background image

5

Model BDF • Belt Drive Duct Fan

®

  7.  The adjustable motor pulley is factory set for 

the RPM specified. Speed can be increased by 
closing or decreased by opening the adjustable 
motor sheave. Two groove variable pitch pulleys 
must be adjusted an equal number of turns open 
or closed. Any increase in speed represents a 
substantial increase in the horsepower required 
by a unit. Motor amperage should always be 
checked to avoid serious damage to the motor 
when speed is varied.

Operation: BDF

  1.  Before starting up or operating fan, check all 

fasteners for tightness. In particular, check 
the setscrews in wheel hub (and pulleys, if 
applicable).

  2.  While in the OFF position or before connecting 

the fan to power, turn the fan wheel by hand 
to be sure it is not striking the venturi or any 
obstacle.

  3.  Start the fan and shut it off immediately to check 

rotation of the wheel with directional arrow in the 
motor compartment, see figure 4.

  4.  When the fan is started, observe the operation 

and check for any unusual noises.

  5.  With the system in full operation and all 

ductwork attached, measure current input to the 
motor and compare with the nameplate rating to 
determine if the motor is operating under safe 
load conditions.

  6.  Keep inlets and approaches to fan clean and 

free from obstruction.

Inspection: BDF

Inspection of the fan should be conducted at the 
first 30 minute and 24 hour intervals of satisfactory 
operation.

30 Minute Interval

Inspect bolts, setscrews and motor mounting bolts. 
Adjust and tighten as necessary.

24 Hour Interval

Check all internal components and inspect belt 
alignment and tension. Adjust and tighten as 
necessary.

Maintenance: BDF

Installation and maintenance are to be performed 
only by qualified personnel who are familiar 
with local codes and regulations and who are 
experienced with this type of equipment.
Motor maintenance is generally limited to cleaning 
and lubrication (where applicable). Cleaning should 
be limited to exterior surfaces only. Removing dust 
buildup on motor housing ensures proper motor 
cooling.
Greasing of motors is only intended when fittings 
are provided. Many fractional horsepower motors 
are permanently lubricated and should not be 
lubricated after installation. Motors supplied with 
grease fittings should be greased in accordance 
with manufacturers’ recommendations. Where 
motor temperatures do not exceed 104°F 

(40°C)

the grease should be replaced after 2,000 hours of 
running time as a general rule.
Wheels require very little attention when moving 
clean air. Occasionally, oil and dust may accumulate 
causing imbalance. When this occurs the wheel and 
housing should be cleaned to ensure smooth and 
safe operation.
All fasteners should be checked for tightness each 
time maintenance checks are performed prior to 
restarting unit.
A proper maintenance program will help these units 
deliver years of dependable service.

Belt/Bearing Maintenance BDF Unit

  1.  Belts tend to stretch after a period of time. They 

should be checked periodically for wear and 
tightness. When replacing belts, use the same 
type as supplied with the unit.

  2.  Matched belts should always be used on units 

with multi-groove pulleys.

  3.  For belt replacement, loosen the tensioning 

device enough to allow removal of the belt by 
hand. Do not force belts on or off. This may 
cause cords to break, leading to premature belt 
failure.

WARNING

The fan has been checked for mechanical noises at 
the factory prior to shipment. If mechanical noise 
should develop, suggested corrective actions are 
offered in the Troubleshooting section.

IMPORTANT

Over tightening will cause excessive bearing wear 
and noise. Too little tension will cause slippage at 
startup and uneven wear.

IMPORTANT

Adjust (tighten) belt tension after the first 24-48 
hours of operation.

WARNING

Always disconnect, lock and tag power source 
before servicing. Failure to disconnect  power 
source can result in fire, shock or serious injury.

CAUTION

Uneven cleaning of the wheel will produce an out 
of balance condition that will cause vibration in the 
fan.

WARNING

This unit should be made non-functional when 
cleaning the wheel or housing (fuses removed, 
disconnect locked off).

Содержание Belt Drive Duct Fan BDF

Страница 1: ...ional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Electrical Code NEC and the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately groun...

Страница 2: ...atures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts and packag...

Страница 3: ...oged Open Drip Proof motor Chart 2 Filter Option Dimensions BDF Size K B C D E F G H Filter Size Filter Quantity 80 493 4 1264 181 2 470 157 8 403 153 16 386 1211 16 322 93 4 248 87 8 225 1 25 16 x 20 406 x 508 2 90 547 8 1394 211 4 540 183 4 476 181 4 464 157 8 403 121 4 311 101 2 267 1 25 20 x 25 508 x 635 2 100 517 8 1318 223 4 578 203 4 527 193 4 502 177 8 454 133 4 349 117 8 302 1 25 20 x 20 ...

Страница 4: ...rtain all connectors are tight and that all washers are in 5 If adjustments are made it is very important to check the pulleys for proper alignment Misaligned pulleys lead to excessive belt wear vibration noise and power loss See figure 5 6 For all BDF Fans Belt tension can be adjusted by loosening four fasteners marked R figure 6 on the drive frame The motor plate slides on the slotted adjusting ...

Страница 5: ...emoving dust buildup on motor housing ensures proper motor cooling Greasing of motors is only intended when fittings are provided Many fractional horsepower motors are permanently lubricated and should not be lubricated after installation Motors supplied with grease fittings should be greased in accordance with manufacturers recommendations Where motor temperatures do not exceed 104 F 40 C the gre...

Страница 6: ...s per day in clean relatively dry atmosphere 12 to 18 Infrequent operation or light duty in clean atmosphere Table 2 Grease Manufacturers Manufacturer Grease NLGI 2 U S Electric Motors Grease No 83343 Chevron U S A Inc Chevron SRI Grease 2 Mobil Oil Corporation Mobilith Mobil 532 Texaco Inc Premium BRB 2 Texaco Multifak 2 Amoco Oil Co Rykon Premium 2 Exxon Unirex N2 Shell B Shell Alvania 2 4 Once ...

Страница 7: ... 8 in 3 8 in 6 12 Cadium plated lock washer 3 8 in 3 8 in 7 4 Cadium plated washer 1 3 8 in O D x 9 16 in I D x 3 32 in 1 3 8 in O D x 9 16 in I D x 3 32 in 7 12 Cadium plated washer 1 3 8 in O D x 9 16 in I D x 3 32 in 1 3 8 in O D x 9 16 in I D x 3 32 in 8 4 Neoprene or Spring Isolator Reference appropriate table below for replacement Isolator s 8 4 Neoprene or Spring Isolator Reference appropri...

Страница 8: ...additional information describing the equipment fan performance available accessories and specification data Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Warranty AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA Internati...

Отзывы: