67
Installation and Maintenance
Service Manual
6.Malfunction of communication E6
Main detection points:
● Check if the connection wire and the built-in wiring of indoor and outdoor unit are connected well and without damage;
● If the communication circuit of indoor mainboard is damaged? If the communication circuit of outdoor mainboard (AP1) is
damaged?
Malfunction diagnosis process:
Start
Cut off power supply. Check if
connection line of IDU and ODU
and the wire inside electric box
are correctly connected.
Correct connection?
Main board matches
with display board? Main board of
IDU matches with that of ODU?
Communication cord is damaged?
Replace IDU's
main board
Malfunction eliminated?
End
Connect the line
according to
wiring diagram.
Match correctly
according to product
specification
Replace
communication
cord
Replace ODU's
main board.
Malfunction eliminated?
Malfunction eliminated?
Malfunction eliminated?
yes
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
no