Pellet burner GP xx sc 34
7.
FAILURES AND TROUBLESHOOTING.
Table 7.1. Description of the failures in the operation of a pellet burner from series “GP xx sc”
and methods for troubleshooting.
N
о
.
FAILURE
CAUSE
TROUBLESHOOTING
1.
In case the burner is
mounted to a hot
water boiler and the
temperature in the
heated premises is
too low
Insufficient heating
output
It is necessary to adjust the burner’s heating
output level.
The assigned
temperature is low
It is necessary to check the circulations water
temperature assignment in the burner’s control
module.
Low temperature
assignment by the
room thermostat (if
connected)
It is necessary to increase the room thermostat
temperature assignment.
2.
In case the burner is
mounted to a hot
water boiler and the
temperature in the
heated premises is
too high
Heating
output,
exceeding
the
consumption
It is necessary to increase the burner’s heating
output level.
The
assigned
temperature is high
It is necessary to decrease the assigned
temperature
High temperature
assignment by the
room thermostat (if
connected)
It is necessary to decrease the room thermostat
temperature assignment
3.
The burner is
switched ON but
there is no burning
process
No assignment for
operation
Check the assignment for operation by the
burner’s control module.
4.
Difficult pellets
ignition
The pellets are with
low quality
It is required to change the fuel, as its water
content is probably higher by the values needed
for normal operation of the appliance.
5.
The fuel ignition is
accompanied by
abnormal noise
Insufficient chimney
draught
It is necessary to check the condition of the
chimney and of the appliance, to which the
burner is mounted and to clean the ash deposits.
After cleaning it might be necessary to adjust the
operational parameters of the system – ask for
servicing assistance.
6.
Overheating of the
appliance, to which
the burner is
mounted
No heating load or
incorrectly adjusted
heating output level
of the burner, or of
the heat energy
consuming appliance
Check the heating system - burner - appliance for
correct operation and eventually adjust the
operation parameters – to be performed by
servicing specialist.
After the consuming appliance cools down and
the failure has been removed deactivate the
emergency thermostat (unscrew the protection
cover cap, press the button and screw the cap
back), after that restart the burner.
7.
No fuel ignition
No pellets in the fuel
hopper
The hopper from which the burner’s transport
auger intakes fuel must be refueled.
No pellets in the
burner’s combustion
chamber
The process of primary fuel ignition can be
restored by restarting the pellet burner.
Presence of non-
ignited or burned
pellets over the
burner’s fire-grate,
but there is no
burning process
Clean the gathered fuel from the burner’s fire-
grate.
If the ignition heating element is damaged or
inactive it must be replaced.