4. OPERATION
Once the batteries are connected well, simply press On/Off button to enable the output of the battery pack.
24V
Over view
48V
Over view
Note
:
One group of LB24V can be stacked up to 4 layers, and up to 6 in parallel connection
One group of LB48V can be stacked up to 2 layers, and up to 6 in parallel connection.
1.Switch on: press On/Off button to switch on the battery, then the battery will do self-inspection before
enable output. The LED will show the SOC.
2.Switch off: press and hold On/Off button for 3 seconds, the battery will shut down directly.
Description for Communication port
4.1 Switch On / Off
Picture PIN Description
1
2
3
4
5
6
7
8
Trigger-GND
Trigger-VCC
NC
COMM-GND
RS485-B
RS485-A
CANL
CANH
The SOC of the battery is shown by the LED
4.2 Description for LED
DIP SWITCH
1-4
5
Communication Address
Termination Resister
Note: The battery need to be fully charged for at least once in one month to ensure the accurate SOC
calculation.
100% 75% 50% 25% Flashing SOC<10%
For pure off grid system ,the PV awake wire need to be connected with MPPT charge controller if the battery
pack is charged by solar panels only . The connection diagram as below :
4.3 ON / OFF or SOC Led (Mode or SOC)
BATTERY
MODE
ON/OFF
SOC
REMARK
GREEN
LED
RED
LED
LED1
LED2
LED3
LED4
POWER
OFF
OFF
OFF
OFF
OFF
OFF
OFF
POWER
ON
OFF
ON
ON
ON
ON
ON
STANDBY
OFF
OFF
SOC
SOC<10%(DEFAULT ):
LED1
FLASH
NORMAL
ON
OFF
RUNNING/SOC
SOC<10%(DEFAULT ):
LED1
FLASH
DISCHARGE
ON
OFF
SOC
SOC<10%(DEFAULT ):
LED1
FLASH
CHARGE
FLASH
OFF
RUNNING
LOW
POWER
FLASH
OFF
OFF
FAULT
OFF
ON
ON
OFF
OFF
OFF
BATTERY
VOLTAGE
HIGH
OFF
ON
OFF
OFF
BATTERY
VOLTAGE
LOW
ON
ON
OFF
OFF
CELL
VOLTAGE
HIGH
OFF
OFF
ON
OFF
CELL
VOLTAGE
LOW
ON
OFF
ON
OFF
CHARGING
CURRENT
HIGH
OFF
ON
ON
OFF
DISCHARGING
CURRENT
HIGH
ON
ON
ON
OFF
BMS
TEMPERATURE
HIGH
OFF
OFF
OFF
ON
BMS
TEMPERATURE
LOW
ON
OFF
OFF
ON
CELL
TEMPERATURE
HIGH
OFF
ON
OFF
ON
CELL
TEMPERATURE
LOW
ON
ON
OFF
ON
CURRENT
SENSOR
ABNOMAL
24V
Over view
48V
Over view
Содержание LB24150