Centrifugal Inline Fans

6

®

Wheel Overlap Dimensions

Figure 7

Model

G - Overlap 

mm (in.)

SQ-M 70-90

(1/8)

SQ-M 100-160

(1/4)

BSQ-M 70-160

(1/4)

BSQ-M 180-240

10 

(3/8)

BSQ-M 300-420

13 

(1/2)

G

WARNING

Correct direction of wheel rotation is critical. Reversed 
rotation will result in poor air performance, motor 
overloading and possible burnout.

 3. 

Vibration Isolators:

 After fan is moved to desired 

location, punch out the four knockout holes which 
are located on the unit top and bottom panels. 
Assemble the brackets to the unit according to the 
appropriate drawings on page 5. Make certain all 
connectors are tight and that all washers are in.

 4. 

For BSQ-M Fans:

 If adjustments are made, it is 

very important to check the pulleys for proper 
alignment. Misaligned pulleys lead to excessive belt 
wear, vibration, noise, and power loss (see Figure 9).

Pre Start-Up Checks

 1. 

Check all fasteners for tightness.

 The wheel 

should rotate freely and be aligned as shown in 
Figure 7. Wheel position is preset and the unit is 
tested at the factory. Movement may occur during 
shipment, and realignment may be necessary. 
Centering can be accomplished by loosening 
the bolts holding the inlet (venturi) panel and 
repositioning. Wheel and inlet cone overlap can be 
adjusted by loosening the setscrews in the wheel 
and moving the wheel to the desired position.

 2.  

Wheel Rotation:

 

Direction of wheel 
rotation is critical. 
Reversed rotation 
will result in poor air 
performance, motor 
overloading and 
possible burnout. 
Check wheel rotation 
by momentarily 
energizing the unit (all 
SQ-M and BSQ-M 
fans have clockwise wheel rotation when viewed 
from top of fan). Rotation should be clockwise as 
shown in Figure 8 and correspond to the rotation 
decal on the unit.

C

lo

c

k

w

is

e

Figure 8

Pre-Start-Up Checks, Operation & Inspection

Side Discharge Duct Openings

Unit Size

Width

Height

SQ-M 70

251 

(9

7

8

)

225 

(8

7

8

)

SQ-M 80-90

327 

(12

7

8

)

302 

(11

7

8

)

BSQ-M 70-80-90

302 

(11

7

8

)

302 

(11

7

8

)

SQ-M 100/BSQ-M 100

352 

(13

7

8

)

352 

(13

7

8

)

SQ-M 120/BSQ-M 120

403 

(15

7

8

)

403 

(15

7

8

)

SQ-M 130/BSQ-M 130 (HP)

454 

(17

7

8

)

454 

(17

7

8

)

SQ-M 140/BSQ-M 140 (HP)

505 

(19

7

8

)

505 

(19

7

8

)

SQ-M 160/BSQ-M 160 (HP)

581 

(22

7

8

)

581 

(22

7

8

)

BSQ-M 180 (HP)

606 

(23

7

8

)

606 

(23

7

8

)

BSQ-M 200 (HP)

708 

(27

7

8

)

708 

(27

7

8

)

BSQ-M 240 (HP)

733 

(28

7

8

)

886 

(34

7

8

)

BSQ-M 300 (HP)

810 

(31

7

8

)

1064 

(41

7

8

)

BSQ-M 360 (HP)

835 

(32

7

8

)

962 

(37

7

8

)

BSQ-M 420

886 

(34

7

8

)

1114 

(43

7

8

)

All dimensions in millimeters (

inches)

.

Figure 6

Height

Left Side
Discharge

Right Side
Discharge

Inline
Discharge

Inlet

Width

Duct Length: 

The inlet and outlet duct length should be 

approximately two to three wheel diameters long before 
and after the fan to achieve cataloged performance.

Side Discharge:

 Make sure discharge is orientated in 

the same direction as originally ordered, performance 
will change with different discharge positions. Refer to 
Figure 6 for proper side discharge definition and the 
Side Discharge chart for dimensions. Refer to the CAPS 
program or consult factory for performance corrections.

Содержание BSQ-M 100

Страница 1: ...erify that the power source is compatible with the equipment 7 Never open access doors to a duct while the fan is running Model SQ M Direct Drive Model SQ M is a direct drive centrifugal inline exhaus...

Страница 2: ...parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts...

Страница 3: ...886 347 8 762 30 508 20 406 16 0 1192 x CFM 159 350 18 ga 889 x 889 35 x 35 300 300HP 1168 46 965 38 1168 46 1064 417 8 864 34 559 22 457 18 0 0826 x CFM 244 537 16 ga 1067 x 1067 42 x 42 360 360HP 13...

Страница 4: ...ss panels are located on the two sides adjacent to the motor Figure 5 Vertical Hanging or Base Mount G B B D D Hanging rails by others Mounting Dimensional Data Model A B C D G SQ M 70 270 105 8 432 1...

Страница 5: ...8 BSQ M 160 420 35 13 8 35 13 8 64 2 Spring Base Isolators Model H J J1 L I K SQ M 70 90 38 1 51 2 70 2 152 6 SQ M 100 160 35 13 8 51 2 150 515 16 BSQ M 70 140 35 13 8 35 13 8 60 23 8 150 515 16 BSQ...

Страница 6: ...itical Reversed rotation will result in poor air performance motor overloading and possible burnout Check wheel rotation by momentarily energizing the unit all SQ M and BSQ M fans have clockwise wheel...

Страница 7: ...not striking the venturi or any obstacle 3 Start the fan and shut it off immediately to check rotation of the wheel with directional arrow in the motor compartment see Figure 8 4 When the fan is star...

Страница 8: ...dition that will cause vibration in the fan WARNING This unit should be made non functional when cleaning the wheel or housing fuses removed disconnect locked off Torque Speci cations for Bushings Ref...

Страница 9: ...y duty in dirty dusty locations high ambient temperatures moisture laden atmosphere vibration 3 to 6 12 to 24 hours per day heavy duty or if moisture is present 6 to 12 8 to 16 hours per day in clean...

Страница 10: ...l Inline Exhaust Fan VENTURI WHEEL ACCESS PANEL HOUSING VENTURI PANEL WHEEL MOTOR COVER MOTOR MOTOR COVER MOTOR ACCESS PANEL BSQ M Belt Drive Centrifugal Inline Exhaust Fan Parts List Each fan bears a...

Страница 11: ...tighten See Pre Start Up Checks pages 6 7 Foreign objects in wheel or housing Remove objects check for damage or unbalance Reduced air ow System resistance too high Check system Proper operation of ba...

Страница 12: ...ct area tab and in the Technical Data Library Greenheck s Centrifugal Inline Fans catalog Models SQ M and BSQ M provides additional information describing the equipment fan performance available acces...

Отзывы: