background image

 Symptom 

          Possible cause 

        corrective action  

 

 

Frame is ‘racked’ causing blades to 

Adjust frame such that it is square 

 

 

bind on jamb seals 

and plumb 

 

 

 

Actuator linkage loose 

Close damper, disconnect power, adjust  

 

 

 

and tighten linkage

 

 

Defective motor 

Replace

 

 

Screws in damper linkage 

Locate screws and remove

 

 

Actuator linkage hitting wall or floor 

Damper installed too far into wall. Move

 

 

 

out to line designated on damper label.

 

 

Contaminants on damper 

Clean with a non-oil-based solvent

 

 

 

(see Damper Maintenance)

Heat 

No power supplied to the actuator

Push reset button located on backside 
of RRL or TOR.

damper trouble Shooting

The following is a possible cause and correction list for common concerns with the dampers.

damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, 
use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft 
bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such 
as dust.

Dampers and their actuator(s) must be maintained, cycled, and tested in accordance with:
•  The latest editions of NFPA 80, 90A, 92A, UL864, and local codes.
•  Actuator manufacturer recommendations.

Damper does not 
fully open and/or 
fully close

Damper does not
operate

RRL or TOR sensor
tripped

Copyright © 2007 Greenheck Fan Corporation

IMO-XXX series IOM Rev. 3 July 2007

Содержание 464603

Страница 1: ...able for damages resulting from misapplication or misuse of its products Greenheck will not be responsible for any installation or removal costs Greenheck will not be responsible for any service work or backcharges without prior written authorization Receiving and Handling Upon receiving dampers check for both obvious and hidden damage If damage is found record all necessary information on the bil...

Страница 2: ...ated a minimum of 6 in 152mm on the damper side and 18 in 457mm on the non damper side see figures 1 4 Any US Coast Guard type approved insulation with an A60 rating can be used The insulation is to be installed on the duct with 0 106 in 2 7mm steel pins and 1 12 in x 1 24 in x 0 4 in 28mm x 31mm x 10mm steel clips 2 Attaching Damper to Duct The damper can be installed to the duct using either bol...

Страница 3: ...code RATINGS Integral Switch Type Single Pole double throw Electrical Capacity 10 Amps 1 3 hp 120 or 240 Vac 1 2 Amp 125 Vdc 1 4 Amp 250 Vdc 5 Amps 120 Vac L lamp load 1 0 Amps 24 Vac 1 5 Amps 24 Vdc Temperature Limit 165 F standard primary sensor 212 F optional primary sensor L1 DAMPER INDICATOR LIGHTS L2 CLOSED POSITION OF THE DAMPER A BLUE MARKER INDICATE THE THE SWITCH WIRES WRAPPED WITH NOTE ...

Страница 4: ...oting The following is a possible cause and correction list for common concerns with the dampers Damper Maintenance Dampers do not typically require maintenance as long as they are kept dry and clean If cleaning is necessary use mild detergents or solvents If lubrication is desired for components such as axle bearings jackshaft bearings and jamb seals do not use oil based lubricants or any other l...

Отзывы: