Troubleshooting:
Yes
No
No
“
d5
”
midst pipe
temperature sensor
error
Is the terminal between
mainboard and ambient temperature
sensor loose or any foreign objects
inside the terminal?
If it is loosened or there are
foreign objects, retighten it
after treatment.
Check if the temperature
sensor is abnormal
Yes
Replace temperature
sensor
Check if the circuit is
abnormal
Yes
Replace the main
control board
(22) “d6” Outlet pipe temperature sensor error
Error display:
IDU displays
.
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error.
Possible reason
:
1) Poor contact between outlet pipe temperature sensor and terminal in mainboard interface.
2) Outlet pipe temperature sensor is abnormal.
3) Detecting circuit is abnormal.
(23) “d9” Jumper cap error
Error display:
IDU displays
.
Error judgment condition and method:
Possible reason
:
If jumper cap model doesn’t match with mainboard, report the error:
1) Jumper cap is not installed.
2) Jumper cap model is wrong.
3) Detecting circuit is abnormal.
Содержание UM600PH/A-M
Страница 4: ...4 PRODUCT...
Страница 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Страница 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Страница 36: ...GREE Duct type Ducted Type Split Air Conditioner Units 36 3 Select language 4 Select system of units...
Страница 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Страница 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Страница 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Страница 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Страница 117: ...GREE Duct type Ducted Type Split Air Conditioner Units 117 UML500H A M P UML600H A M P UMD400PH A M P...
Страница 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Страница 121: ...JF00303352 JF00304250...