REFRIGERATION& PIPING SPECIFICATIONS
REFRIGERANT CHARGE
Model Number
Refrigerant
Type
Factory System
Charge (oz.)
Max Total Pipe
Length Without Adding
Refrigerant (ft.)
Additional
Charge Level
(oz./ft.)
NEO09HP115V1AO
R-410A
41.2
25
0.2
NEO12HP115V1AO
R-410A
45.9
25
0.2
NEO09HP230V1AO
R-410A
45.9
25
0.2
NEO12HP230V1AO
R-410A
45.9
25
0.2
NEO18HP230V1AO
R-410A
49.4
25
0.2
NEO24HP230V1AO
R-410A
56.4
25
0.
5
NEO30HP230V1AO
R-410A
84.7
25
0.
5
NEO36HP230V1AO
R-410A
91.7
25
0.
5
REFRIGERANT PIPING LENGTHS
Model Number Min. Pipe Length
for System (ft.)
Max Pipe Length for
System (ft.)
Max Elevation between
Outdoor & Indoor Units (ft.)
NEO09HP115V1AO
10
50
33
NEO12HP115V1AO
10
6
6
33
NEO09HP230V1AO
10
50
33
NEO12HP230V1AO
10
66
33
NEO18HP230V1AO
10
82
33
NEO24HP230V1AO
10
82
33
NEO30HP230V1AO
10
100
33
NEO36HP230V1AO
10
100
33
11
© 2014 Gree Electric Appliance, Inc.