Model BCSW-FRP

Ducted Outlet Installations

Discharge Duct Turns - 

Duct turns located near the 

fan discharge should always be in the direction of the 
fan rotation.
Fan performance is reduced when duct 
turns are made immediately off the 
fan discharge. To achieve cataloged 
fan performance there 
should be at least 
three equivalent 
duct diameters of 
straight ductwork 
between the fan 
discharge and 
any duct turns.

Ducted Inlet Installations

Inlet Spin - 

Inlet spin is a frequent cause of reduced 

fan performance. The change in fan performance is a 
function of the intensity of spin and not easily defined. 
The best solution is proper duct design and airflow 
patterns. Turning vanes reduce the effects of inlet spin.

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Parallel Fan Installation

Non-Ducted Installations

Inlet Clearance - 

Installation of a fan with an open 

inlet too close to a wall or bulkhead will cause 
reduced fan performance. It is desirable to have 
one fan wheel diameter between parallel fan units 
and a minimum of three-fourths of a wheel diameter 
between the fan inlet and the wall.

Free Discharge - 

Free or abrupt discharge into a 

plenum results in a reduction in fan performance. The 
effect of discharge static regain is not realized.

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Inlet Duct Turns - 

Installation of a duct turn or elbow 

too close to the fan inlet 
reduces fan performance 
because air is loaded 
unevenly into the fan 
wheel. To achieve full fan 
performance, there should 
be at least three fan wheel 
diameter between the turn 
or elbow and the fan inlet.

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Installation

Installations with inlet or discharge configurations 
that deviate from this standard may result in reduced 
fan performance. Restricted or unstable flow at the 
fan inlet can cause pre-rotation of incoming air or 
uneven loading of the fan wheel yielding large system 
losses and increased sound levels. Free discharge 
or turbulent flow in the discharge ductwork will also 
result in system effect losses. Refer to the following 
diagrams for the most efficient installation conditions.

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

Three fan wheel diameters

One fan

wheel

diameter

3/4 to 

one fan

wheel

diameter

One fan

diameter

3/4 to 

one fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Rotat

io

n

R

ot

ati

on

R

ot

ati

on

Rotat

io

n

Turning

Vanes

Turning

Vanes

POOR

POOR

GOOD

POOR

GOOD

Length of Straight Duct

GOOD

1 Fan

Wheel

Diameter

One fan

wheel

diameter

One fan

wheel

diameter

3/4 to one

fan

wheel

diameter

One fan

diameter

3/4 to one

fan

wheel

diameter

SYSTEM EFFECT FACTORS CURVES

ST

ATIC PRESSURE LOS

S

1.2

1.0

0.8

0.6

0.4

0.2

0.0

0

5

10

15

20

25

30

35

40

45

FPM X 100

OUTLET VELOCITY

CUR

VE 

1

CUR

VE 

2

CUR

VE 

3

CUR

VE 4

Single Fan Installation

Содержание 474051

Страница 1: ...Code NEC the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or...

Страница 2: ...nt on motor If paint deterioration begins consideration should be given to touch up or repainting Fans with special coatings may require special techniques for touch up or repair Receiving Upon receiv...

Страница 3: ...doors to ensure that they are installed and secure Table of Contents General Information Receiving 2 Handling 2 Storage 2 Installation Recommendations BCSW FRP 4 Bases 5 Belt Guards 5 Drain Connection...

Страница 4: ...lose to the fan inlet reduces fan performance because air is loaded unevenly into the fan wheel To achieve full fan performance there should be at least three fan wheel diameter between the turn or el...

Страница 5: ...hen the motor is not mounted to the fan itself a bracket should also be located near it This information is intended as only a guide and actual field conditions may dictate another mounting location f...

Страница 6: ...n moving from one component to the other Inlet Cone Wheel Unit Size A Dimension Radial Gap Overlap maximum Tolerance in Tolerance mm Tolerance in Tolerance mm Tolerance in Tolerance mm 6 3 1 8 76 3 1...

Страница 7: ...y or failure of the following components 1 Fan shaft 2 Fan wheel 3 Bearings 4 V belt 5 Motor FAN FAN MOTOR MOTOR Aligning sheaves with a straight edge Improper sheave alignment Proper sheave alignment...

Страница 8: ...See warning below 2 Check all fasteners set screws and locking collars on the fan bearings drive motor base and accessories for tightness 3 Rotate the fan wheel by hand and assure no parts are rubbing...

Страница 9: ...the fan therefore special care is required when mounting them on the unit and maintaining them Refer to the following chart and the manufacturers instructions for grease types and intervals for vario...

Страница 10: ...s After replacing belts insure that slack in each belt is on the same side of the drive Belt dressing should never be used Do not install new belts on worn sheaves If the sheaves have grooves worn in...

Страница 11: ...ypass dampers Check filters and access doors Fan Doesn t Operate Electrical supply Check fuses circuit breakers Check for switches turned off or disconnected Check for correct supply voltage Drive Che...

Страница 12: ...______________________________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Note...

Отзывы: