MODULAR MINI CHILLER                                                         MAINTENANCE 

 

35

 

UNITS MAINTENANCE   

1 TROUBLE TABLE 

Name of Error 

Source of 

Error Signal 

Description 

high pressure 
of compressor 
1 (compressor 
2) 

high 

pressure 
switch of 

system 1 

(system 2) 

If the high pressure switch of compressor 1 

(compressor 2) disconnects, the corresponding 
compressor will stop. If both compressors stop, the two 
fans will stop later. 

The error LED of the display board lights and the 

corresponding alarm mark will be shown in “malfunction 
view”. The error must be removed manually before the unit 
resume normal running. 

low pressure of 

compressor 1 

(compressor 2) 

low 

pressure 
switch of 

system 1 

(system 2) 

If the low pressure switch of compressor 1 

(compressor 2) disconnects, the corresponding 
compressor will stop. If both compressors stop, the two 
fans will stop later. The error can be removed automatically 
for 5 times while it can not resume automatically for the 6

th

 

time. If it is detected for 3 times in one hour, it can not 
resume automatically. The corresponding marks will be 
shown in “error view”. It is required to remove the error 
manually. 

When the display board is off, the low pressure will not 

be detected. In automatic anti-freezing and defrosting 
mode, after startup of the water pump, the low pressure will 
be detected by pressing heating low pressure button.   
When the display board is on, if the low pressure is lower 
than heating low pressure protection value, the controller 
will send “low pressure protection” signal. The error can not 
be removed unless repaired by service man. When the 
compressor stops running, if the low pressure is lower than 
heating low pressure, the controller will send “low pressure 
protection” signal. The error can not be removed unless 
repaired by service man. 

discharge high 

temperature 

protection of 

compressor 1 

(compressor 2) 

discharge 

temperature 

sensor 

system 1 

(system 2) 

If the discharge high temperature protection 

(

130 start protection; the resume value is 85 ) of 

compressor 1 (compressor 2) is detected, the 
corresponding compressor will stop. If both compressors 
stop, the two fans will stop later. 

The error LED of the display board lights and the 

corresponding alarm symbol will be shown in “malfunction 
view”. The error must be removed manually before the unit 
resume normal running. 

overcurrent of 

compressor 

overcurrent 
protector of 

compressor 

If the overcurrent of compressor 1 (compressor 2) is 

detected, the corresponding compressor will stop. If both 
compressors stop, the two fans will stop later. 

The error LED of the display board lights and the 

corresponding alarm symbol will be shown in “malfunction 
view”. The error must be removed manually before the unit 
resume normal running. 

Содержание HLR35SM/NaA-M

Страница 1: ...Modular Mini Chiller Service Manual T1 R410A 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...

Страница 2: ...peration View 12 3 3 Display View 13 3 4 Wired Controller Operation Instructions 13 3 5 Controller Menu Structure 26 4 SKETCH MAP OF DIP SWITCH 27 UNITS INSTALLATION 29 1 UNITS INSTALL 29 1 1 Installa...

Страница 3: ...MODULAR MINI CHILLER PRODUCT 3 PRODUCT...

Страница 4: ...2 3 4 5 6 7 NO Description Options 1 Mini chiller 2 Product type R Heat pump 3 Nominal Cooling Capacity 35 35kW 45 45kW 4 Refrigeration Circuits Default One circuit S Twin circuit 5 Module 6 Refriger...

Страница 5: ...er Evaporator Water In Out Pipe Diameter inch 1 1 2 Heat Exchanger Aluminum fin copper tube Fin sleeve Heat exchanger Condenser Fan Motor Power Input kW 0 6 0 8 L s 2 2 Water Flow GPM 29 Delivery Lift...

Страница 6: ...A MRC A NRC A HLR35SM NaA M 380 415V 3Ph 50Hz 2 101 17 3 2 1 36 6 26 3 Notes LRA Locked rotor amps A MRC Maximum running current A NRC Nominal running current A 5 PIPING DIAGRAM Heating circuit Coolin...

Страница 7: ...GREE COMMERCIAL AIR CONDITIONERS MODULAR MINI CHILLER 7 CONTROL...

Страница 8: ...MODULAR MINI CHILLER CONTROL 8 UNITS CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Operation...

Страница 9: ...MODULAR MINI CHILLER CONTROL 9 1 2 Heating Operation...

Страница 10: ...of this module will stop When the anti freezing temperature is higher than the required value for resume this system will eliminate the anti freezing protection When the anti freezing temperature is b...

Страница 11: ...l remain the original state and the water pump will not stop Disorderly closedown the compressor stops and then the fan stops unless the fan is wrong After the corresponding compressor stops for a per...

Страница 12: ...N OFF button Control the start or stop of the unit Under stop state press the button for 3s to start up the unit Under running state press the button for 3s to stop the unit 5 RESTORE button Press thi...

Страница 13: ...timing mode The manual mode is given priority to the timing mode Manual mode 1 Manual start in the unit stop state press the on off button for 3 seconds and start the unit and at that time the operati...

Страница 14: ...en the unit is in the cooling heat recovery mode stop state if you select YES and press the Confirm you can go back to the home page and the unit is in the heating heat recovery operation state and if...

Страница 15: ...u Home Page Press the Exit button on the wired controller at any time for enough times you can go back the default home page menu as shown above 3 4 2 2 Main Menu When home page is present on the scre...

Страница 16: ...y on the screen is as follows Press the Confirm button to acknowledge a selected object press the Up or Down selection button to change a selected object and press the Exit button to cancel the model...

Страница 17: ...to quit the page and go back to the previous menu and save set values f Clock Setup Select Clock Setup and press the Confirm button to go to the page The following display is present on the screen Pr...

Страница 18: ...d or not The function is for selecting whether the unit will memorize its operation state if power supply is shut down 2 Module View When the Main Menu is present on the screen select Module View pres...

Страница 19: ...e Exit button to quit the page and go back to the previous menu Press the Up or Down selection button to select a needed function and press the Confirm to go to corresponding page X stands for one num...

Страница 20: ...ver Tin and H Aver Tin And press again the Reset button and the Exit button simultaneously for 3 seconds and C Water Tin and H Water Tin will be displayed again As such display can be converted betwee...

Страница 21: ...temperature display is dependent on unit model If the temperature sensor is not existent for a certain model None would be present on the display zone for corresponding temperature point c Error View...

Страница 22: ...are available below You can press the Down selection button for reading more failures If the first line is followed with a more failures are available above You can press the Up selection button for...

Страница 23: ...arameter Setup and press Confirm to go to the page as shown in the following drawing Press Exit to quit the page and go back to the previous menu Press Up or Down selection button to select a needed s...

Страница 24: ...ce press the Up and Down selection buttons to enter parameter value and press Confirm or Exit to go back to the Parameter Set menu other parameters can be modified in the same way After entered Defaul...

Страница 25: ...the following 1 Erasing Error Press Confirm to confirm it and go back to the previous page 2 Relieve Discharge Temp Sensor locking Press Confirm to go to Code Entry page and enter correct password to...

Страница 26: ...mode setting and start stop mode 2 Module view View the temperature state malfunction defrosting of the module 3 Parameter setup It can be divided into user parameter setup and system parameter setup...

Страница 27: ...ich are connected with one wired controller their toggle switches indicated the address should be different Toggle switches 1 2 3 and 4 are binary code with 1 for the lowest bit and 4 for the highest...

Страница 28: ...GREE COMMERCIAL AIR CONDITIONERS MODULAR MINI CHILLER 28 INSTALLATION...

Страница 29: ...nit allows for sufficient air circulation z There is no danger of fire due to leakage of flammable gas z All piping lengths and distances have been taken into consideration 1 2 Matters need Attention...

Страница 30: ...bolt4 M12 1750 1000 300 1000 foundation bolt base rubber isolator concrete base 1200 1000 1750X2 300 3800 water outlet lift method Cable through the hole lift by hook 2000 unit mm air outlet water in...

Страница 31: ...omatic release of air in the water circuit remains possible 2 3 Antifreeze by Weight 0 12 22 30 36 41 Freezing Point 0 32 5 23 10 14 15 5 20 4 30 22 Ambient Temperature 8 3 47 3 3 38 1 7 29 6 7 20 11...

Страница 32: ...ith Consumers COM1 COM2 COM2 3 3 Specification of Power Cord Air Switch Model Power Supply Capability of Air Switch A Minimum Sectional Area of Earth Wire mm 2 Minimum Sectional Area of Power Cord mm2...

Страница 33: ...ident due to over load 3 If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard 4 The appliance shall be in...

Страница 34: ...GREE COMMERCIAL AIR CONDITIONERS MODULAR MINI CHILLER 34 MAINTENANCE...

Страница 35: ...the low pressure will be detected by pressing heating low pressure button When the display board is on if the low pressure is lower than heating low pressure protection value the controller will send...

Страница 36: ...p during heating mode and cooling mode If there is signal of temperature sensor malfunction and it resume to normal automatically the error mark will be removed automatically But if it occurs 3 times...

Страница 37: ...p e n s a f te r r e p a ir o f u n it M is d e c la r in g a la r m o f c o n tr o lle r C o n ta c t w ith s u p p lie r I m p r o p e r d e s ig n o f w a te r w a y p ip e lin e a n d lo w f lo w...

Страница 38: ...ly s c a le s d u rin g c o o lin g F ilte r b lo c k s Im p ro p e r d e s ig n o f w a te rw a y p ip e lin e a n d lo w flo w v o lu m e u p o n s to p o f te rm in a l C o n ta c t w ith s u p p l...

Страница 39: ...heck if it happens frequently If necessary replace mainboard Misdeclaring alarm of controller Adjust discharge temp sensor Misuse discharge temp sensor easy to happen after repair of unit No No Yes Re...

Страница 40: ...o Yes Check if it happens frequently If necessary replace mainboard Misdeclaring alarm of controller Contact with supplier Replace inverse protector Inverse protector is broken Check power supply Phas...

Страница 41: ...AINTENANCE 41 3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 3 1 Integral Type 1 Remove the front case Loosen the tappong screws fixing the front case See Fig 1 Pull down and remove the front case...

Страница 42: ...e box cover Remove all pressure switches and temp sensor See Fig 3 3 Remove the shell and tube heat exchanger welding out the pipes connected to the shell and tube heat exchanger Remove the shell and...

Страница 43: ...MODULAR MINI CHILLER MAINTENANCE 43 4 EXPLODED VIEW AND PARTS LIST 4 1 Exploded View and Parts List Integral Type Model HLR35SM NaA M Exploded view...

Страница 44: ...mpressor and fittings 00202231 2 27 Electric heater compressor 76515404 2 28 Pressure Protect Switch 4602001515 1 29 Pressure Protect Switch 4602001512 1 30 Inhalation Tube Sub Assy 1 04672263 1 31 Ac...

Отзывы: