Multi Variable Air Conditioners Ducted Type Indoor Unit
11
Fig 4.3.6 Fig 4.3.7 Fig 4.3.8
(7) The installation height of raising pipe for drainage should be lower than B. The gradient
from raising pipe towards drainage direction should be at least 1%~2%. If the raising
pipe is vertical with the unit, the raising height should be less than C.
Unit: mm(in.)
Fig 4.3.9
Unit: mm(in.)
Model
A
B
C
GMV-ND07PLS/A-T(U)
GMV-ND09PLS/A-T(U)
GMV-ND12PLS/A-T(U)
GMV-ND14PLS/A-T(U)
GMV-ND18PLS/A-T(U)
GMV-ND22PLS/A-T(U)
155(6-1/8)
845(33-1/4)
795(31-5/16)
(8) Drain pipes should have a downward slope of at least 1%~2%, in order to prevent pipes
from sagging, install hanger bracket at intervals of 1000~1500mm (39-3/8~59 in.).
Unit: mm(in.)
Fig 4.3.10