Pipe between ODU and the 1 indoor branch
The 1 indoor branch
st
st
Dimension of outdoor connection pipe:
Basic module
Pipe dimension
Connection method
Gas pipe (mm/inch)
Liquid pipe(mm/inch)
GMV-HY36WLT/A-T(U)
Φ15.9(5/8)
Φ9.52(3/8)
Flared joint
GMV
-HY48WLT/A-T(U)
Φ15.9(5/8)
Φ9.52(3/8)
6.3 Selection of Indoor Branches
Select indoor branches according to the total capacity of downstre
am indoor units.
ODU
IDU
Indoor branches
R410A
Refrigerant system
Total capacity of downstream indoor units C (Btu/h)
Model
Y type branch
C
6800
FQ01A
6.4 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor units; if the capacity exceeds that of the outdoor
unit, capacity of outdoor unit prevails.
Photovoltaic Direct-driven
VRF