4.2 Operation Range
Mode
Range of Outdoor Temperature (
ć
)
Cooling
16~43
Heating
-15~28
4.3 Electrical Data
4.3.1 Split Type
Model
Rated
Power
Supply
Compressor
Fan Motor
Pump
Total
Outdoor
NO.
LRA each
(A)
MRC each
(A)
NO.
MRC
(A)
MRC
(A)
MRC
(A)
NRC
(A)
HLR8WZNa-M
380-415V
3Ph 50Hz
1
65
9.1
1
1.5
0.7
9.4
7.0
HLR10WZNa-M
1
66
11.6
2
2.0
0.7
13.0
8.5
HLR12.5WZNa-M
1
67
13.7
2
2.0
0.7
14.5
10.5
HLR15WZNa-M
1
67
13.7
2
2.0
0.7
14.5
10.5
4.3.2 Integral Type
Model
Rated
Power
Supply
Compressor
Fan Motor
Pump
Total
NO.
LRA each
(A)
MRC each
(A)
NO.
MRC
(A)
MRC
(A)
MRC
(A)
MRC
(A)
HLR22SNa-M
380-415V
3Ph 50Hz
2
73
11.6
2
5.0
1.5
19.5
14.5
HLR25SNa-M
2
66
13.5
2
5.0
1.5
23.5
18.5
HLR35SNa-M
2
101
16.4
2
7.5
3.0
28.5
24.5
HLR45SNa-M
2
110
22.5
2
7.5
3.0
45.0
31.0
Notes:
a. LRA: Locked rotor amps (A).
b. MRC: Maximum running current (A).
c. NRC: Nominal running current (A).
5 PIPING DIAGRAM