52
Product Introduction
Basic Functions - 30K & 36K 230 volt
Designation of Sensors
Faults
Indoor Ambient Temperature
The sensor is detected to be open-circuited or short-cir-
cuited for successive 30 seconds
Indoor Tube Temperature
The sensor is detected to be open-circuited or short-cir-
cuited for successive 30 seconds
Outdoor Ambient Temperature
The sensor is detected to be open-circuited or short-cir-
cuited for successive 30 seconds
Outdoor Tube Temperature
The sensor is detected to be open-circuited or short-cir-
cuited for successive 30 seconds, and no detection is
preformed within 10 minutes after defrost begins.
Exhaust
After the compressor has operated for 3 minutes, the
sensor is detected to be open-circuited or short circuited
for successive 30 seconds.
Overload
After the compressor has operated for 3 minutes, the
sensor is detected to be open-circuited or short circuited
for successive 30 seconds.