Specialist’s Manual

Repair to intrinsically safe components

Do  not  apply  any  permanent  inductive  or  capaci-

tance loads to the circuit without ensuring that this 

will not exceed the permissible voltage and current 

permitted for the equipment in use.

Intrinsically safe components are the only types that 

can be worked on while live in the presence of a fl- 

ammable atmosphere. The test apparatus shall be 

at the correct rating.

Replace components only with parts specified by the 

manufacturer. Other parts may result in the ignition 

of refrigerant in the atmosphere from a leak.

● 

Cabling

Check that cabling will not be subject to wear, cor- 

rosion, excessive pressure, vibration, sharp edges 

or  any  other  adverse  environmental  effects.  The 

check  shall  also  take  into  account  the  effects  of 

aging or continual vibration from sources such as 

compressors or fans.

● 

Detection of flammable refrigerants

Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detec- 

tor using a naked flame) shall not be used.

● 

Leak detection methods

Leak detection fluids are suitable for use with most 

refrigerants but the use of detergents containing ch- 

lorine shall be avoided as the chlorine may react 

with the refrigerant and corrode the copper pipe-work.

● 

Decommissioning

Before carrying out this procedure, it is essential that 

the technician is completely familiar with the equip- 

ment and all its detail. It is recommended good pr- 

actice  that  all  refrigerants  are  recovered  safely. 

Prior to the task being carried out, an oil and refri- 

gerant sample shall be taken in case analysis is re- 

quired prior to re-use of reclaimed refrigerant. It is 

essential  that  electrical  power  is  available  before 

the task is commenced.

a) Become familiar with the equipment and its opera- 

tion.

b) Isolate system electrically.

c) Before attempting the procedure, ensure that:

– mechanical handling equipment is available, if

required, for handling refrigerant cylinders;

– all  personal  protective  equipment  is  available

and being used correctly;

– the recovery process is supervised at all times

by a competent person;

● 

d) Pump down refrigerant system, if possible.

e) If a vacuum is not possible, make a manifold so

that refrigerant can be removed from various parts 

of the system.

f) Make sure that cylinder is situated on the scales

before recovery takes place.

g) Start the recovery machine and operate in accor- 

dance with manufacturer's instructions.

h) Do not overfill cylinders. (No more than 80% vo- 

lume liquid charge).

i) Do not exceed the maximum working pressure of

the cylinder, even temporarily.

j) When the cylinders have been filled correctly and

the process completed, make sure that the cylinders 

and the equipment are removed from site promptly 

and all isolation valves on the equipment are closed 

off.

k) Recovered refrigerant shall not be charged into

another refrigeration system unless it has been clean- 

ed and checked.

Labelling

● 

Recovery

When  removing  refrigerant  from  a  system,  either 

for servicing or decommissioning, it is recommend-

ed good practice that all refrigerants are removed 

safely.

When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovery cylinders 

are employed. Ensure that the correct number of cy- 

linders for holding the total system charge are av- 

ailable. All cylinders to be used are designated for 

the recovered refrigerant and labelled for that refri- 

gerant (i.e. special cylinders for the recovery of refri- 

gerant). Cylinders shall be complete with pressure-re- 

lief valve and associated shut-off valves in good work- 

ing order. Empty recovery cylinders are evacuated 

and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working 

order  with  a  set  of  instructions  concerning  the 

equipment that is at hand and shall be suitable for 

the recovery of all appropriate refrigerants includ-

ing, when applicable, flammable refrigerants. In ad- 

● 

– recovery  equipment  and  cylinders  conform  to

the appropriate standards.

23

Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The 

label shall be dated and signed. For appliances con-

taining flammable refrigerants, ensure that there are 

labels on the equipment stating the equipment con-

tains flammable refrigerant.

Содержание GWH07AGA-K6DNA1A/I

Страница 1: ...on and introduction of remote controller 20 Configuration of connection pipe Specialist s Manual 22 NOTE Actual product may be different from graphics please refer to actual products Thank you for cho...

Страница 2: ...9AGB K6DNA1B I GWH09AGC K6DNA1F I GWH12AGB K6DNA1A I GWH12AGB K6DNA4A I GWH12AGC K6DNA1A I GWH12AGC K6DNA1F I GWH18AGD K6DNA1A I GWH18AGD K6DNA1D I GWH18AGD K6DNA1E I GWH18AGD K6DNA4A I GWH24AGD K6DNA...

Страница 3: ...reasons This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information u...

Страница 4: ...aware that refrigerants may not contain an odour Read specialist s manual All the work men who are engaging in the refrig eration system should bear the valid certification awarded by the authoritati...

Страница 5: ...erant If you should cut or weld the refrigerant system pipes in the process of maintaining please foll ow the steps as below c Vacuuming d e Cutting or welding Clean it with N2 gas f Carry back to the...

Страница 6: ...ir conditioner Unstable power supply or incorrect wiring may result in electric shock fire haza rd or malfunction Please install proper power supply cables before using the air conditioner The groundi...

Страница 7: ...must be po sitioned so that the plug is accessible For the air conditioner with plug the plug should be re achable after finishing in stallation For the air conditioner with out plug a circuit breaker...

Страница 8: ...by the manufacturer its ser vice agent or similarly qua lified persons in order to avoid a hazard Do not connect air condi tioner to multi purpose soc ket Otherwise it may cau se fire hazard Do discon...

Страница 9: ...It may cause mal function Do not step on top panel of outdoor unit or put heavy objects It may cause dam age or personal injury When below phenomenon occurs please turn off air conditioner and discon...

Страница 10: ...ystem pre ssure rise or compressor rupture resulting in injury Measuring tape spanner Inner hexagon When installing or moving this unit do not charge the refrigerant which is not comply with that on t...

Страница 11: ...e requirement of air conditioner Unstable power supply or incorrect wiring or malfunction Pl ease install proper power supply cables before using the air conditioner grounding wire of power socket 5 B...

Страница 12: ...es when opening the hole bellmouth Pretighten the union nut with hand Please refer to the actual circumstances for the number of screws and the position of screws rear right 1 7 The pipe can be led ou...

Страница 13: ...ross hole at the back of indoor unit and then pull it out from the front side panel screw wiring cover outlet pipe drain hose All wires of indoor unit and outdoor unit should be If the length of power...

Страница 14: ...on pipe drain hose with the band drain hose band indoor power cord Put the bound pipes in the wall pipe and then Bind up the connection pipe power cord and NOTICE make them pass through the wall hole...

Страница 15: ...on 1 2 3 Clean and maintenance 2 WARNING WARNING Please contact qualified professionals for service Error Code Error code F2 E8 Troubleshooting C5 F0 F1 U8 H6 H3 E1 E5 E6 Notice for recovery 1 Clean s...

Страница 16: ...ck the batteries If the power of batter s e i o l is too w please rep lace them Under heating mode indoor temperature is reached to set temp erature Power failure Is plug loose In order to prevent blo...

Страница 17: ...turn off the air conditioner When the air conditioner is turned on it will operate under auto mode Display Temp indicator Power indicator This is the general introduction and the color of indicator i...

Страница 18: ...t Clock Operation mode Set time TIMER ON TIMER OFF Turbo mode Send signal Auto mode Cool mode Left right swing Up down swing Child lock Dry mode Fan mode Heat mode Temp I feel Set fan speed display ty...

Страница 19: ...multifunction For the functions which the model doesn t have if press the corresponding button on the remote controller the unit will keep the original running status After putting through the power...

Страница 20: ...ngle When selecting air condition er is blowing fan at xed position Horizontal louver will stop at the xed position Press or button once increase or decr ease set temperature 1 F Holding or button 2s...

Страница 21: ...display the corresponding temperature of last setting sleep curve and blink The first entering will display according to the initial curve setting value of original factory 2 Adjust and button could...

Страница 22: ...usted Under 8 heating function set temperature can t be adjusted Press TURBO button and the remote controller won t send signal Sleep function and 8 heating function can t operate at the same time If...

Страница 23: ...f the auto clean function When the auto clean func tion is turned on indoor unit displays CL During the auto clean process of evaporator the unit will perform fast cooling or fast heating There may be...

Страница 24: ...function or damage the parts Is there any obstruction in the air inlet and outlet Is heat insulation of pipe line sufficient It may cause malfunction or damage the parts The gas valve and liquid valve...

Страница 25: ...m and 8m the min length of con nection pipe is 3m Max length of connection pipe is shown as below 4 1 2 The calculation method of additional refrigerant oil and refrigerant charging amount after prolo...

Страница 26: ...fferent according to the diameter please refer to the sheet below DB WB C any blemish expand the port again according to the steps above Outdoor side DB WB C Maximum GWH12AGC K6DNA1F I LC GWH09AGC K6D...

Страница 27: ...al ed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted on the refrigera tion equipment or any associated parts appropriate Ventilated area Ensure that the area is...

Страница 28: ...and being used correctly the recovery process is supervised at all times by a competent person d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrige...

Страница 29: ...refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not i...

Страница 30: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Tel 86 756 8522218 Fax 86 756 8669426 E mail global cn gree com Web www gree com Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 600005062912...

Отзывы: