GREE Air-ccoled Closed Control Unit Service Manual
41
following places:
①
Water pipe;
②
Gas pipe;
③
Blowing pipe;
④
Other places that professional personnel consider unreliable.
7.2 Matching Form of Power Cord and Air Switch
Model
Power Supply
Air Switch
Capacity
(
A
)
Minimum Sectional
Area
(
mm
2
)
Earthed
Cable
Power
Cord
JKFD5DXXX(I)
220V
~
50Hz
40
10
10
JKFD5/Na-E(O)
220V
~
50Hz
-
1
1
JKFD7DXXX(I)
220V
~
50Hz
63
16
16
JKFD7XXX(I)
380V 3N
~
50Hz
32
4
4
JKFD7/Na-E (O)
220V
~
50Hz
-
1
1
JKFD13XXX(I)
380V 3N
~
50Hz
32
6
6
JKFD13/Na-M(O)
220V
~
50Hz
-
1.5
1.5
JKFD19XXX(I)
380V 3N
~
50Hz
40
10
10
JKFD19/Na-M (O)
220V
~
50Hz
-
1.5
1.5
JKFD25XXX(I)
380V 3N
~
50Hz
63
16
16
JKFD13//NaA-M
(O)
220V
~
50Hz
-
1.5
1.5
JKFD40XXX(I)
380V 3N
~
50Hz
100
25
25
JKFD19//NaA-M
(O)
220V
~
50Hz
-
1.5
1.5
JKFD40/Na-M(O)
380V 3N
~
50Hz
-
2.5
2.5
Note:
(1) Power cord of the unit must the cable with copper conductor and its working
temperature cannot exceed the designated value.
(2) If the power cord is longer than 15m, the cross sectional area shall be expanded
accordingly in case any accident caused by overloading.