Single Sided Angle Method:

 For single side installations the retaining angles must be attached to the wall/floor  

(see 

Figures 8-11

). For metal stud partitions only, the single side mounting angle may be directly attached to the 

metal stud prior to the installation of the drywall.
  •  Retaining angles must be attached to the partition using one of the methods shown below:
    -  #10 screws of a length such that the screw engages the steel stud/track by ½ in. (13 mm) (steel framing).
    -  #10 screws of a length such that the screw engages the wood stud by 13/4 in. (44 mm) (wood framing).
    -  Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31 mm).
  •  A minimum of two connections per side are required. Additional connections made at a maximum of 12 in. (305 

mm) O.C. for openings of 48 in. W x 36 in. H (1219 mm x 914 mm) and less. Dampers greater than 48 in. wide 
(1219 mm) or 36 in. high (914 mm) require the connections to be no more than 6 in. (152 mm) O.C.

Damper 
Sleeve

Angle Fastener

Stud or Runner

Two layers of 1/2 in. UL 
Classified Gypsum 
Wallboard for 2 hour 
rated walls. One layer 
for 1 hour rated walls 
(see UL Rated Wall 
Design for Additional 
Details). 

Figure 8: Single Side Angle With Steel Stud Wall 

Angle Over Wallboard

Stud or Runner

Damper

Sleeve

Angle Fastener

Two layers of 1/2 in. UL 
Classified Gypsum 
Wallboard for 2 hour 
rated walls. One layer 
for 1 hour rated walls 
(see UL Rated Wall 
Design for Additional 
Details).

Figure 9: Single Side Angle With Wood Stud Wall

Damper 
Sleeve

Metal Stud
or Runner

Two layers of 1/2 in. UL 
Classified Gypsum 
Wallboard for 2 hour 
rated walls. One layer 
for 1 hour rated walls 
(see UL Rated Wall 
Design for Additional 
Details).

Figure 10: Single Side Angle With Steel Stud Wall 

Angle Under Wallboard

Masonry or
Concrete
Wall

Damper

Sleeve

Angle Fastener

Masonry or
Concrete 
Floor

Damper

Sleeve

Angle Fastener

Top Side

Figure 11: Single Side Angle With Masonry or Concrete 

Wall and Floor

Grille Installations (Dampers up to 36 in. x 36 in. [914 mm x 914 mm])

Retaining angles used in conjunction with grille installations must be a minimum of 

5

8

 in. x 1 in. (15 mm x 25 mm) 16 

gauge (1.5 mm) steel. Space screws a maximum of 6 in. (152 mm) O.C. and a maximum of 2 in. (51 mm) from the 
corners (minimum of 2 screws per side). See 

Figure 12

 and 

Figure 13.

Note:

 Screws used to attach grille are allowed to penetrate reversed angle leg.

Curtain Fire Dampers

7

®

Содержание DFD 150 Series

Страница 1: ...tion service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Pre Installation Guidelines 2 Preparation of Openings 3 Clearances Required Between Damper Sleeves Wall Floor Openings 4 Installing Multiple Section Assemblies 4 Maximum As...

Страница 2: ... or spray painting will be performed within 5 feet of the damper 7 Caulking is not necessary nor is it allowed between the damper sleeve and the wall or floor opening annular space However caulking may be applied to the retaining angles 8 ACCESS Suitable access such that the fusible link may be removed and the damper s blade stack may be reset etc must be provided for damper inspection and servici...

Страница 3: ...nt Dow Metal Stud Framing Shown Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or smaller Metal stud only 24 in 610mm O C max Detail A A Detail A A Floor Runner Ceiling Runner Notched Piece Bent Down Metal Stud Framing Shown Ceiling Runner Detail A A Floor Runner 24 in 610mm O C Max Figure 2A Metal Stud Construction Wooden Stud Construction In metal stud construction ...

Страница 4: ...minmum of 1 in 25 mm For stainless steel dampers and stainless steel or galvanized sleeves 3 16 in per foot 5 mm per 3 m of damper width and height with a minimum clearance of 1 4 in 6 mm maximum of 2 in 51 mm These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper Although the minimum requirements are listed above for ease of installation the foll...

Страница 5: ... x 762 mm DFD 350 Vertical 36 x 36 914 mm x 914 mm Horizontal 24 x 18 610 mm x 457 mm 48 x 36 1217 mm x 914 mm 30 x 30 762 mm x 762 mm DFD 310 Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm SSDFD 150 SSDFD 350 Vertical 30 x 30 762 mm x 762 mm FD 150X Vertical or Horizontal 48 x 48 1219 mm x 1219 mm DFD 150X Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm Al...

Страница 6: ...he leg of the retaining angle on the damper sleeve shall be a minimum of 11 4 in 32 mm The leg of the retaining angle on the wall floor shall be long enough to cover the annular space and overlap the wall floor by a minimum of 1 in 25 mm Retaining Angle Attachment to Sleeve Retaining angles must be attached to the damper using one or more of the following methods of attachment refer to label on ou...

Страница 7: ...1 hour rated walls see UL Rated Wall Design for Additional Details Figure 8 Single Side Angle With Steel Stud Wall Angle Over Wallboard Stud or Runner Damper Sleeve Angle Fastener Two layers of 1 2 in UL Classified Gypsum Wallboard for 2 hour rated walls One layer for 1 hour rated walls see UL Rated Wall Design for Additional Details Figure 9 Single Side Angle With Wood Stud Wall Damper Sleeve Met...

Страница 8: ...n 178mm Type A Type B Field installed Sleeve Damper 1 4 in minimum total clearance See Section 1 Maximum 6 in Maximum 6 in Wall or floor Wall or floor Wall or floor Damper Damper Duct Duct Duct Retaining Angles See Section 4 Sleeve See Sleeve Requirements Sleeve Sleeve On types R CR factory furnished duct collar qualifies as breakaway connection See Connecting Ducts to Fire Damper Sleeve Retaining...

Страница 9: ...Precision DP1010 water base duct sealant manufactured by Design Polymerics Grey Pookie Ductmate PROseal or CL Ward S Seal in accordance with SMACNA recommendations Transverse Joints The transverse joints shown below are approved as breakaway connections A maximum of two 10 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip poc...

Страница 10: ...facturer s instructions Duct 3 8 in bolts in corners are optional 6 in long metal cleat or 1 16 in max thickness plastic cleat 12 in c c min 1 per side Figure 18 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward Nexus Radiant T 35m and MEZ are approved as breakaway connections when installed as illustrated see Figure 18 Figure 22 Me...

Страница 11: ...rated dampers utilizing a fusible link are required to be tested by removing the fusible link and allowing the damper to fully close and then manually reopening the damper Re install the fusible link Greenheck s life safety dampers shall not be tested by applying heat with uncontrollable heat sources i e heat guns torches etc as this can permanently damage the thermostat or other parts of the damp...

Страница 12: ...ves the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck com Resources Library Literature Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com Our Commitment ...

Отзывы: