Installation and Maintenance

Service Manual

Do not bend the drain hose too excessively in order to prevent 
blocking.

Note:

Indoor

Outdoor

Wall pipe

Sealing gum

Upper hook

Lower hook of

wall-mounting frame

Fig.16

Fig.17

NO.

Items to be checked

Possible malfunction

1

Has the unit been 
installed firmly?

The unit may drop, shake or 
emit noise.

2

Have you done the 
refrigerant leakage test?

It may cause insufficient cooling 
(heating) capacity.

3

Is heat insulation of 
pipeline sufficient?

It may cause condensation and 
water dripping.

4 Is water drained well?

It may cause condensation and 
water dripping.

5

Is the voltage of power 
supply according to the 
voltage marked on the 
nameplate?

It may cause malfunction or 
damage the parts.

6

Is electric wiring and 
pipeline installed 
correctly?

It may cause malfunction or 
damage the parts.

7

Is the unit grounded 
securely?

It may cause electric leakage.

8

Does the power cord 
follow the specification?

It may cause malfunction or 
damage the parts.

9

Is there any obstruction 
in air inlet and air outlet?

It may cause insufficient cooling 
(heating).

10

The dust and 
sundries caused 
during installation are 
removed?

It may cause malfunction or 
damaging the parts.

11

The gas valve and liquid 
valve of connection pipe 
are open completely?

It may cause insufficient cooling 
(heating) capacity.

1. Check after Installation

Check according to the following requirement after finishing 
installation.

8.6 Check after Installation and Test 

Operation

2. Test Operation

(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote 
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and 
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16

, the air 

conditioner can’t start cooling.

Содержание GWH18KG-K3DNA6G/I

Страница 1: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Change for Life Service Manual Model GWH18KG K3DNA6G I Refrigerant R410A...

Страница 2: ...s 11 Part Installation and Maintenance 14 7 Notes for Installation and Maintenance 14 8 Installation 16 8 1 Installation Dimension Diagram 16 8 2 Installation Parts checking 18 8 3 Selection of Instal...

Страница 3: ...of Contents Appendix 39 Appendix 1 Reference Sheet of Celsius and Fahrenheit 39 Appendix 2 Configuration of Connection Pipe 39 Appendix 3 Pipe Expanding Method 40 Appendix 4 List of Resistance for Te...

Страница 4: ...1 Technical Information Service Manual 1 Summary Part Technical Information Indoor Unit GWH18KG K3DNA6G I Remote Controller YAA1FB F C H O U R ONOFF...

Страница 5: ...1200 1050 900 Fan Motor Power Output W 20 Fan Motor Running Current A 0 31 Fan Motor Capacitor F 1 5 Evaporator Material Aluminum Fin copper Tube Evaporator Pipe Diameter mm 7 Evaporator Number of Row...

Страница 6: ...am 3 1 Indoor Unit 70 70 70 90 45 45 40 55 55 55 55 40 41 3 41 3 71 161 54 54 5 120 5 548 5 H 103 149 542 176 130 685 193 70 70 70 90 45 45 40 55 55 55 55 40 41 3 41 3 71 161 54 54 5 120 5 548 5 W D H...

Страница 7: ...ecification Liquid pipe 1 4 6mm Gas pipe 1 2 12mm Indoor unit Outdoor unit COOLING HEATING 4 Way valve Discharge Suction Heat exchanger evaporator Heat exchanger condenser Valve Valve Liquid pipe side...

Страница 8: ...is used to determine fan speed and the swing angle of horizontal lover for this model SENSOR SENSOR AC L BK PE ROOM TUBE M2 SWING UD1 ROOM TEMP RT2 AP2 BN PG YEGN M1 BU FAN MOTOR OUTDOOR UNIT 2 3 XT N...

Страница 9: ...rface of neutral wire 4 Capacitor of fan motor 5 Fuse 6 Interface of PG motor 7 Interface of health function live wire 8 Auto button 9 Up down swing 10 Feedback interface of PG motor 11 Interface of I...

Страница 10: ...ton LIGHT button 16 X FAN button SLEEP button TEMP button button button F C H O U R ONOFF 2 3 4 5 6 7 8 9 10 11 12 13 14 16 15 Send signal Turbo mode 8 heating function Set temperature Set time TIMER...

Страница 11: ...8 Technical Information Service Manual no display...

Страница 12: ...9 Technical Information Service Manual...

Страница 13: ...10 Technical Information Service Manual battery Cover of battery box remove reinstall...

Страница 14: ...ssor is reached the compressor and the outdoor fan motor stop operation The upper down horizontal louver will rotate to the horizontal position L The indoor fan will be stopped after operating for 60s...

Страница 15: ...he temperature has increased by 3 C the unit will keep this temperature When the unit has operated for 7 hours the temperature will decrease by 1 C and then the unit will operate at this temperature a...

Страница 16: ...or is detected short circuit for 5s successively The detected temperature by the temperature sensor is too high and the complete unit will stop operation meanwhile the protection and malfunction of te...

Страница 17: ...unit adequately grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire a...

Страница 18: ...ng tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 T...

Страница 19: ...Manual 8 Installation 8 1 Installation Dimension Diagram Drainage pipe At least 250cm At least 15cm At least 300cm Space to the Space to the ceiling Space to the obstruction At least 15cm At least 15...

Страница 20: ...or unit Make the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installat...

Страница 21: ...ent 3 The place near coast area 4 The place with oil or fumes in the air 5 The place with sulfureted gas 6 Other places with special circumstances 7 The appliance shall nost be installed in the laundr...

Страница 22: ...ightly downward to the outdoor side with the gradient of 5 10 As show in Fig 2 Note Insulating pipe Torque wrench Open end wrench Indoor pipe Pipe Union nut Union nut Pipe joint Pipe Hex nut diameter...

Страница 23: ...hen binding to a certain degree separate the indoor power and then separate the drain hose As show in Fig 15 3 Bind them evenly 4 The liquid pipe and gas pipe should be bound separately at the end 2 M...

Страница 24: ...ause electric leakage 8 Does the power cord follow the specification It may cause malfunction or damage the parts 9 Is there any obstruction in air inlet and air outlet It may cause insufficient cooli...

Страница 25: ...ture sensor is open short circuited F1 Indoor evaporator temperature sensor is open short circuited F2 Module temperature sensor is open short circuited P7 Outdoor ambient temperature sensor is open s...

Страница 26: ...then peformedischarging NOTE A large capacity electrolytic capacitor is used in the outdoor unit controller inverter Therefore if the power supply is turned off charge charging voltage DC280V to 380V...

Страница 27: ...oken Malfunction diagnosis process Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes...

Страница 28: ...he connection of PG motor control terminal is firm Turn on the unit again measure whether the output voltage on control terminal for PG motor is more than 50V within 1 min after the louvers are opened...

Страница 29: ...the mainboard is defined abnormal Malfunction diagnosis process Start Is there jumper cap on the mainboard Is the jumper cap inserted correctly and tightly Replace the jumper cap with the same model...

Страница 30: ...harges slowly The zero cross detectioncircuit of the mainboard is defined abnormal Malfunction diagnosis process Turn power off for 1minute the turn back on The unit returns to normal Conclusion U8 is...

Страница 31: ...wiring diagram Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Main board matches with display board Main board of IDU matches with that of ODU...

Страница 32: ...od for details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 9 3 Troubleshooting for Normal Malfunction 1 Air Conditioner Can t be Started Up 2...

Страница 33: ...re parts touching together inside the outdoor unit There s abnormal sound fro outdoor unit Remove foreign objects Adjust all parts position of outdoor unit tighten screws and stick damping plaster bet...

Страница 34: ...d View and Parts List Indoor Unit FAN AUTO OPER HEALTH AIR FILTER TURBO ON OFF X FAN HOUR HUMIDITY ON OFF MODE FAN X FAN TURBO TEMP TIMER SLEEP LIGHT 13 39 38 37 12 11 10 9 8 7 6 5 4 22 21 20 19 18 17...

Страница 35: ...16 Wall Mounting Frame 01252484 1 17 Cross Flow Fan 10352036 1 18 Motor Press Plate 26112231 1 19 Fan Motor 15012146 1 20 Connecting pipe clamp 2611216401 1 21 Drainage hose 0523001407 1 22 SteppingMo...

Страница 36: ...g air filters If ON OFF button is kept pushing for 5 seconds a forced cooling operation will be carried out for ap prox 15 minutes Pull protrusions on left and right sides of panel with fingers and op...

Страница 37: ...r hand Draw out the axial bush Bend the horizontal louver slightly and then remove it a Left and right filters are interchangeable To re install insert air filter along the guide Hook a finger onto th...

Страница 38: ...upper part there are 2 hooks in the left and the right Remove the 5 screws in the right and the left which fix the main body with the front grille a Disengage the hooks by pressing knobs with a screwd...

Страница 39: ...nect the connection wires Twist off the earthing screw fixing the evaporator Pull out the all the wiring terminals b Pay attention to the direction of the retainer of the thermistor so that the retain...

Страница 40: ...rocedure Points 7 Remove piping fixture Remove Pipe Clamp a Loosen the screws in the right and the left which fix the Evaporator Assy Remove Evaporator Assy b Auxiliary piping Piping fixture Adjust th...

Страница 41: ...plate of motor 9 Remove shaft cushion rubber base Remove screws of motor press plate and then remove the motor press plate Pressure plate of motor Shaft cushion rubber base Remove motor blade and shaf...

Страница 42: ...32 0 55 56 55 4 13 79 80 78 8 26 34 35 33 8 1 57 58 57 2 14 81 80 6 27 36 35 6 2 59 60 59 15 82 83 82 4 28 37 38 37 4 3 61 62 60 8 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65...

Страница 43: ...llowing steps A Cut the pip Confirm the pipe length according to the distance of indoor unit and outdoor unit Cut the required pipe with pipe cutter B Remove the burrs Remove the burrs with shaper and...

Страница 44: ...88 33 10 63 72 2 439 111 0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 1...

Страница 45: ...983 5 84 61 34 13 59 73 3 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 6...

Страница 46: ...62 11 32 101 3 22 15 362 9 24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 2...

Страница 47: ...Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 Email gree gree com cn Http www gree com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add Unit 2612 26 F Miramar Tower 132 Natha...

Отзывы: