Air-to-water Heat Pump Split Versati
24
SPLIT TYPE
Outdoor unit
Indoor unit
B
B
B
Indoor unit
Outdoor unit
Outdoor unit
A
A
A
Indoor unit
Oil bend
Model
Pipe size
(Diameter:Φ)
Length B
Elevation A
Additional
refrigerant
gas
Liquid
Standard
Max.
Standard
Max.
GRS-CQ8.0Pd/NhH-M
1/2"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ10Pd/NhH-M
1/2"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ12Pd/NhH-M
5/8"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ14Pd/NhH-M
5/8"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ16Pd/NhH-M
5/8"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ12Pd/NhH-E
5/8"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ14Pd/NhH-E
5/8"
1/4"
5m
15m
0m
15m
0g/m
GRS-CQ16Pd/NhH-E
5/8"
1/4"
5m
15m
0m
15m
0g/m
Notes
(a) the refrigerant charge for the 8/10kW model is as high as 1.84kg. It is the allowed maximum charge for the
split type unit. If more charge is required, the indoor ventilation equipment must be equipped. Therefore, in the
case of increasing the length of the connecting tube, there is no need to add refrigerant to the unit.