mm x 610mm) 

36 in. x 36 in. (914mm x 914mm) 

12 in. x 48 in. (305mm x 1219mm) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.03 

1000

0.10

1500

0.23 

2000

0.41

2500

0.63

3000

0.91

3500

1.24

4000

1.62

48 in. x 12 in. (1219mm x 305mm) 

AMCA Figure 5.2

AMCA Figure 5.3

AMCA Figure 5.5

5D

6D

5D

Figure 5.3

Figure 5.2

Figure 5.5

D=

4 (W) (H)

3.14

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.02 

500

0.01 

500

0.01 

500

0.01 

1000

0.09 

1000

0.04 

1000

0.03 

1000

0.04 

1500

0.20

1500

0.09 

1500

0.06 

1500

0.10 

2000

0.36

2000

0.16 

2000

0.11 

2000

0.17 

2500

0.56

2500

0.25 

2500

0.17 

2500

0.27 

3000

0.81

3000

0.35

3000

0.24

3000

0.39

3500

1.10 

3500

0.48

3500

0.33 

3500

0.53

4000

1.44

4000

0.63 

4000

0.42

4000

0.70 

12 in. x 12 in. (305mm x 305mm) 

24 in. x 24 in. (610mm x 610mm) 

36 in. x 36 in. (914mm x 914mm) 

12 in. x 48 in. (305mm x 1219mm) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.02 

1000

0.07

1500

0.16 

2000

0.29

2500

0.45 

3000

0.64

3500

0.88

4000

1.14

48 in. x 12 in. (1219mm x 305mm) 

5D

6D

5D

D

4 (W) (H)

3.14

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.06

500

0.03

500

0.03 

500

0.03 

1000

0.22 

1000

0.14 

1000

0.12 

1000

0.13 

1500

0.50

1500

0.31

1500

0.26

1500

0.30 

2000 

0.89 

2000

0.54

2000

0.46

2000

0.53

2500

1.39

2500

0.85

2500

0.73

2500

0.83

3000

2.00

3000

1.22

3000

1.05

3000

1.19

3500

2.72

3500

1.66

3500

1.42 

3500

1.62

4000

3.55

4000

2.17

4000

1.86

4000

2.11

12 in. x 12 in. (305mm x 305mm) 

24 in. x 24 in. (610mm x 610mm) 

36 in. x 36 in. (914mm x 914mm) 

12 in. x 48 in. (305mm x 1219mm) 

Velocity (fpm) 

Pressure Drop  

(in. wg) 

500

0.04 

1000

0.17 

1500

0.38 

2000

0.67

2500

1.04

3000

1.50

3500

2.05

4000

2.67 

48 in. x 12 in. (1219mm x 305mm) 

Содержание FSD-212

Страница 1: ... out of airstream concealed in jamb Axle Bearings 304SS Axle Material Plated steel Blade Seals Silicone Jamb Seals 304SS Closure Device RRL RRL OCI TOR PRV or Fusible Link Closure Temperature 165 F 74 C 212 F 100 C 250 F 121 C 350 F 177 C Features Frames are constructed with reinforced corners Low profile head and sill are used on sizes less than 17 in high 432mm Blades are a double skin airfoil w...

Страница 2: ...eam and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because entrance losses are minimized by a straight duct run upstream of the damper Figure 5 5 Illustrates a plenum mounted damper This configuration has the highest pressure drop because of extremely high entrance and exit losses due...

Страница 3: ... 14 Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 02 500 0 01 500 0 01 500 0 01 1000 0 09 1000 0 04 1000 0 03 1000 0 04 1500 0 20 1500 0 09 1500 0 06 1500 0 10 2000 0 36 2000 0 16 2000 0 11 2000 0 17 2500 0 56 2500 0 25 2500 0 17 2500 0 27 3000 0 81 3000 0 35 3000 0 24 3000 0 39 3500 1 10 3500 0 48 3500 0 3...

Страница 4: ...120 S Belimo 31 2 in 89mm 0 6 in 152mm NA ML4XXX Series Honeywell 43 4 in 121mm 0 6 in 152mm NA MS4X09 Series Honeywell 43 4 in 121mm 0 6 in 152mm NA MS4120 Series Honeywell 123 4 in 324mm 0 6 in 152mm 9 in 229mm GND 22X 1 Siemens 123 4 in 324mm 0 6 in 152mm NA 24 Volt AC FSAF24 S Belimo 123 4 in 324mm 0 6 in 152mm NA FSLF24 S Belimo 31 2 in 89mm 0 6 in 152mm NA FSNF24 S Belimo 123 4 in 324mm 0 6 ...

Страница 5: ... within a range of 6 in 152mm to 12 in 305mm for the A dimension Application Data FSD 212 50 in 32 in 813mm 32 in 813mm 64 in 1626mm 50 in 1270mm 1270mm 50 in 1270mm Single Section Double Section Damper Sizing Information Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size The following figures show maximum damper section size an...

Страница 6: ...ocation Each damper shall be supplied with an appropriate actuator installed by the damper manufacturer at the time of damper fabrication Damper actuator shall be specifier select one of the following electric type for 120 24 or 230 volt operation or pneumatic type for 25 psi minimum 30 psi maximum operation Damper blades shall be 16 ga 1 5mm galvanized steel 3V type with three longitudinal groove...