D Series Modular Air-cooled Scroll Chillers
13
(7)
Under ultra-low temperature in winter, showdown at night will cause the evaporator and pipeline frozen
up, so it is highly recommended to add alcohol and propanol mixture in chilled water. Do not cut off the
power supply when the unit is turned off, otherwise the freeze protection does not work. Alternatively,
cut off the power supply and drain the water system thoroughly.
(8)
When the unit runs under the low load requirement, in order to avoid low load protection which would
affect the service life of the unit, make sure the water capacity is more than 1/6 of total rated flow rate
per hour of each module. If necessary, a water tank will be installed.
(9) Note: never use salt mixture to prevent the unit from being corroded.
Steam current Switch
Steam current Switch
Steam current Switch
Steam current Switch
Manual exhaust valve
Manual exhaust valve
Manual exhaust valve
How to drain the water system
(1)
Loosen screws around the panel and then take down it.
(2)
Remove anticlockwise the blind plug located at the bottom of the heat exchanger to let the chilled water
flow out, after that, tighten the blind plug and reinstall the panel. (Note: place the drainage equipment
beneath the drain pipe to prevent pollution caused by the drain water.)