D Series Modular Air-cooled Scroll Chillers 

1

Safety Notices (Please be sure to abide )

 WARNING

: If not abide strictly, it may cause severe damage to the unit or the people.

 

NOTE

: If not abide strictly, it may cause slight or medium damage to the unit or the people.

 This sign indicates that the operation must be prohibited. Improper operation may cause severe 

damage or death to people.

 This sign indicates that the items must be observed. Improper operation may cause damage to 

people or property.

 

Safety Notices for On-site Installation

WARNING

• 

Installation should be performed by qualified servicemen who have taken specialized training and 
acquired corresponding certificates in accordance with relative laws, regulations and this manual, 
otherwise it would lead to damage to the unit, water leakage, electrocution, or fire hazards etc.

• 

The unit should be installed on the smooth foundation capable of supporting the unit and fixed with screw 
bolts. The foundation with inadequate strength would lead to leakage, turn-over or personal injury or 

death.

• 

Special lines should be used for electric installation by qualified electricians. Lines with inadequate 
capacity would lead to electrocution or fire hazards.

• 

Make sure each connector is properly tightened; otherwise it would lead to over-temperature or fire 

hazards etc.

• 

When installation is finished, please check for the drainage lines, pipelines, and electric lines to prevent 
water leakage, electrocution or fire hazards.

• 

This equipment should be installed where the drainage system can work well. Never block the drain hole. 
Improper drainage system would lead to drainage difficulty and make the unit suffer from malfunctions.

• 

When there is something unusual (like stinky smell) during installation or commissioning, please cut off 
the main power at once and then contact the after-sales service center. This ongoing unusual condition 
will damage the air conditioning unit and lead to electrocution or fire hazards.

• 

When refrigerant leaks, take corrective measures as soon as possible to prevent oxygen depletion by 
increased refrigerant concentration.

CAUTION

• 

Do not install the unit where there is high-intensity magnetic field or it is highly basic or acid or the voltage 

is quietly unstable.

• 

Do not install the unit where there would be leaked inflammable gas, as it would lead to fire hazards.

• 

The outer casing of the unit should be grounded. Do not connect the grounding line to the gas line, water 
line, lightning rod or communication line, otherwise it would lead to .

• 

Do not stand on the unit or place other object on it.

• 

Do not insert fingers or other objects into the outlet grill to prevent damage to the unit or personal injury 

or death.

• 

Do not start or stop the unit by inserting or drawing out the power plug.

• 

Do not let children play with this unit.

• 

The unit should be equipped with the leakage protector which should be installed in accordance with 
electric technical standards. Uninstallation or incorrect installation would lead to electrocution. Do electric 
leakage detection after electric installation is finished.

• 

Volatile liquid like thinner or gasoline would damage appearance of the unit. (Only clean the outer casing 
with of the unit with soft dry cloth or wet cloth with neutral detergent. )

Содержание LSQWRF130M/D-M

Страница 1: ...nual carefully before operation and retain it for future reference If you have lost the Owner s Manual please contact the local agent or visit www gree com or send an email to global gree com cn for t...

Страница 2: ...spection which may impact the normal operation of unit please do not disassemble the unit by yourself You can contact with the special maintenance center of our company if necessary 3 For personal inj...

Страница 3: ...shops in light industry and on farms or for commercial use by lay persons DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is...

Страница 4: ...er Operation Instructions 16 5 4 Reset for erasing error 26 5 5 Menu Structure 27 6 Electric Control Cabinet 31 6 1 Wiring for Output Control Lines 31 6 2 Specification of Power Cord and Air Switch 31...

Страница 5: ...Charging 37 7 9 Removal of the Compressor 37 7 10 Freeze Protection 38 7 11 Routine Maintenance 38 7 12 Precautions 39 8 Troubleshooting 39 8 1 Error Lists and Troubleshooting Measures 39 8 2 After s...

Страница 6: ...em can work well Never block the drain hole Improper drainage system would lead to drainage difficulty and make the unit suffer from malfunctions When there is something unusual like stinky smell duri...

Страница 7: ...f electrocution Do not connect the groundling line to the gas tank water line lightning rod or telephone line Only specialized accessories and parts are allowed for installation otherwise it would lea...

Страница 8: ...t of used in quite long time add anti freezing agent to water or drain the water system otherwise it would make the shell and tube crack and then leak Do not use the fuse out of the normal range or re...

Страница 9: ...fire hazards Besides make sure insulation of power lines always in good condition Connection between two ends of the power lines is not allowed When its length is not enough please contact the after s...

Страница 10: ...ith the wired controller It overcomes the problem which would occur to the product of other manufacturer that the whole system would fail to work properly when the fixed master unit malfunctions Compa...

Страница 11: ...Maximum and minimum water operating pressures y y The maximum inlet water pressure is 1 0 106 Pa y y The minimum inlet water pressure is 0 2 106 Pa 3 Operating Range Item Water Side Air Side Water Flo...

Страница 12: ...3 Outline Dimension 1 Graph for the shape and dimensions for LSQWRF65M D M LSQWRF80M D M Unit mm 2 Graph for the shape and dimensions for LSQWRF65M NaD M LSQWRF80M NaD M Unit mm 1000 2160 2040 1396 2...

Страница 13: ...rs 8 3 Graph for the shape and dimensions for LSQWRF130M D M Unit mm 2160 1650 1617 Ground bolt 4 M12 4 Graph for the shape and dimensions for LSQWRF130M NaD M Unit mm 2226 1676 2026 Ground bolt 4 M12...

Страница 14: ...shape and dimensions for LSQWRF160M D M Unit mm 403 2160 1676 2226 1650 2026 Ground bolt 4 M12 1617 Ground bolt 4 M12 317 6 Graph for the shape and dimensions for LSQWRF160M NaD M Unit mm 403 337 1676...

Страница 15: ...d tube heat exchanger before connecting the water tube and check if the water pipe is clean 6 Check if the installation and operation are within the allowable conditions When there is damager or any o...

Страница 16: ...ts Distance between each single unit shall be keep 1m as a minimal 3 Enough space shall be left for service and ventilation Be sure there is at least 2m between the equipment and any barrier and it is...

Страница 17: ...ken carfelly for the water system 1 Each water inlet and outlet should be labeled properly to avoid misconnection 2 A flexible connector should be used at the chilled water outlet to reduce vibration...

Страница 18: ...e life of the unit make sure the water capacity is more than 1 6 of total rated flow rate per hour of each module If necessary a water tank will be installed 9 Note never use salt mixture to prevent t...

Страница 19: ...water system open in order to drain the evaporator and condenser completely Diameters of Entering Leaving Water Pipes Diamter mm Cooling load kW DN15 0 3 DN20 3 7 DN25 5 13 DN32 10 25 DN40 15 38 DN50...

Страница 20: ...s off 4 On Off button For controlling unit conversion between start and stop press the button for 3 seconds in stop state to start the unit and press the button for 3 seconds in operation state to sto...

Страница 21: ...ton for 3 seconds and stop the unit and at that time the operation indicator is off When ambient temperature is lower than 16 and Run Mode is Heat pressing On Off button the following prompt window co...

Страница 22: ...hin 10 minutes the system will automatically go back to the above default home page menu Home Page Press the Exit button on the wired controller at any time for enough times you can go back the defaul...

Страница 23: ...nge a selected object and press the Exit button to cancel the model set Different models have different display modes If you is setting a mode in the startup state the following prompt will appear Set...

Страница 24: ...to change value or state of a selected object Press the Exit button to quit the page and go back to the previous menu and save set values y y Sound On set Select Sound press the Confirm button and th...

Страница 25: ...e and press the Confirm button to go to corresponding page A module followed with means having a failure The following menu will display after going to the module Press the Exit button to quit the pag...

Страница 26: ...ress the Exit button to quit the menu page and go back to the previous menu When page 1 is present on the screen press the Reset button and the Exit button simultaneously for 3 seconds and C Water Tin...

Страница 27: ...o to the pages as shown in the following drawings Sys State Cool Heat Defrost Anti fre Page 1 Page 2 Page 3 Page 4 Exthalpy Inc EXV 2 Page 5 Dis T Sensor 1 Lock Unlock Lock Unlock Dis T Sensor 2 Page...

Страница 28: ...Fan1 OverLoad Pro Sys 1 Dis HighTemp C Water Flow Switch Fan3 OverLoad Pro Jumper Error Comp 2 HP Pro Comp 2 OverLoad Pro Fan2 OverLoad Pro Sys 2 Dis HighTemp H Water Flow Switch Comp 1 LP Pro Comp 2...

Страница 29: ...ost and press Exit to quit the interface and go back to the previous menu When manual defrost is on and the two systems do not stop defrosting completely the following prompt will come up Do you need...

Страница 30: ...is dependent on unit model If this Item is not existent for a certain model NA would be present on the display zone for corresponding Item y y System level Parameter Set User shall not use the functi...

Страница 31: ...for erasing error On any interface press Reset the following page appears Clear Error Remove Dis Sensor Press Exit to go back to the previous interface and press Confirm to select function as shown in...

Страница 32: ...D Series Modular Air cooled Scroll Chillers 27 5 5 Menu Structure...

Страница 33: ...Water Tin Water inlet temperature checking C Water Tout Water outlet temperature checking H Water Tin Hot water inlet temperature checking H Water Tout Hot water outlet temperature checking C AVER To...

Страница 34: ...T Sensor 2 Exhaust sensor 2 status checking Water_Out EXV Water out electromagnetic valve status checking Water_In EXV Water in electromagnetic valve status checking Error View Error checking Comp 1...

Страница 35: ...unction LP Sensor1 Error Low voltage sensor 1 malfunction LP Sensor2 Error Low voltage sensor 2 malfunction H Water in Sensor Hot water in sensor malfunction H Water out Sensor Hot water out sensor ma...

Страница 36: ...M NaD M 50 25 25 125 LSQWRF160M D M LSQWRF160M NaD M 70 35 35 160 Notes a The specifications of the breaker and power cable listed in the table above are determined based on the maximum power maximum...

Страница 37: ...a rubber or plastic ring to avoid any damaged caused by the sharp edge of the metal sheet 3 The power cord close to the electric box must be attached securely to prevent the terminal block of the elec...

Страница 38: ...D Series Modular Air cooled Scroll Chillers 33 6 5 Wiring betwween Chilled Modules 130 160 Electric control cabinet 130 160 Electric control cabinet...

Страница 39: ...t bit and 4 for the highest bit Comparison drawings are as follows Caution only in the condition of power supply shutoff can toggle switches be set 6 7 Jumpers When it is required to replace the main...

Страница 40: ...properly 7 2 Requirements on Water System and Water Quality Be sure to open the water pump after the water system has been flushed times and the water quality has met the requirements and meanwhile be...

Страница 41: ...ot yet been drained up Do not restart the unit when the unit has been stopped less than for 6 minutes 7 4 Routine Startup Shutdown It is recommended to start the system through the wired controller in...

Страница 42: ...inutes and keeps below 100Pa charge refrigerant at the low pressure side as per the rated specification on the nameplate 4 Refrigerant charge will be affected by the ambient temperature When charged r...

Страница 43: ...lity of occurrence of faults Record and keep the running status of the unit to facilitate troubleshooting for the servicemen Daily Maintenance 1 Check the circulating water pump and the flow rate 2 Ch...

Страница 44: ...suction pressure Let part of refrigerant out Too low discharge pressure The suction pressure is too low Refrigerant leaks or is charged insufficiently See Too low suction pressure Take leakage test an...

Страница 45: ...control circuit fails to get through There is no electric currrent High or low pressure protection acts The contact coil is blown out Power phase is wired improperly The water system malfunctions and...

Страница 46: ...V Allowable range 380 415V Voltage fluctuation Allowable value 5 Interphase insulation resistance Phase ground insulation resistance Rab Rbc Rac Min allowable value Rag Rbg Rcg Min allowable value 1 1...

Страница 47: ...ressure Chilled water Entering System I Leaving System Running state Troubleshooting Commissioning Flow control Final flow rate T h Entering water temp Nominal value 12 7 Unloading state System I leav...

Страница 48: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: