Check Your Chimney

Chimney must be clean, right size, properly constructed 

and in GOOD CONDITION. 

1. 

Installation must conform to requirements of the 

authority having jurisdiction or, in absence of such 

requirements, to the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54.

2. 

Boiler’s induced draft blower has 3” outlet. 3” X 

4” increaser 

fi

 tting is included in parts bag. Locate 

increaser 

fi

 tting on outlet of induced draft blower, and 

secure gas-tight with bead of furnished silicone sealant. 

Increaser 

fi

 tting is required on this boiler for Category I 

venting, and 4” is minimum permissible vent diameter. 

This does not imply vent connector is intended to be 4” 

diameter pipe. Vent connector shall be sized according 

to appropriate venting tables in the National Fuel 

Gas Code and may be required to be larger than 4” 

diameter.

NOTICE

Boiler installation for chimney venting is not 

complete unless increaser 

fi

 tting is located and 

secured.

3. 

These are high ef

fi

 ciency boilers with low stack or 

exhaust temperature.

4. 

Venting into masonry chimney without liner, line 

chimney from top to bottom with either:
A.  Listed Type B vent pipe 
B. Listed 

fl

 exible vent liner

C.  Poured ceramic liner. 

5. 

Outside chimneys should not be used unless they are 

(choose one of the following):
A.  Enclosed in a chase
B.  Lined with Type B vent pipe
C. Use listed 

fl

 exible vent liner

D. Use certi

fi

 ed chimney  lining system

6. 

Vent connector from boiler to chimney should run as 

directly as possible with as few elbows as possible.

7. 

Where possible, it is recommended to common vent 

water heater and boiler. Consult appropriate Vent 

Sizing Tables in National Fuel Gas Code for speci

fi

 c 

requirements of multiple appliance venting.

8. 

Boiler is only appliance connected to vent, Type B vent 

pipe is recommended for vent connector.

9. 

Slope pipe up from boiler to chimney not less than 1/4” 

per foot (21mm/m).

10. 

End of vent pipe must be 

fl

 ush with inside face of 

chimney 

fl

 ue. Use sealed-in thimble for chimney 

connection.

11. 

Fasten sections of vent pipe with sheet metal screws to 

make piping rigid. Use stovepipe wires to support pipe 

from above.

12. 

Do not connect to 

fi

 replace 

fl

 ue.

13. 

Do not install damper on this boiler.

Minimum Vent Pipe Clearance

• Use Type B vent pipe through crawl space. Where vent 

pipe passes through combustible wall or partition, use 

ventilated metal thimble. Thimble should be 4 inches 

larger in diameter than vent pipe. 

• Boiler installed with single wall vent, must have 6” 

clearance between its surface and any combustible 

material. New Type B gas vent or 

fl

 exible liner must be 

installed in accordance with instructions furnished with 

vent. Maintain clearances as speci

fi

 ed for vent pipe.

• Verify vent pipe is 

fi

 re-stopped where it goes through 

fl

 oor or ceiling. It should have approved vent cap with 

clearances from roof.  If clearances are less than shown, 

have vent checked by local authorities.  Figure 7, Page 11 .

• Vent connectors serving appliances vented by natural 

draft shall not be connected into any portion of 

mechanical draft systems operating under positive 

pressure.

VENT INSTALLATION

Содержание GMPVB

Страница 1: ...VB Gas Fired Hot Water Induced Draft Boiler INSTALLATION OPERATION MAINTENANCE MANUAL Series II Models GMPVB 42 GMPVB 150 GMPVB 75 GMPVB 188 GMPVB 112 GMPVB 225 Manufactured by ECR International Inc 2...

Страница 2: ...is boiler must be performed by a qualified installer TO THE INSTALLER Leave all instructions with boiler for future reference When this product is installed in the Commonwealth of Massachusetts the in...

Страница 3: ...d be based upon Net AHRI Rating being equal to or greater than calculated heat loss of building Manufacturer should be consulted before selecting a boiler for installations having unusual piping and p...

Страница 4: ...4 DIMENSIONS Model Width A GMPVB 42 11 GMPVB 75 14 1 4 GMPVB 112 17 1 2 GMPVB 150 20 3 4 GMPVB 187 24 GMPVB 225 27 1 4...

Страница 5: ...ting installation See rating and capacity table 8 When installed in utility room door should be wide enough to allow largest boiler part to enter or to permit replacement of another appliance such as...

Страница 6: ...s communicating directly or by ducts with outdoors Two Permanent Opening Method Provide opening commencing within 12 inches of top and second opening commencing within 12 inches of bottom enclosure Di...

Страница 7: ...all be installed to relief valve outlet connection to avoid burns scalding or water damage due to discharge of steam and or hot water during operation Discharge line shall connect to relief valve outl...

Страница 8: ...8 INSTALLATION SYSTEM PIPING Figure 3 Forced Hot Water Typical Piping Figure 4 Forced Hot Water Typical Piping With Zone Control Valve...

Страница 9: ...exposed to refrigerated air circulation piping system shall be equipped with flow control valves or other automatic means to prevent gravity circulation of boiler water during cooling cycle INSTALLATI...

Страница 10: ...as directly as possible with as few elbows as possible 7 Where possible it is recommended to common vent water heater and boiler Consult appropriate Vent Sizing Tables in National Fuel Gas Code for sp...

Страница 11: ...n to gas vents or chimneys vent installations shall be in accordance with Venting of Equipment of the National Fuel Gas Code ANSI Z223 1 NFPA 54 or applicable provisions of the local building codes Fi...

Страница 12: ...ng system Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Place in operation the...

Страница 13: ...eter 90 elbow or 3 feet of straight pipe for 3 diameter 90 elbow 2 3 4 5 Section Boilers use 3 vent pipe for 6 7 Section Boilers use 4 vent pipe CHOICE OF VENT PIPE MATERIAL U L Listed Z Flex Z Vent S...

Страница 14: ...0 elbow pointing down fitted with a minimum 1 4 mesh screen to keep out rodents and birds The elbow shall be of the same material and size as vent pipe The elbow exit should be at least 6 away from ex...

Страница 15: ...egulators and relief equipment See Figure 9 United States Terminate vent system at least 4 feet 1 22m horizontally from and in no case above or below unless a 4 feet 1 22m horizontal distance is maint...

Страница 16: ...fore operating appliance B For Heat Fab Saf T Vent stainless steel vent pipe use a high temperature silicone sealant rated for 550 F The outside of the male end and inside of the female end of the pip...

Страница 17: ...boiler to prevent collection of condensate throughout the assembly 7 Allow the sealant to cure for 24 hours before operating the appliance D For ProTech Systems FasNSeal stainless steel vent pipe no...

Страница 18: ...ls Power Venter 2 3 4 5 SWG 4D 6 7 SWG 5D Some possible reasons for using a power venter for sidewall venting 1 May be preferred by local codes 2 Need a vent piping run beyond 30 9 1m but not more tha...

Страница 19: ...g Install manual shut off valve in vertical pipe about 5 feet 1 5m above floor See Figure 10 Tighten all joints securely Propane gas connections should only be made by licensed propane installer Two s...

Страница 20: ...pacity BTU Per Hour Input Includes Fittings 1 1 20 92 000 190 000 350 000 625 000 40 63 000 130 000 245 000 445 000 60 50 000 105 000 195 000 365 000 Table 6 PROPANE GAS Length of Pipe Ft Pipe Capacit...

Страница 21: ...ot install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering therm...

Страница 22: ...er water temperature reaches high limit set point high limit contacts open cutting power to blower and pilot control Burners extinguish and blower stops Circulator pump continues to run as long as the...

Страница 23: ...23 WIRING DIAGRAMS Figure 12 Control Module Damper is not an option...

Страница 24: ...s Repeat until you have covered every radiation unit in system End at highest unit in system If units have automatic vents manual venting is unnecessary but it will speed up proper filling of system I...

Страница 25: ...ob WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance is equipped with an ignition device whi...

Страница 26: ...quire primary air adjustment and are not equipped with primary air shutters Main burner flames form sharp blue inner cones in softer blue outer mantel with no yellow Puffs of air from blow ing on flam...

Страница 27: ...supply to burners 3 Turn your thermostat up to call for heat and let your boiler run until temperature of water reaches limit setting Gas valve shuts off and circulator keeps running until thermostat...

Страница 28: ...ater left in to freeze will crack pipes and or boiler Cleaning Your Boiler And Burners Flue passages between sections should be examined yearly and cleaned if necessary To clean Remove burners pilot a...

Страница 29: ...trical contact Check all control terminals and wire joints Chimney flue is blocked Pressure switch will not close and pilot spark will not operate to start pilot Have your service technician check and...

Страница 30: ...o expand as temperature changes Diaphragm type tank can be mounted on air purger fitting or at any convenient place in supply or return line AIR ELIMINATING FITTING AIR PURGER Air purger is used to re...

Страница 31: ...ed Factory Pressure Switch Set point 0 4 wc for 2 5 section boilers 0 5 w c for 6 7 section boilers Rollout Switch FLAME ROLLOUT SAFETY SHUTOFF Rollout switch is temperature sensitive fuse link device...

Страница 32: ...TT using wire nuts Ensure remaining Molex plug connectors have not worked loose during transit Check sensing bulb is fully inserted in well and is not loose A 3 Adjusting Settings To discourage unauth...

Страница 33: ...ion was not detected and delay is called before retry Recycle delay Flame signal was lost and delay is called before retry 11 Wait for pressure switch to open failed to close Inducer is still off Pres...

Страница 34: ...out models must be reset through key buttons and display On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module c...

Страница 35: ...ut Soft lockout is reset after one hour if alarm reason disappears 63 Soft lockout maximum number of recycles exceeded Soft lockout 64 Soft Lockout electronics failure On board self diagnostics detect...

Страница 36: ...ged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set ther...

Страница 37: ...Date Service Performed Company Name Tech Initials Company Address Phone...

Страница 38: ...NOTES...

Страница 39: ...Date Service Performed Company Name Tech Initials Company Address Phone...

Страница 40: ...Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...

Отзывы: