background image

Stationary, Non-Drainable Blade Louver Models

7

®

Multiple Section Wide x Single Section High Installation - Supported

1.  Locate the optional extended sill, if provided, and 

place in the opening. 

(Extended Sill Details)

2.  Locate mounting angles and fasteners required to 

attach the louver to the structure. Clip angles and 
fasteners are by others unless the optional mounting 
angles have been ordered from manufacturer with 
the louvers. Anchors to the structure are by others 
and are not manufacturer provided.  

(Mounting Clip Details)

3.  Place the left louver section (as viewed from the 

exterior) in the opening and shim around the 
perimeter to maintain proper spacing for backer rod 
and caulk joint. 

4.  Using the appropriate fasteners, secure the 

mounting angles to the back of the louver frame at 
the perimeter. 

5.  Ensure the louvers is level and in the correct 

location within the opening and secure the mounting 
angles to the structure using the correct anchor (by 
others) for the building substrate material. 

6.  Place the next louver section to the right of the 

first louver section and repeat steps 3-5 above to 
secure the louver to the structure. Follow the same 
procedure for any additional sections to the right.

7.  Install additional structural supports (not by 

manufacturer) at the vertical louver mullions. Secure 
the louver frame to the structural support with the 
appropriate mounting angles and/or anchors (not by 
manufacturer).

8.  Once the louver assembly is secured to the 

structure, install backer rod and caulk around the 
perimeter of the opening at the front of the louver as 
well as the mullion joint between the louver jambs.

Figure 4.1

Figure 4.2

Figure 4.3 

Structural Reinforcing (by others) 

Figure 4.4

Содержание ESJ-202

Страница 1: ...s and hidden damage If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Check to be sure that all parts of the shipment including accessories are accounted for Safety Warning Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instru...

Страница 2: ...ouvers will ship fully assembled Multiple section assemblies will ship as individual louver sections to be combined into the larger assembly at installation Large multiple section louver assemblies may ship in multiple crates 5 All louver sections will have a factory applied louver label affixed This label will identify the louver size and a Tag identification if one was provided during the order ...

Страница 3: ...nd are not manufacturer provided Mounting Clip Details 3 Place the louver in the opening and shim around the perimeter to maintain proper spacing for backer rod and caulk joint 4 Using the appropriate fasteners secure the mounting angles to the back of the louver frame at the perimeter 5 Ensure the louvers is level and in the correct location within the opening and secure the mounting angles to th...

Страница 4: ...ll Details 4 Locate mounting angles and fasteners required to attach the louver to the structure Clip angles and fasteners are by others unless the optional mounting angles have been ordered from manufacturer with the louvers Anchors to the structure are by others and are not manufacturer provided Mounting Clip Details 5 Place the louver in the opening and shim around the perimeter to maintain pro...

Страница 5: ...s not required reference the Multiple Section Wide and Single Section High Unsupported installation instructions If additional support is required reference the Multiple Section Wide and Single Section High Supported installation instructions ESJ 202 ESJ 401 and ESK 402 Section Width In Maximum Unsupported Height At 25 PSF Wind Load In 36 90 48 78 60 70 72 66 84 58 96 54 108 52 120 48 Table 1 1 ES...

Страница 6: ...he perimeter to maintain proper spacing for backer rod and caulk joint 4 Using the appropriate fasteners secure the mounting angles to the back of the louver frame at the perimeter 5 Ensure the louvers is level and in the correct location within the opening and secure the mounting angles to the structure using the correct anchor by others for the building substrate material 6 Place the next louver...

Страница 7: ... to the back of the louver frame at the perimeter 5 Ensure the louvers is level and in the correct location within the opening and secure the mounting angles to the structure using the correct anchor by others for the building substrate material 6 Place the next louver section to the right of the first louver section and repeat steps 3 5 above to secure the louver to the structure Follow the same ...

Страница 8: ...ouver to the structure Clip angles and fasteners are by others unless the optional mounting angles have been ordered from manufacturer with the louvers Anchors to the structure are by others and are not manufacturer provided Mounting Clip Details 5 Place the combined left louver section assembly as viewed from the exterior in the opening and shim around the perimeter to maintain proper spacing for...

Страница 9: ...Stationary Non Drainable Blade Louver Models 9 Multiple Section Wide x Multiple Section High Installation Continued Figure 5 3 Structural Reinforcing by others Figure 5 4 IOM 468788 IOM 468788 ...

Страница 10: ...n of the website at Greenheck com Resources Library Literature Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com Our Commitment AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca ...

Отзывы: