Troubleshooting
Malfunction diagnosis flowchart:
Troubleshooting for low pressure protection of compressor (E3)
Start
Check whether the
main board and display board is
connected tightly?
Check whether the
LPP terminal on main board is connected well
with the low pressure switch on the
complete unit
Check whether the wire
of low presure switch is loosened? whether
the low pressure switch is damaged
or poor connected?
Refrigerant is insufficient
Check whether the LPP input is
high level?
Connect them
correctly
Please confirm that
they are connected
well
Make sure that the
wires are connected
well and the switch
is normal
Recharge the
refrigerant according
to requirement
De-energize the
unit and then restart
the unit
Replace the control
board
Eliminate the
malfunction
Eliminate the
malfunction
Eliminate the
malfunction
Eliminate the
malfunction
Eliminate the
malfunction
End
no
no
no
no
no
no
no
no
no
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
Содержание GWC36LB-D1NNA2A/I
Страница 1: ...5 75 33 1 6 1 2 8 6HUYLFH 0DQXDO 02 11 11 5HIULJHUDQW 5...
Страница 11: ...8 65 60 40 65 60 40 3 Construction Views 3 1 Indoor Unit Constrction views 1350 326 253 253 746 351...
Страница 12: ...9 840 1018 412 3 2 Outdoor Unit Constrction views 572 950 378...
Страница 35: ...32 8 Exploded Views and Parts List 8 1 Indoor Unit Exploded Views and Parts list...
Страница 38: ...35 Exploded Views and Parts list GWC36LB D1NNA2A O 8 2 Outdoor Unit...
Страница 40: ...37 Exploded Views and Parts list GWH36LB D1NNA2A O...
Страница 49: ...46 Troubleshooting Troubleshooting for communication malfunction E6 Malfunction diagnosis flowchart...
Страница 74: ...5 75 33 1 6 1 2 8 GG LQML ZHVW 5G 4LDQVKDQ KXKDL XDQJGRQJ KLQD 3RVW FRGH 7HO IWHU VDOH 6HUYLFH HSW...