Digital Temperature Interlock
Table of Contents
Product Specification . . . . . . . . . . . . . . . . . . . . . . . . 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . 2
Installation
Hood
Mounting
. . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Duct Collar Mounting . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Connections
Sensor
Connections
. . . . . . . . . . . . . . . . . . . . . . . 3
Switch Connections to Control Box
or Fan Control Center . . . . . . . . . . . . . . . . . . . . 3
Circuit
Connections
. . . . . . . . . . . . . . . . . . . . . . . 3
Calibration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Factory Selected Parameters
Setting Parameters . . . . . . . . . . . . . . . . . . . . 3-4
Control Circuit Diagrams . . . . . . . . . . . . . . . . . . . . 5-6
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Frequently Asked Questions . . . . . . . . . . . . . . . . . . . 8
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Codes and Standards Compliance . . . . . . . . . . . . . . 8
Our Commitment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Receiving and Handling
Upon receiving the equipment, check for both obvious
and hidden damage. Check to be sure that all parts of
the shipment, including accessories, are accounted for.
Make sure the equipment does not suffer any heavy
vibrations or knocks.
Storage
If a temperature interlock must be stored prior to
installation, it must be protected from dirt and moisture.
Indoor storage is recommended. For outdoor storage,
cover the control package with a tarp to keep it clean,
dry, and protected from UV (ultraviolet) radiation
damage.
Improper storage which results in damage to the unit
will void the warranty.
NOTE
Resistive temperature detector(s) may be factory
installed. If so, continue to the next section.
Resistive Temperature Detector(s)
Hood Mounting
Installation
Control Box Mounting
Locate an area with enough space to mount the control
box and fasten to the wall. Avoid installing the control
box in environments with high magnetic and/or radio
frequency interference.
2. Cut a 3/4 to 7/8-inch diameter
hole in the flat spot of the
capture tank. Make
sure the resistive
temperature detector(s)
will not interfere with fire
system nozzles and is
not within 12 inches of
light fixtures.
0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole
Hood Surface
NOTE
Control box may be factory mounted. If so, continue
to the next section.
1. Locate flat area(s) at the top interior of the hood in
front of the filters, towards the front of the hood.
3 inch air space
2 inch typical
19.525 inches
Sensor Install
(cutout area)
Exhaust Area
Supply Area
(optional)
P.O.BOX 410 SCHOFIELD, WI
TITLE
INSTR, ADJ. T
Top View of Exhaust Hood
Octagon Extension
PN 830125
Lock Washer
Nut
Compression Seal
PN 463570
Gasket
J-Box Plate
PN 732396
3. Place the J-box plate inside of the octagon extension
ring and place over the hole.
4. Disassemble the compression seal and place
through hole and J-box plate as shown. Tighten the
nut inside the octagon extension ring.
®