background image

Installation

Failure to follow instructions will void all warranties

1.  Ensure the AMS or AMD series damper is mounted 

with airflow straightener upstream of the damper.

2.  Duct opening or opening square should measure 

1

4

 

inch (6mm) larger than damper dimension and should 
be straight and level.

3.  Use shims between damper frame and duct opening 

or opening space to prevent distortion of frame by 
fasteners holding it in place. Brace at every horizontal 
mullion and vertically brace at every 8 feet (2.4m) of 
damper width for strength. Dampers in high velocity 
(2000 fpm [610m per second]) may require more 
bracing.

Note: Greenheck dampers are specifically designed 
and engineered for structural integrity based on 
model and conditions. Attachment, framing, mating 
flanges, and anchoring of damper assemblies into 
openings, ductwork, or walls is the responsibility of 
the installer. Design calculations for these retaining 
and supporting members should be determined by 
field engineers for that particular installation.

4.  Individual damper sections, as well as entire multiple 

section assemblies must be completely square and 
free from racking, twisting, or bending. Measure 
diagonally from upper corners to opposite lower 
corners of each section.

5.  Damper blades, axles, and linkage must operate 

without binding. Before system operation, cycle 
dampers after installation to assure proper operation. 
On multiple section assemblies all sections should 
open and close simultaneously.

6)  Installing two section high AMD series together. 

AMD’s more than one section high will be shipped 
separately in individual sleeves. The high and low 
pressure ports need to be plumbed together and then 
plumbed back to the pressure transducer. 

Do not twist or 
bow. Mount damper 
plumb in the 
opening.

AF = BE

AB = CD

C

D

E

F

Damper Sleeve

Damper Sleeve

Pressure Transducer

Plumb the high pressure parts together

Plumb the low pressure parts together

AMD & AMS Series

3

®

Содержание AMD-42

Страница 1: ...velocity of 300 fpm 1 5 m s is required Table of Contents Pre Installation Guidelines 2 Electrical Guidelines 2 Installation 2 10 Setup and Operation for AMS and AMD Series Without Factory Supplied Controller 3 Clearances Required Between Damper Sleeves and Wall Floor Openings 4 Installing Multiple Damper Section Assemblies 4 5 Multiple Section Damper Wiring 5 Maximum Assembly Tables 5 Inserting D...

Страница 2: ...nstallation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on damper can cause excessive leakage and or...

Страница 3: ...staller Design calculations for these retaining and supporting members should be determined by field engineers for that particular installation 4 Individual damper sections as well as entire multiple section assemblies must be completely square and free from racking twisting or bending Measure diagonally from upper corners to opposite lower corners of each section 5 Damper blades axles and linkage ...

Страница 4: ...MS see example label below Using the high pressure limit of the transducer and the voltage output of the transducer the real time pressure reading can be calculated using the formula Ptransducer Transducer Output Voltage High Pressure Limit of Transducer 10 Formula 1 The pressure reading of the transducer can then be used to calculate the volumetric flow rate going through the AMS or AMD using the ...

Страница 5: ...4 2590 8 2743 2 40 40 0 79 0 81 0 82 0 84 0 85 0 87 0 88 0 90 0 92 0 93 0 95 0 97 0 99 1 01 1 02 1 04 1 06 1 08 1 10 20 29 0 83 0 85 0 86 0 88 0 89 0 91 0 93 0 94 0 96 0 98 1 1 01 1 03 1 05 1 07 1 09 1 11 1 14 1 16 0 18 0 87 0 88 0 9 0 92 0 93 0 95 0 97 0 99 1 1 02 1 04 1 06 1 08 1 10 1 12 1 14 1 16 1 19 1 21 20 7 0 91 0 92 0 94 0 96 0 97 0 99 1 01 1 03 1 05 1 07 1 09 1 11 1 13 1 15 1 17 1 19 1 22...

Страница 6: ...1 Setting the Flow Setpoint The controller accepts an analog input configurable for either 0 10 or 2 10 VDC that is proportional to a target volumetric airflow rate cfm The voltage corresponding to the setpoint can be determined using the following formulas 0 10 VDC setpoint C Q Vmax A 10 2 10 VDC setpoint C Q Vmax A 8 2 Formula 3 Where C Flow Setpoint VDC Q Desired Airflow cfm V max Maximum Velocity...

Страница 7: ...ing the Damper Actuator The actuator can be powered either by the same power supply as the controller as shown in Figure 2 or by running a separate power supply to terminals 4 and 5 of the factory supplied terminal block on the AMD AMS In addition the Control Out from the controller terminal 7 must be run to terminal 6 on AMD AMS terminal block Connecting the Flow or position Setpoint Signal Conne...

Страница 8: ...one at factory when the actuator is externally mounted When the actuator is internally mounted the actuator must be wired to the terminal block in the field Vari Green Constant Volume Controller Wiring Diagram Figure 2 AMD AMS Series 8 ...

Страница 9: ... Elbow Without Vanes D 2 2D Round Sweep Elbow D 2 2D Sweep Elbow 3D Centrifugal Fan Discharge 1 5D Centrifugal Fan Inlet 5D Vane Axial Fan Discharge 2D Vane Axial Fan Inlet Optimal Placement for AMS AMD Damper Series Fans AMD AMS Series 9 ...

Страница 10: ...ransitions 1D Į Į Transition 1 D 2 Į Į Transition 2 1D Į Į Transition 3 D 2 Transition 4 Į Į 1D Į Transition 5 1D Į Transition 6 1D Į Transition 7 D 2 Transition 8 Į Dampers 1D D1 4D D2 AMD AMS Series 10 ...

Страница 11: ... D Duct Diameter 4 x Width x Height H Rectangular Duct D Air Handling Units 1D Louver Air Handler with Louver Hood Return Air 1D Takeoffs 3D Branch Takeoff 1 3D Branch Takeoff B2B 2D Branch Takeoff 3 1D Branch Takeoff 4 Branch Takeoff B2A AMD AMS Series 11 ...

Страница 12: ...l bearings without grease fittings do not require lubrication Ball bearings with grease fittings require only minimal grease Closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades with each other or with the frame Operation While operating the damper through its full cycle check to see that the blades open and close properly If there is a probl...

Отзывы: