5 - CONNECTING SUPPLY & RETURN PIPING

Figure 1 -  Safety Relief Valve

Check local codes 

for maximum 

distance from floor 

or allowable safe 

point of discharge.

Discharge Line

 Safety Relief Valve

WARNING

Burn or Scald Hazard. Discharge line shall be installed to relief valve outlet connection to avoid burns, 

scalding, or water damage due to discharge of steam and/or hot water during operation.
Discharge line shall:

• 

connect to relief valve outlet and piped down to safe point of disposal. Check local codes for maximum 

distance from floor or allowable safe point of discharge.

• 

be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge 

line;

• 

have no intervening shutoff valve between safety relief valve and discharge to atmosphere (do not plug or 

place any obstruction in discharge line.

• 

terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing;

• 

allow complete drainage of the valve and the discharge line;

• 

be independently supported and securely anchored to avoid applied stress on the relief valve;

• 

be as short and straight as possible;

• 

terminate with plain end (not threaded);

• 

be constructed of material suitable for exposure to temperatures of 375° F (191°C); or greater.

Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation 

requirements.

!

   

 P/N# 240011109, Rev. C [07/22/2015]

Содержание GMGW Series

Страница 1: ...N OPERATIONS AND MAINTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com Models GMGWB045FE GMGWB120FE GMGWB070FE GMGWB145FE GMGWB096...

Страница 2: ...a level to 2 000 ft 610m above sea level United States over 2000 ft 610m above sea level Reduce input rate 4 for every 1 000 ft 304m above sea level 2 Net AHRI Water Ratings shown based on piping and...

Страница 3: ...1 GMGWB070FE 15 7 5 28 2015 16 415 16 1 GMGWB096FE 15 7 5 28 2015 16 415 16 1 GMGWB120FE 19 9 6 29 217 16 57 16 1 GMGWB145FE 19 9 6 29 217 16 57 16 1 GMGWB170FE 22 113 16 7 30 2115 16 515 16 1 GMGWB19...

Страница 4: ...agram 18 12 Lighting Instructions 20 13 Normal Sequence Of Operation 21 14 General Instructions 21 15 Checking Gas Input Rate To Boiler 23 Appendix A Control Module 24 A 1 Installation Environment Con...

Страница 5: ...NCE WARNING Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modification substitution or elim...

Страница 6: ...and service circulator replacement condensate trap control replacement etc 6 Locate boiler on level solid base as near chimney as possible and centrally located with respect to heat distribution syste...

Страница 7: ...filtration rate is less than 0 40 air changes per hour See Table 3 for space with boiler only Use equation for multiple appliances Volume 50 ft3 x Total Input Mbh Known Air Infiltration Rate See Table...

Страница 8: ...ater than that of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any ob...

Страница 9: ...relief valve Systems with automatic fill valves require back flow prevention device Install discharge piping from safety relief valve See Warning Page 8 When boiler is connected to heating system util...

Страница 10: ...T CIRCULATOR A PRESSURE REDUCING VALVE PROPER BACKFLOW PROTECTION DEVICE GATE VALVE PURGE VALVE NOTICE Circulators in following illustrations are mounted on system supply side mounting on system retur...

Страница 11: ...s Page 9 5 CONNECTING SUPPLY AND RETURN PIPING Figure 3 Bypass Piping Automatic Mixing Valve See Bypass Piping Options Page 9 BOILER WATER INLET ALTERNATE CIRCULATOR LOCATION TO SYSTEM FROM SYSTEM CIR...

Страница 12: ...12 5 CONNECTING SUPPLY AND RETURN PIPING Figure 5 Single Zone System With DHW Priority Figure 6 Multi Zone System with Circulators and DHW Priority P N 240011109 Rev C 07 22 2015...

Страница 13: ...NG SUPPLY AND RETURN PIPING Figure 7 Multi zone System With Zone Valves And DHW Priority With Circulator Figure 8 Multi zone System With Zone Valves And DHW Priority With Zone Valve P N 240011109 Rev...

Страница 14: ...ion of the common venting system the common venting system should be re sized to approach the minimum size determined using the appropriate tables in Chapter 13 of the National Fuel Gas Code ANSI Z223...

Страница 15: ...e in visible location following installation 5 Thermostat s heat anticipator must be adjusted to match total current draw of all controls associated with boiler during heating cycle 8 VENT DAMPER INST...

Страница 16: ...ing with hooks straps bands brackets hangers or building structure components to prevent or dampen excessive vibrations and prevent strain on gas connection Boiler will not support piping weight Use t...

Страница 17: ...connection 4 Line power connections 5 LWCO kit 550002998 includes wiring instructions and wiring diagrams If using a different LWCO refer to the specific instructions provided with that unit See wiri...

Страница 18: ...2 Integrated High Limit Electronic Ignition Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life...

Страница 19: ...19 11 WIRING DIAGRAM Figure 13 Integrated High Limit Electronic Ignition Control P N 240011109 Rev C 07 22 2015...

Страница 20: ...ff Gas To Appliance and call qualified service technician or your gas supplier TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if...

Страница 21: ...ave them repaired immediately Check and maintain circulators Refer to circulator manufacturer s instructions Inspect venting system at the start of each heating season Check vent pipe from boiler to c...

Страница 22: ...ns of corrosion rust or scale buildup Area around boiler must be kept clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating ai...

Страница 23: ...ter column from specified pressure Primary air adjustment is not necessary therefore air shutters are not furnished as standard equipment Air shutters can be furnished on request where required by loc...

Страница 24: ...loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater Verify vent damper connection is made See page 15 A 3 Adjusting Settings To discourage unauthorized changi...

Страница 25: ...n Appropriate alarm is sent OR Flame signal sensed out of sequence during post purge Appropriate alarm is sent OR Flame signal present when not expected Appropriate alarm is sent 17 Pilot valve diagno...

Страница 26: ...set at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified service agent to...

Страница 27: ...ppears 63 Soft lockout maximum number of recycles exceeded After main burner ignition Soft lockout 64 Soft Lockout electronics failure On board self diagnostics detected error Soft lockout 65 Over tem...

Страница 28: ...ck for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire from MV terminal Turn on power and set thermostat to ca...

Страница 29: ...29 NOTES P N 240011109 Rev C 07 22 2015...

Страница 30: ...30 NOTES P N 240011109 Rev C 07 22 2015...

Страница 31: ...31 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD P N 240011109 Rev C 07 22 2015...

Страница 32: ...ture is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE...