background image

5

Energy Core Ventilator

®

The MiniCore comes standard with end connections. 
The option for configurable intake and discharge 
connections (shaded in below drawing) are available 
and can be interchanged based on application in 
the field. 

Changing the Discharge Location
Step 1

 -

 Disconnect and lockout all power switches.

Step 2 –

 Remove the sheet metal block off from the 

desired discharge location.

Step 3 –

 Cut the insulation from the desired discharge 

location opening.

Step 4 –

 Remove the backdraft damper from its current 

position and reinstall in the desired discharge location. 
The hinged door should be on the discharge end of 
the unit.

Step 5 –

 Glue the cut out insulation to the sheet metal 

block off. Install where the damper had been located.

Step 6 –

 Using a 1/2-inch wrench, remove the four 

(4) bolts from the discharge end of the unit that holds 
the blowers.

Step 7 –

 Remove the four (4) plastic plugs from the 

desired discharge location and reinstall the plastic 
plugs in the holes where the bolts were removed from 
in Step 6.

Step 8 –

 Position the blowers to line up with the 

desired discharge location. The motor needs to be on 
the discharge end of the blower and unit. If the motor 
is positioned on the return side of the blower/unit, the 
motor/blower will interfere with the energy recovery 
core. The blower adjacent to the control center needs to 
be rotated 90°. The blower not adjacent to the control 
center needs to be flipped and rotated such that the 
motor is now opposite the control center side of the 
unit. It may be necessary to unwire the motors.

Step 9 –

 Bolt the blowers in their desired locations. 

Securely reconnect and fasten all wires.

Exhaust Air 
Intake

Outdoor Air 
Intake

Exhaust Air 
Discharge

Outdoor Air 
Discharge

Intake and Discharge Locations

Changing the Inlet Location
Step 1

 - 

Remove the metal cover for optional inlet 

location by unfastening the four (4) sheet metal screws 
holding it in place.

Step 2 - 

Hand bend flanges out to form a duct collar in 

the newly uncovered intake opening.

Step 3 - 

Cut insulation.

Step 4 - 

Hand bend flanges in on original intake and 

replace metal cover removed in Step 1.

Содержание ECV

Страница 1: ... applicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded 4 Do not spin fan wheel faster than maximum cataloged fan RPM Adjustments to fan speed significantly affects motor load If the fan RPM is changed the motor current should be checked to make sure it...

Страница 2: ...ergy recovery core The preconditioned air is typically mixed with return air going back to the air handler for final conditioning Table of Contents General Safety Information 1 Unit Overview 2 Receiving Handling Storage 3 Dimensional Data and Weights 4 Service Clearances and Access Panel Locations 4 Intake and Discharge Locations 5 Installation 6 Electrical Connections 8 Wiring Schematics 9 System...

Страница 3: ...ent condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for periodic inspection The unit should be stored at least 3 in 89 mm off the floor Clearance should be provided to permit air circulation and space for inspecti...

Страница 4: ...ecome necessary If the MiniCore unit is to be mounted on its side Reference the Mounting Options sections of this IOM then service clearance should be on the electrical input side Access Panel Locations Outdoor and exhaust fans and motor Electrical connection Energy core and internal filters Energy Core and Filter Access Panel Service Clearance Electrical Access Panel Energy Core and Filter Access...

Страница 5: ...ic plugs in the holes where the bolts were removed from in Step 6 Step 8 Position the blowers to line up with the desired discharge location The motor needs to be on the discharge end of the blower and unit If the motor is positioned on the return side of the blower unit the motor blower will interfere with the energy recovery core The blower adjacent to the control center needs to be rotated 90 T...

Страница 6: ...nging Vibration Isolator Assembly Side Discharge End Installation IMPORTANT The MiniCore unit can be hung in any orientation The installation contractor is responsible for safely mounting the unit to provide appropriate removal or access to the panels and unit components The system design and installation should follow accepted industry practices such as described in the ASHRAE Handbook and SMACNA...

Страница 7: ... Fan Wheel Dia 1 Fan Wheel Dia R o tation R o tation Length of Straight Duct GOOD POOR GOOD POOR GOOD POOR Turning Vanes SYSTEM EFFECT FACTOR CURVES FPM X 100 OUTLET VELOCITY 0 5 10 15 20 25 30 35 40 45 1 2 1 0 0 8 0 6 0 4 0 2 0 0 STATIC PRESSURE LOSS CURVE 1 CURVE 2 CURVE 3 CURVE 4 Ductwork Connections Examples of poor and good fan to duct connections are shown Airflow out of the fan should be di...

Страница 8: ...DANGER High voltage electrical input is required for this equipment This work should be performed by a qualified electrician Frost Control Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery core Frost control is an optional feature that will prevent control core frosting 1 Timed exhaust frost control This option is provided with a thermodisc...

Страница 9: ...DC SEE NOTE 2 BLACK BLACK WHITE POT A SEE NOTE 1 BLACK RED RED CLOSED 115 120V OPEN 208 230 277 2CBL MA 2CBL MA L2 L1 MB B B BLOWER MOTOR B ORANGE RED BLACK 0 10VDC SEE NOTE 2 BLACK BLACK WHITE POT B SEE NOTE 1 BLACK RED RED CLOSED 115 120V OPEN 208 230 277 2CBL MB 2CBL MB B SEE NOTE 3 A SEE NOTE 3 VERIFY BLOWER MOTOR VOLTAGE MATCHES LINE VOLTAGE 110 120V 50 60HZ 208 230 277V 50 60HZ NOTE 1 Potent...

Страница 10: ...l No ___________________________________ Unit Serial No _____________________________________ Start Up Date ____________________________________ Start Up Personnel Name __________________________ Start Up Company_________________________________ Phone Number____________________________________ Pre Start Up Checklist o Disconnect and lock out all power switches o Remove any foreign objects that are...

Страница 11: ...ed and compared with its rated air volume The unit is directly driven therefore balancing dampers or speed controls are required for airflow balancing Air volume measurement must be conducted with access doors on the unit The most accurate way to measure the air volume is by using the pitot traverse method in the ductwork away from the blower Other methods can be used but should be proven and accu...

Страница 12: ...e detergents and cleaners on the core This will result in a damaged core WARNING Disconnect all electrical power to the MiniCore prior to inspection or servicing Failure to comply with this safety precaution could result in serious injury or death Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and mainten...

Страница 13: ...e motor will still not rotate the motor will not attempt to start again until power is cycled Thermal Protection The motors will have an internal thermal protection which electronically regulates the RPM limit until an acceptable temperature is met Operation and Wiring These motors have the ability to accept a plug in potentiometer for speed adjustment AND the ability to accept a 0 10V signal for ...

Страница 14: ...ings Tighten collars and fasteners Wheel out of balance Clean replace or rebalance Low airflow cfm Fan speed too low Increase fan speed Dirty filters or energy core Replace filters and or follow the cleaning procedures High static pressure Incorrect fan to duct connections Make sure dampers open appropriately Increase fan speed High airflow cfm Fan speed too high Decrease fan speed Low static pres...

Страница 15: ..._____________________ _________________________________________________ _________________________________________________ Date____________________Time______________ AM PM Notes ____________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ ____________________________...

Страница 16: ...al Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Product warranties can be found online at...