U-MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL
41
Figure 2-7-11
Note:
①
In order to realize the MODBUS interface function, the address mode of the unit must be set
into long-distance control address mode; you can not set it into centralized control address mode,
otherwise, this function can not be realized;
②
The unit can not be connected to MODBUS and centralized controller at the same time; only
one of them can be selected;
③
255 sets of unit in maximum can be connected in the same network; the unit addresses in the
same network must be different, otherwise, the unit control will be affected;
④
Perform wiring when the unit power is cut off.
7.2.4 Connect to interface of centralized controller:
The indoor unit is with the interface of centralized controller. When centralized controller is
connected, centralized control of unit can be realized when the wired controller is not connected;
(1) Interface instruction:
1) The printing is COM-BMS2, COM-BMS3 and the interface type is B2B-XH-K3;
2) Electrical characteristic: none;
3) Working principle: centralized control the communication of indoor mainboard and realize the
unit control;
(2) Function instructions:
In order to achieve this function, set the address mode and address through wired controller. Please
Содержание U-MATCH B Series
Страница 4: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 1 PRODUCT ...
Страница 14: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 11 CONTROL ...
Страница 52: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 49 INSTALLATION ...
Страница 75: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 72 MAINTENANCE ...
Страница 96: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 93 ...
Страница 125: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 122 Model GFH36D3F2I exploded view and spare parts list ...
Страница 127: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL 124 Model UMAT36HP230V1BD exploded view and spare parts list ...