background image

26

Energy Recovery Ventilator

Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or 
service information.

Symptom

Possible Cause

Corrective Action

Blower fails to 

operate

Blown fuse or open circuit breaker.

Replace fuse or reset circuit breaker and check 
amps.

Defective motor or capacitor.

Replace.

Motor starter overloaded.

Reset starter and check amps.

Electrical.

Check for On/Off switches. Check for correct 
supply voltage.

Drive.

Check for broken or loose belts. Tighten loose 
pulleys.

Motor starters 

“chatter” or 

do not pull in

Control power (24 VAC) wiring run is too long 
(resistance should not exceed 0.75 ohms).

Shorten wiring run to mechanical room or 
install a relay which will turn unit on/off. Consult 
Factory for relay information.

Incoming supply power is less than anticipated. 
Voltage supplied to starter coil must be within 
+10% / -15% of nominal voltage stated on the coil.

Need to increase supply power or use a special 
control transformer which is sized for the actual 
supply power.

Motor over amps

CFM too high.

Check cfm and adjust drives if needed.

Static pressures are higher or lower than 
design.

If higher, ductwork should be improved.
If lower, fan rpm should be lower.

Blower rotation is incorrect.

Check rotation and reverse if necessary.

Motor voltage incorrect.

Check motor nameplate versus supplied 
voltage.

Motor horsepower too low.

See specifications and catalog for fan curves to 
determine if horsepower is sufficient.

Shorted windings in motor.

Replace motor.

Low airflow (cfm)

Unit damper not fully open.

Adjust damper linkage or replace damper motor.

System static pressure too high.

Improve ductwork to eliminate losses using 
good duct practices.

Blower speed too low.

Check for correct drives and rpm with catalog 
data.

Fan wheels are operating backwards.

For 3-phase, see Direction of Fan Wheel 
Rotation under Unit Start-Up section.

Dirty filter or energy wheel.

Follow cleaning procedures in Routine 
Maintenance section.

Leaks in ductwork.

Repair.

Elbows or other obstructions may be 
obstructing fan outlet.

Correct or improve ductwork.

Belt slippage.

Adjust belt tension.

High airflow (cfm)

Blower fan speed too high.

Check for correct fan rpm. Decrease fan speed 
if necessary.

Filter(s) not in place.

Install filters.

Insufficient static pressure (Ps) (airflow 
resistance).

Induce Ps into system ductwork. Make sure 
grilles and access doors are installed. Decrease 
fan speed if necessary.

Troubleshooting – Unit

Содержание ERVe

Страница 1: ...codes as well as the National Electrical Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 All moving parts must be free to rotate wi...

Страница 2: ...ve been received If any items are missing report shortages to your local representative to arrange for obtaining missing parts Sometimes it is not possible that all items for the unit be shipped toget...

Страница 3: ...ct Overview The ERVe brings in fresh outdoor air and removes stale exhaust air Prior to discharging the exhaust air the energy recovery wheel transfers energy from the exhaust air to the outdoor air a...

Страница 4: ...4 21 8 23 9 All dimensions are in inches Door handles hinges and other protrusions are not included in the dimensions above Dimensions are rounded up to the nearest 1 inch Duct Dimensions Unit Size A...

Страница 5: ...of a clearance of one inch must be maintained between the outside edges of the duct and combustible material in accordance with NFPA Standard 90A Unit Size A B Approx Weight lbs ERVe 20 22 37 825 ERVe...

Страница 6: ...ration it is important that the installation be level Shim as required to level 3 Install Ductwork Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines Duct adapter p...

Страница 7: ...raight duct lengths were calculated based on 100 effective duct length requirements as prescribed in AMCA Publication 201 Calculated values have been rounded up to nearest foot Ductwork Connections Ex...

Страница 8: ...rating plate Voltage Imbalance In a 3 phase system excessive voltage imbalance between phases will cause motors to overheat and eventually fail Maximum allowable imbalance is 2 To determine voltage i...

Страница 9: ...gauge Control wires should not be run inside the same conduit as that carrying the supply power Make sure that field supplied conduit does not interfere with access panel operation If wire resistance...

Страница 10: ...R EXHAUST DIRTY FILTER SWITCH SUPPLY DIRTY FILTER SWITCH HOT COMMON Dirty Filter Indicator powered by others A W1 12 7 6 Y2 Y1 G C R UNIT ON OFF COOL STAGE 1 ECONOMIZER COOL STAGE 2 UNOCCUPIED RECIRCU...

Страница 11: ...modes are available 1 Stopping the wheel 2 Modulating the wheel Stopping the wheel A field supplied call for cool Y1 is required De energizing the wheel is accomplished one of three ways 1 The outdoor...

Страница 12: ...ill run at full speed If the outdoor air temperature is less than 5 F AND the pressure differential is greater than the set point the wheel will run at reduced speed until the pressure differential fa...

Страница 13: ...______ Start Up Company _______________________________ Phone Number _______________________________ Pre Start Up Checklist check as items are completed Disconnect and lock out all power switches Remo...

Страница 14: ...es No Wheel Rotation Sensor Yes No N A Yes No OA Dirty Filter Sensor Yes No N A Yes No EA Dirty Filter Sensor Yes No N A Yes No CO2 Sensor Yes No N A Yes No Service Outlet Yes No N A Yes No Remote Con...

Страница 15: ...fter adjustment Check pulleys and belts for proper alignment to avoid unnecessary belt wear noise vibration and power loss Motor and drive shafts must be parallel and pulleys in line see diagrams in t...

Страница 16: ...s door and apply power Observe by opening door slightly remove filters if necessary to view wheel the wheel should rotate freely at about 20 40 RPM Energy Recovery Wheel The ERVe models contain a tota...

Страница 17: ...arameter value 6 Press the button to increase change the displayed parameter value 7 Press enter to accept the displayed value and store it in non volatile RAM 8 CHANGE STORED displays 9 Press enter t...

Страница 18: ...Hz TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS PARAMETER A1 01 CHANGE TO 2 PARAMETER d1 02 FOR NEW 40Hz SETTING PARAMETER d1 01 FOR NEW 60Hz SETTING PARAMETER d1 03 FOR NEW 30Hz SETTI...

Страница 19: ...ers command the VFD to run at multiple speed settings Open Drive runs at 60 Hz SC to S4 Drive runs at 40 Hz SC to S5 Drive runs at 30 Hz CO2 Sensor Set Point Control A carbon dioxide sensor is provide...

Страница 20: ...ecel Time 600 C4 01 Torque Gain 0 6 C6 02 Carrier Frequency 2 D2 01 Ref Upper Limit 40 or 50 D2 02 Ref Lower Limit 5 E2 01 Motor Rated FLA Motor FLA E2 03 Motor No Load Current Must be less than FLA H...

Страница 21: ...periodically thereafter Fan Motors Motor maintenance is generally limited to cleaning and lubrication Cleaning should be limited to exterior surfaces only Removing dust and grease buildup on the moto...

Страница 22: ...ency of cleaning depends upon the cleanliness of the incoming air These filters should be cleaned prior to start up Clean filters by rinsing with a mild detergent in warm water Internal Filter Mainten...

Страница 23: ...does not affect its performance Thoroughly spray wheel matrix with household cleaner such as Fantastik or equivalent Gently rinse with warm water and using a soft brush remove any heavier accumulatio...

Страница 24: ...ult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the fol...

Страница 25: ...lease determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SMACNA and AMCA guidelines Unit 1 Uni...

Страница 26: ...pressures are higher or lower than design If higher ductwork should be improved If lower fan rpm should be lower Blower rotation is incorrect Check rotation and reverse if necessary Motor voltage inc...

Страница 27: ...gy wheel runs intermittently Wheel motor overloads are tripping due to rubbing between wheel and air seals Recheck air seals make sure they are not too tight See Energy Recovery Wheel under Unit Start...

Страница 28: ..._________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ________...

Отзывы: