Service Manual
●Indoor unit:
9.2 Troubleshooting for Main Malfunction
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Is the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Start
Insert the temperature
sensor tightly
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Replace it with a
temperature sensor with
the same model
Make the parts upright
Is there short circuit due to trip-
over of the parts
Is the temperature sensor normal
according to the resistance table?
Replace the mainboard with
the same model.
End
61
Содержание LIVV09HP230V1A Series
Страница 103: ...190 Service Manual 100 ...
Страница 109: ...214 Service Manual LIVV24HP230V1AO LIVV18HP230V1AO Note Take heat pump for example 106 ...
Страница 110: ...215 Service Manual 107 ...
Страница 111: ...216 Service Manual 108 ...
Страница 112: ...217 Service Manual 109 ...
Страница 113: ...218 Service Manual 110 ...
Страница 114: ...219 Service Manual 111 ...