background image

Controller Display

The controller has a two line backlit LCD display. By using the up and down arrows on the controller’s cover the 
display can be toggled to show one of three sets of data:

 

• Top Screen: Real-Time CFM and CFM Setpoint

 

• Middle Screen: Real-Time Velocity (fpm) and Velocity Setpoint

 

• Bottom Screen: Real-Time Differential Pressure Measurement and Actuator Position

Wiring the Controller

The basic wiring of the controller is shown below in 

Figure 2

. The controller’s three terminal blocks can be accessed 

by opening the cover of the enclosure.

Powering the Controller

The controller is powered by applying electrical power to the “Power In” terminal block. The controller can run off of 
24 VAC +/- 20% 50/60 Hz ; 24 VDC +/- 10%.

Connecting the Pressure Transducer

The second terminal block is labeled “Remote Sensor” and is used to connect the pressure transducer. The three 
terminals from the Remote Sensor block connect directly to the pressure transducer as shown in 

Figure 2

. The 

controller supplies the transducer with its power and reads the pressure signal.

Connecting the Damper Actuator

The actuator can be powered either by the same power supply as the controller (as shown in 

Figure 2

) or by running 

a separate power supply to terminals 4 and 5 of the factory supplied terminal block on the AMD/AMS. In addition, 
the “Control Out” from the controller (terminal 7) must be run to terminal 6 on AMD/AMS terminal block.

Connecting the Flow (or position) Setpoint Signal

Connect the 0-10 VDC or 2-10 VDC flow (or position) setpoint to the controller’s terminals 1 and 3. The controller’s 
terminal 1, labeled Remote Setpoint, is the positive terminal and the controller’s terminal 3 is the negative terminal.

Connecting to the Flow Output Signal

Connecting to controller terminals 6 and 3 allows the user to read the 0-10 VDC or 2-10 VDC flow output that is 
proportional to the cfm measured by the AMD/AMS.  To convert the voltage signal to cfm see the section above on 
Controller’s Analog Output Proportional to Real-Time Airflow.

Override Mode

See the full Vari-Green constant volume controller installation and operation manual for a description of the override 
feature. The override feature can be activated by closing the contacts of an external relay across terminals 2 and 3 
(or by simply putting a jumper wire across them).

AMD & AMS Series

7

®

Содержание AMD-42

Страница 1: ...velocity of 300 fpm 1 5 m s is required Table of Contents Pre Installation Guidelines 2 Electrical Guidelines 2 Installation 2 10 Setup and Operation for AMS and AMD Series Without Factory Supplied Controller 3 Clearances Required Between Damper Sleeves and Wall Floor Openings 4 Installing Multiple Damper Section Assemblies 4 5 Multiple Section Damper Wiring 5 Maximum Assembly Tables 5 Inserting D...

Страница 2: ...nstallation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on damper can cause excessive leakage and or...

Страница 3: ...staller Design calculations for these retaining and supporting members should be determined by field engineers for that particular installation 4 Individual damper sections as well as entire multiple section assemblies must be completely square and free from racking twisting or bending Measure diagonally from upper corners to opposite lower corners of each section 5 Damper blades axles and linkage ...

Страница 4: ...MS see example label below Using the high pressure limit of the transducer and the voltage output of the transducer the real time pressure reading can be calculated using the formula Ptransducer Transducer Output Voltage High Pressure Limit of Transducer 10 Formula 1 The pressure reading of the transducer can then be used to calculate the volumetric flow rate going through the AMS or AMD using the ...

Страница 5: ...4 2590 8 2743 2 40 40 0 79 0 81 0 82 0 84 0 85 0 87 0 88 0 90 0 92 0 93 0 95 0 97 0 99 1 01 1 02 1 04 1 06 1 08 1 10 20 29 0 83 0 85 0 86 0 88 0 89 0 91 0 93 0 94 0 96 0 98 1 1 01 1 03 1 05 1 07 1 09 1 11 1 14 1 16 0 18 0 87 0 88 0 9 0 92 0 93 0 95 0 97 0 99 1 1 02 1 04 1 06 1 08 1 10 1 12 1 14 1 16 1 19 1 21 20 7 0 91 0 92 0 94 0 96 0 97 0 99 1 01 1 03 1 05 1 07 1 09 1 11 1 13 1 15 1 17 1 19 1 22...

Страница 6: ...1 Setting the Flow Setpoint The controller accepts an analog input configurable for either 0 10 or 2 10 VDC that is proportional to a target volumetric airflow rate cfm The voltage corresponding to the setpoint can be determined using the following formulas 0 10 VDC setpoint C Q Vmax A 10 2 10 VDC setpoint C Q Vmax A 8 2 Formula 3 Where C Flow Setpoint VDC Q Desired Airflow cfm V max Maximum Velocity...

Страница 7: ...ing the Damper Actuator The actuator can be powered either by the same power supply as the controller as shown in Figure 2 or by running a separate power supply to terminals 4 and 5 of the factory supplied terminal block on the AMD AMS In addition the Control Out from the controller terminal 7 must be run to terminal 6 on AMD AMS terminal block Connecting the Flow or position Setpoint Signal Conne...

Страница 8: ...one at factory when the actuator is externally mounted When the actuator is internally mounted the actuator must be wired to the terminal block in the field Vari Green Constant Volume Controller Wiring Diagram Figure 2 AMD AMS Series 8 ...

Страница 9: ... Elbow Without Vanes D 2 2D Round Sweep Elbow D 2 2D Sweep Elbow 3D Centrifugal Fan Discharge 1 5D Centrifugal Fan Inlet 5D Vane Axial Fan Discharge 2D Vane Axial Fan Inlet Optimal Placement for AMS AMD Damper Series Fans AMD AMS Series 9 ...

Страница 10: ...ransitions 1D Į Į Transition 1 D 2 Į Į Transition 2 1D Į Į Transition 3 D 2 Transition 4 Į Į 1D Į Transition 5 1D Į Transition 6 1D Į Transition 7 D 2 Transition 8 Į Dampers 1D D1 4D D2 AMD AMS Series 10 ...

Страница 11: ... D Duct Diameter 4 x Width x Height H Rectangular Duct D Air Handling Units 1D Louver Air Handler with Louver Hood Return Air 1D Takeoffs 3D Branch Takeoff 1 3D Branch Takeoff B2B 2D Branch Takeoff 3 1D Branch Takeoff 4 Branch Takeoff B2A AMD AMS Series 11 ...

Страница 12: ...l bearings without grease fittings do not require lubrication Ball bearings with grease fittings require only minimal grease Closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades with each other or with the frame Operation While operating the damper through its full cycle check to see that the blades open and close properly If there is a probl...

Отзывы: