Installation and Maintenance

Service Manual

5. Remove Axial bush

Remove the axial bush of horizontal

louver to remove the axial bush.

a

Remove Axial bush

b

a

Take out the front case to separate the

front case with bottom assembly.

b

6. Remove front case

Remove the screw cover of front case,

unscrew the 8 screws of front case

with screwdriver.

hook

Axial sleeve

Axial bush

Steps

Procedure

front case

Содержание GWH18TC-S3DBA1E

Страница 1: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Change for Life Service Manual GWH18TC S3DBA1E GWH18TC S3DBA2E GWH18TC S3DBA3E GWH24TD S3DBA1E GWH24TD S3DBA2E GWH24TD S3DBA3E Refrigerant R410A Models...

Страница 2: ...Diagram 11 6 Function and Control 13 6 1 Remote Controller Introduction 13 6 2 Operation of Smart Control Smart Phone Tablet PC For Gree 19 6 3 Operation of Smart Control Smart Phone Tablet PC 32 6 4...

Страница 3: ...83 10 Exploded View and Parts List 85 10 1 Indoor Unit 85 10 2 Outdoor Unit 91 11 Removal Procedure 95 11 1 Removal Procedure of Indoor Unit 95 11 2 Removal Procedure of Outdoor Unit 110 Appendix 121...

Страница 4: ...ual 1 Summary Indoor Unit Outdoor Unit Part Technical Information GWH18TC S3DBA2E I GWH24TD S3DBA2E I GWH18TC S3DBA1E I GWH24TD S3DBA1E I GWH18TC S3DBA3E I GWH24TD S3DBA3E I GWH18TC S3DBA3E O GWH24TD...

Страница 5: ...24TD S3DBA3E I 3 GWH24TD S3DBA1E I Indoor Unit Product Code 1 CB411N03800 2 CB148N09001 3 CB412N03201 CB412N03202 1 CB411N04000 2 CB412N03101 3 CB148N08901 Fan Type Cross flow Cross flow Diameter Leng...

Страница 6: ...Coil Length LXDXW mm 823 5X38 1X660 945X38 1X748 Fan Motor Speed rpm 780 820 Output of Fan Motor W 60 90 Fan Motor RLA A 0 58 0 65 Fan Motor Capacitor F Air Flow Volume of Outdoor Unit m3 h 3200 4000...

Страница 7: ...High Pipe length 5m Conditions Indoor DB20 C WB15 C Outdoor DB7 C WB6 C Indoor air flow High Pipe length 5m 24K 24K 18K 18K 2 3 Capacity Variation Ratio According to Temperature Cooling Cooling Heati...

Страница 8: ...necting indoor and outdoor unit Inlet and outlet pipe temperature of heat exchanger Fan speed of indoor unit Fan speed of outdoor unit Compressor revolution rps Indoor Outdoor P MPa T1 C T2 C 20 15 7...

Страница 9: ...ical Information Service Manual 3 Outline Dimension Diagram 3 1 Indoor Unit Unit mm Model W H D 18K 1018 319 230 24K 1178 326 264 130 100 50 178 747 253 70 70 144 685 189 55 44 70 13 55 70 119 W H D 1...

Страница 10: ...7 Technical Information Service Manual 3 2 Outdoor Unit 340 963 700 396 890 560 364 Unit mm 427 1000 920 610 370 790 395 GWH24TD S3DBA3E O GWH18TC S3DBA3E O Unit mm...

Страница 11: ...ING 4 Way valve Discharge Suction Heat exchanger evaporator Heat exchanger condenser Valve Valve Liquid pipe side Gas pipe side Strainer Electron expansion valve Strainer Accumlator Compressor Capilla...

Страница 12: ...er for this model 6361000023204 83 2 1 83 2 1 0 0 6 1 8 6 1 8 3 3 803 211 725 1 75267 7 867 1 1 1 8 1 5 725 2 3 60 211 725 3 2 7 50 1 5 8 7 7 1 35 17 5 8 7 2 5 6 7 6 12 1 211 7 1 9 325 725 1 20 287 7...

Страница 13: ...SUHYHQW WKH ULVN RI HOHFWULF VKRFN 20B 11 5 9 9 9 9 8 5 725 2 9 9 3 16 21 7521 9 35 17 5 8 7 2 5 7 03 6 1625 867 7 03 6 1625 2875220 28778 7 03 6 1625 8 203 203 6 7 29 B 203 5 57 57 57 3 3 5 8 8 8 9...

Страница 14: ...on neutral wire 4 Neutral wire 5 Interface of DC motor 6 Interface of electrostatuc dedusting 7 Auto button 8 Up down swing interface 1 9 eft right swing interface 10 Up down swing interface 2 11 Inte...

Страница 15: ...essor wire 2 Terminal of low pressure protection 3 Terminal of compressor overload protection 4 Terminal of outdoor temperature sensor 5 Terminal of outdoor fan 6 Terminal of 4 way valve 7 Communicati...

Страница 16: ...k once and the air conditioner will give out a de sound which means the signal has been sent to the air conditioner WIFI 6 3 7 9 11 13 15 12 14 16 10 8 5 4 2 1 1 ON OFF button 2 MODE button 3 FAN butt...

Страница 17: ...cold air after starting up heating mode indoor unit will delay 1 5 minutes to blow air actual delay time is depend on indoor ambient temperature Set temperature range from remote controller 16 30 61...

Страница 18: ...nfirmation Note In the above presetting or enquiry procedure if continuously within 10s there is no button pressed the sleep curve setting within 10s there is no button pressed the sleep curve setting...

Страница 19: ...ate at notch 2 speed or quiet mode according to the comparison between indoor ambinet temperature and set temperature Under heating mode indoor fan operates at notch 3 speed or quiet mode according to...

Страница 20: ...ion 3 Child lock function 4 Temperature display switchover function Under heating mode press TEMP and CLOCK buttons simultaneously to start up or turn off 8 heating function When this function is star...

Страница 21: ...e receiving window on indoor unit The distance between signal sender and receiving window should be no more than 8m and there should be no obstacles between them Signal may be interfered easily in the...

Страница 22: ...tance control as shown below Please refer to Functions introduction for specific control methods Install the APP according to its guidance When successfully installed your smart phone homepage will sh...

Страница 23: ...n tap Next select the name of home Wifi router then enter the correct password and select a server Select Add device and enter the page of Add device Tap Manual configuration and enter the page Manual...

Страница 24: ...e short distance operation to control the air conditioner and then you can use the long distance control Functions introduction 1 User registration Purpose To realize long distance control Operation i...

Страница 25: ...rollable smart devices will be generated Default name for air conditioner is the last 8 numbers of the air condtioner mac address Step 1 Tap and hold a0b417ac to enter the page Edit device Tap Image t...

Страница 26: ...Save the setting of preset name 3 Set device image Please refer to step 1 in 2 1 3 Control functions 1 Common control functions General control on the operation of smart devices On Off temperature fa...

Страница 27: ...an speed Step 2 Advanced settings Tap to enter advanced settings You may select Air Dry Health Light Sleep or Energy saving 2 Advanced control functions Set scene Preset Link Infrared control only APP...

Страница 28: ...Select execution device select the air conditioner named babyroom Then select ON or OFF Continue to select the next execution device as instructed above Tap to set the interval Tap Save Tap the scene...

Страница 29: ...need to synchronize the time tap synchronize If such Hint interface doesn t show up please skip this operation step Tap Name to customize the preset name Preset device can t be selected and it will de...

Страница 30: ...d enter the page Add linkage Tap Device Param to enter the page Select device Take baby room as an example Tap babyroom Enter the page Select environment parameters Tap Temperature to enter the page S...

Страница 31: ...ting days Then tap Save Step 3 Select Execute command Tap Execute command and enter the page Select device Tap the name of device that you want to control Tap ON or OFF and then tap Save to complete t...

Страница 32: ...advanced functions Tap Sleep to enter the page Sleep You can select Traditional sleep Expert sleep or DIY sleep Tap DIY sleep and then tap the left and right arrows to set sleep time Tap up and down...

Страница 33: ...uick configuration information and unit s information including backup to cloud and backup list on the cloud Backup to cloud Enter the Menu on the left and tap Backup Tap Backup to cloud and then tap...

Страница 34: ...ates etc The server setting here must be the same as the server setting in Configuration mentioned before Otherwise remote control will be invalid 4 Feedback User can feedback suggestions to back stag...

Страница 35: ...hrough your smart phone The name of wifi hotspot is the last 8 numbers of the air conditioner mac address Password is 12345678 Step 2 Open APP and the screen will show the air conditioner that you jus...

Страница 36: ...ge Manual configuration Step 2 Tap Next in the First Step Step 3 Select the wireless network of air conditioner APP will show the password 12345678 default password of the network of air conditioner T...

Страница 37: ...hot spot signal of air conditioner is the last 8 bits of MAC address Eg Select a0b41737 and enter the defaulted password 12345678 to connect it Notice Finally press Configuration and APP will send th...

Страница 38: ...the device after connecting to the wireless router such as Tenda_XXX and turning on the APP Functions introduction 1 User registration Purpose To realize long distance control Operation instruction Fo...

Страница 39: ...Edit device Tap Image to select the source of image Select from Default images or Take photo or Choose from photos and save an image Step 2 Tap Name to change device name Save it and the new device n...

Страница 40: ...mer type select On Then select the repeating days Save the setting of preset name 3 Set device image Please refer to step 1 in 2 1 3 Control functions 1 Common control functions General control on the...

Страница 41: ...vanced settings You may select Air Dry Health Light Sleep or Energy saving 2 Advanced control functions Set scene Preset Link Infrared control only applicable to smart phones with infrared emitter Set...

Страница 42: ...on condition of the scene 3 Preset includes single device preset and multi device preset Single device preset This can preset a certain device to be On Off at a specific time On the homepage Device ta...

Страница 43: ...t device to select one or more devices Then return to the page Device 4 Link This function is applicable to some models Select a master device When the environment satisfies the parameters as set in t...

Страница 44: ...hen tap Save Step 2 Set time parameter for linkage Tap Time parameter to enter the page Set time Slide rightwards to turn on the setting time Tap Execution time then tap Start and Stop to set start ti...

Страница 45: ...cenes 4 Menu functions Menu functions Share Set History Feedback 1 Share To share quick configuration information and unit s information including local export and local import For local import you ju...

Страница 46: ...phones and are connecting to the same wireless router 2 Backup To keep backup of the quick configuration information and unit s information including backup to cloud and backup list on the cloud Backu...

Страница 47: ...t vibration message alerts server updates etc The server setting here must be the same as the server setting in Configuration mentioned before Otherwise remote control will be invalid 4 Help Please re...

Страница 48: ...the unit keeps previous operation status When Tamb Tpreset 2 C compressor outdoor fan and indoor fan operate at set fan speed low fan speed quiet fan speed or auto quiet fan speed Under this mode the...

Страница 49: ...t fan mode the default set temperature is 25 C When 22 C Tamb 25 C and the unit is turned on for the first time if it changes to auto mode from other mode the previous operation mode will be maintaine...

Страница 50: ...her Control 1 Clock Timer Timer ON If timer ON is set during operation of the unit the unit will continue to operate If timer ON is set at unit OFF upon ON time reaches the unit will start to operate...

Страница 51: ...ill operate at high speed When Tpreset 3 C Tamb Tpreset 2 C indoor fan will operate at med speed When Tpreset 2 C Tamb Tpreset 4 C indoor fan will operate at low fan speed When Tamb Tpreset 4 C indoor...

Страница 52: ...Upon energization the vertical louver will be reset to the start position firstly and then stop in the middle position When setting horizontal swing there are 7 status Position Position Position Posit...

Страница 53: ...ode in COOL operation and FAN operation 25 C will be displayed while in HEAT operation and FAN operation 20 C will be displayed For cooling only controller only 25 C will be displayed 16 Locked protec...

Страница 54: ...ing the temperature point in heating 6 2 Under this mode the temperature setting range is 16 30 7 Defrosting control heating mode 7 1 If it turns to defrosting time and it detected that the defrosting...

Страница 55: ...ompressor may decrease or increase 14 2 1 18K If 17A IAC current the system will stop operation because of overcurrent the complete unit can resume operation only after the compressor stops for 3min 1...

Страница 56: ...unit adequately grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire...

Страница 57: ...sure rise or compressor rupture resulting in injury 4 During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection p...

Страница 58: ...ng tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 T...

Страница 59: ...ast 15cm At least 15cm At least 250cm Space to the wall S p a c e t o t h e o b s t r u c t i o n r o o l f e h t o t e c a p S Space to the obstruction Drainage pipe Space to the wall Space to the ob...

Страница 60: ...or unit Make the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installat...

Страница 61: ...t 1 Select a location where the noise and outflow air emitted by the outdoor unit will not affect neighborhood 2 The location should be well ventilated and dry in which the outdoor unit wont be expose...

Страница 62: ...erring to the following sheet Place the open end wrench on the pipe joint and place the torque wrench on the union nut Tighten the union nut with torque wrench As show in Fig 6 4 Wrap the indoor pipe...

Страница 63: ...power cord and drain hose with the band As show in Fig 14 2 Reserve a certain length of drain hose and power cord for installation when binding them When binding to a certain degree separate the indo...

Страница 64: ...e wire clip connect the power connection wire and power cord to the wiring terminal according to the color fix them with screws As show in Fig 23 6 Neaten the Pipes 1 The pipes should be placed along...

Страница 65: ...to check whether the operation is normal or not If the ambient temperature is lower than 16 the air conditioner can t start cooling 2 Leakage Detection 1 With leakage detector Check if there is leakag...

Страница 66: ...it and then remove the cover of electric box 2 As shown in the fig below connect the plug of discharge resistance about 100ohm 20W if there is no discharge resistance you can use the plug of soldering...

Страница 67: ...of moto r 5 Controller is damaged 6 Malfunction protection of jumper cap C5 Operation of remote controller or control panel is available but the unit won t act 1 There s not jumper cap on the controll...

Страница 68: ...mpressor 15 Defrosting Heating indicator off for 0 5s and then blinks for 10s Defrosting will occur in heating mode Compressor will operate while indoor fan will stop operation Its the normal state 16...

Страница 69: ...if the voltage is higher than 150VAC turn on the unit after the supply voltage is increased to the normal range 2 If the AC input is normal measure the voltage of electrolytic capacitor C on control...

Страница 70: ...controller loosened or poorly contacted Insert the temperature sensor tightly yes Is malfunction eliminated Is there short circuit due to trip over of the parts Make the parts upright yes Is malfuncti...

Страница 71: ...s eliminated Reinsert the wiring terminal of indoor fan It s the malfunction of main board Replace a new main board that is of the same model It s the malfunction of main board Replace a new main boar...

Страница 72: ...er cap inserted correctly and tightly Replace the jumper cap with the same model End yes yes Assemble the jumper cap with the same model no Is malfunction eliminated no yes Insert the jumper cap tight...

Страница 73: ...board matches with display board Main board of IDU matches with that of ODU Communication cord is damaged Replace IDU s main board Malfunction eliminated End Connect the line according to wiring diag...

Страница 74: ...anual 5 Malfunction of detecting plate WIFI JF Start Is malfunction eliminated The end check if the connection wire are correctly connected Replace the detecting plate with the same model Replace the...

Страница 75: ...apacitor of power DC 180V 380V Test 5 Two ends of diode D15 D15 IPM modular 15V power supply DC 14 5V 15 6V Test 6 Two ends of electrolytic capacitor C715 C715 12V power supply DC 12V 13V Test 7 Two e...

Страница 76: ...ault with the voltage testing circuit on control panel AP1 Replace the control panel AP1 Measure the AC voltage between terminalL andN on wiring board XT power supply Voltage within 210VAC 250VAC Shut...

Страница 77: ...ompressor COMP is well connected If they are loosened If the connection sequence is correct Is voltage input in the normal range Test the voltage between L N of wiring board XT by DC voltage meter If...

Страница 78: ...the voltage between the two ends of capacitor C2 until the voltage is lower than 20V Replace the capacitor C2 Then energize and start the unit Replace the control panel AP1 Take corrective actions ac...

Страница 79: ...ss 1 Check if fan terminal OFAN is connected well 2 Test if resistance value of any two terminals is less than 1k with ohmic meter If the indoor and outdoor fan work well After the unit de energized f...

Страница 80: ...re COMP UVW is well connected and connection sequence is correct Replace control board AP1 Replace the compressor If malfunction is removed If the stop time of compressor is more than 3min N If the st...

Страница 81: ...an works normally If the stop time of compressor is more than 3min Synchronism after energize the unit and start it Connect wire well Synchronism occurred during operation Replace control board AP1 If...

Страница 82: ...ing diagram Replace EKV coil of electron expansion valve If the wiring terminal FA of electron expansion is well connected Remove malfunction The resistance value of first 4 l ead foot an d th e fifth...

Страница 83: ...inals Capacity is short circuit and replace it Y Re energize the unit and start it Cut the terminal of reactor test the resistance between two terminals of reactor with ohmic meter Replace the reactor...

Страница 84: ...Start Check communication circuit of outdoor unit Problem of communication circuit Check built in wiring of indoor and outdoor unit Connection correct Malfunction of circuit is detected with control...

Страница 85: ...ter Number jumping Outdoor unit malfunction Test voltage value with Test 13 position in diagram with voltage meter Number jumping Test voltage value with Test 11 position in diagram with voltage meter...

Страница 86: ...od for details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 9 4 Troubleshooting for Normal Malfunction 1 Air conditioner can t be started up 2...

Страница 87: ...n pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor can t operate Possible causes Discriminatin...

Страница 88: ...nual 10 Exploded View and Parts List 10 1 Indoor Unit 1 18K Unit 1 2 3 4 5 6 7 8 10 9 21 11 12 13 14 15 16 17 18 20 19 22 23 24 25 26 27 28 30 29 31 32 33 34 35 36 The component picture is only for re...

Страница 89: ...pport 24212139 24212139 1 15 Evaporator Assy 0100238603 0100238603 1 16 Wall Mounting Frame 01252123 01252123 1 17 Motor Press Plate 26112330 26112330 1 18 Fan Motor 1501212701 1501212701 1 19 Drainag...

Страница 90: ...Assy 0100238603 0100238603 1 16 Wall Mounting Frame 01252123 01252123 1 17 Motor Press Plate 26112330 26112330 1 18 Fan Motor 1501212701 1501212701 1 19 Drainage Hose 0523001406 0523001406 1 20 Connec...

Страница 91: ...88 Installation and Maintenance Service Manual 2 24K Unit 48 The component picture is only for reference please refer to the actual product...

Страница 92: ...1 1 20 Pipe Clamp 26112071 26112071 1 21 Fixed Clip Evaporator 26112324 26112324 1 22 Motor Fixed Clip 26112325 26112325 1 23 Drainage Hose 0523001403 0523001403 1 24 Rubber Plug Water Tray 76712012 7...

Страница 93: ...204201 1 19 Fan Motor 1501213401 1 20 Pipe Clamp 26112071 1 21 Fixed Clip Evaporator 26112324 1 22 Motor Fixed Clip 26112325 1 23 Drainage Hose 0523001403 1 24 Rubber Plug Water Tray 76712012 1 25 Ste...

Страница 94: ...aintenance Service Manual GWH18TC S3DBA3E O 1 2 3 4 5 6 8 9 10 11 12 13 14 15 16 17 18 19 20 22 23 24 25 26 27 28 29 30 7 21 The component picture is only for reference please refer to the actual prod...

Страница 95: ...sy 01705036 1 13 Condenser Assy 0110020007301 1 14 Rear Grill 01473043 1 15 Wiring Clamp 26115004 1 16 Temperature Sensor 3900030901 1 17 Electronic Expansion Valve assy 0713522201 1 18 4 Way Valve As...

Страница 96: ...93 Installation and Maintenance Service Manual GWH24TD S3DBA3E O The component picture is only for reference please refer to the actual product...

Страница 97: ...13 Clapboard Sub Assy 01235091 1 14 Condenser Assy 0110300010601 1 15 Electronic Expansion Valve assy 07133958 1 16 Temperature Sensor 3900030901 1 17 Temperature Sensor 39000072 1 18 Electrical Heate...

Страница 98: ...l power supplies and discharge the refrigerant completely before removal 18K 1 Before disassembling the unit Before disassembling the unit 2 Remove filter Open the panel Loosen the clasps on filter pu...

Страница 99: ...it b c Remove the axial bushing of small guide louver Remove the rotating shaft of small guide louver from the groove slightly bend the small guide louver to remove it d big guide louver axial bushin...

Страница 100: ...screw screw detecting plate Steps Procedure electric box cover2 Remove the screw fixing electric box cover2 and remove the electric box cover2 Remove the screw fixing detecting plate and remove the de...

Страница 101: ...Remove front case a Remove the screws fixing electric box cover 2 to remove the electric box cover 2 electric box cover 2 screw b Remove the screws fixing front panel loosen the clamps to remove the f...

Страница 102: ...ting rod to remove the swing connecting rod b remove the swing fan blade a Remove the indoor tube temp sensor b Remove the screws fixing earth wire to remove the earth wire swing fan blade clamp clamp...

Страница 103: ...wiring terminals and remove the electric box cover sub assy a Remove the screws fixing connection pipe clamp to remove the connection pipe clamp 7 Remove evaporator sub assy electric box cover sub as...

Страница 104: ...fixing evaporator sub assy slightly regulate the tube to remove the evaporator sub assy a motor to remove the motor b to remove the motor 8 Remove cross fan blade and motor auxiliary piping evaporator...

Страница 105: ...ws fixing motor clamp to remove the motor clamp d Remove the cross fan blade and motor e Remove the shafting bearing cushion rubber base f blade and motor and then remove the motor screw motor clamp b...

Страница 106: ...ore disassembly of the unit Before disassembling the unit 2 Remove filter Open the panel Loosen the clasps on filter push the filter inward and then pull it upward then the filter can be removed a b S...

Страница 107: ...er Remove the screws fixing display on the panel to remove the display Along the groove fixing front panel slide the rotor shaft outward to remove the front panel screw Unscrew a screw of electric box...

Страница 108: ...ntal louver to remove the axial bush a Remove Axial bush b a Take out the front case to separate the front case with bottom assembly b 6 Remove front case Remove the screw cover of front case unscrew...

Страница 109: ...ic box cover to separate the electric box cover 2 b c screw earth wire Remove every wiring terminals and remove the screws fixing electric box to remove the electric box sub assy electric box Remove T...

Страница 110: ...nection pipe clamp to remove the connection pipe clamp pipe clamp evaporator sub assy water tray Loosen the clasps connecting the water tray and chassis and then remove the water tray Remove the screw...

Страница 111: ...t the pipe line to the position as shown by the broken line d e Remove the 2 screws of step motor with screwdriver and remove the step motor a 9 Remove the cross flow louver and motor srews srews Lift...

Страница 112: ...tion and Maintenance Service Manual Remove screws fixing cross flow blade and motor b c Pull out the plug of ring of bearing Remove the motor sub assy d Cross blow blade Fan motor Ring of Bearing Step...

Страница 113: ...the big handle Remove the screw connecting the valve cover and right side plate and then remove the valve cover 2 Remove grille and outer case grille Remove the 4 screws connecting the grille and out...

Страница 114: ...side plate and left side plate and then remove the outer case Remove the screws connecting the right side plate with electric box assy valve support chassis and condenser side plate and then remove t...

Страница 115: ...the 2 screws connecting the motor support and chassis and then loosen the stopper to remove the motor support Remove the screws fixing the electric box sub assy loosen the wire bundle pull out the wi...

Страница 116: ...hen remove the isolation plate Unsolder the welding joints connecting the 4 way valve assy with capillary sub assy compressor and condenser remove the 4 way valve Note Before unsoldering the welding j...

Страница 117: ...ts of discharge pipe and suction pipe from foreign objects Remove the screws connecting the support condenser and condenser assy and then remove the support condenser Remove the 2 screws fixing the co...

Страница 118: ...le up ward to remove it Remove the screws connecting the top panel with the front panel and left right side plate and then remove the top panel 3 Remove front side panel front side panel Loosen the sc...

Страница 119: ...the panel Twist off the screws connecting the grille and panel and then remove the grille 5 Remove right side plate right side plate Twist off the screws connecting the right side plate and chassis v...

Страница 120: ...pliers pull out the wiring terminal pull it upwards to remove the electric box electric box fireproofing Twist off the screws on electric box fireproofing with screwdriver and then remove the electric...

Страница 121: ...e motor support Twist off the screws connecting isolation sheet and end plate of condenser and chassis and then remove the isolation sheet 11 Remove 4 way valve 10 Remove isolation sheet isolation she...

Страница 122: ...ng joint wrap the gas valve with wet cloth completely to avoid the damage to valve and release all refrigerant completely at first Unsolder the soldering joint between liquid valve and connection pipe...

Страница 123: ...left side plate left side plate Twist off the screws connecting the left side plate and chassis with screwdriver and then remove the left side plate Pull it upwards to separate the chassis and conden...

Страница 124: ...28 66 67 66 2 19 75 76 75 2 24 84 85 84 2 29 68 68 20 77 77 25 86 86 30 1 Standard length of connection pipe 5m 7 5m 8m 2 Min length of connection pipe is 3m 3 Max length of connection pipe and max hi...

Страница 125: ...llowing steps A Cut the pip Confirm the pipe length according to the distance of indoor unit and outdoor unit Cut the required pipe with pipe cutter B Remove the burrs Remove the burrs with shaper and...

Страница 126: ...66 88 33 10 63 72 2 439 111 0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 06...

Страница 127: ...983 5 84 61 34 13 59 73 3 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2...

Страница 128: ...62 11 32 101 3 22 15 362 9 24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10...

Страница 129: ...218 Fax 86 756 8669426 Email gree gree com cn Http www gree com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add Unit 2612 26 F Miramar Tower 132 Nathan Road TST Kowloon HK Tel 852 31658898 Fax 85...

Отзывы: