fire extinguishing equipment shall be available to 

hand. Have a dry powder or CO

2

 fire extinguisher 

adjacent to the charging area.

The following checks shall be applied to instal- 

lations using flammable refrigerants:

– the charge size is in accordance with the room size

within which the refrigerant containing parts are in- 

stalled;

– the ventilation machinery and outlets are operat-

ing adequately and are not obstructed;

– if an indirect refrigerating circuit is being used, the 

secondary circuit shall be checked for the presence 

of refrigerant;

– marking to the equipment continues to be visible

and legible. Markings and signs that are illegible shall 

be corrected;

– refrigeration pipe or components are installed in a 

position where they are unlikely to be exposed to any 

substance which may corrode refrigerant contain-

ing components, unless the components are const-

ructed of materials which are inherently resistant to 

being corroded or are suitably protected against be- 

ing so corroded.

Repair and maintenance to electrical compo-

nents shall include initial safety checks and com- 

ponent inspection procedures. If a fault exists 

that could compromise safety, then no electrical 

supply shall be connected to the circuit until it 

is satisfactorily dealt with. If the fault cannot 

be corrected immediately but it is necessary 

to continue operation, an adequate temporary 

solution shall be used. This shall be reported 

to the owner of the equipment so all parties are 

advised.

● 

Initial safety checks shall include:

– that capacitors are discharged: this shall be done

in a safe manner to avoid possibility of sparking;

– that no live electrical components and wiring are

exposed while charging, recovering or purging the 

system;

– that there is continuity of earth bonding.

● 

Checking for presence of refrigerant

The area shall be checked with an appropriate refri- 

gerant detector prior to and during work, to ensure 

the technician is aware of potentially toxic or flamm- 

able atmospheres. Ensure that the leak detection 

equipment being used is suitable for use with all app- 

licable refrigerants, i.e. non-sparking, adequately seal- 

ed or intrinsically safe.

● 

Presence of fire extinguisher

If any hot work is to be conducted on the refrigera-

tion equipment or any associated parts, appropriate

● 

● 

Ventilated area

Ensure that the area is in the open or that it is ad- 

equately ventilated before breaking into the system 

or conducting any hot work. A degree of ventilation 

shall continue during the period that the work is carri- 

ed out. The ventilation should safely disperse any re- 

leased refrigerant and preferably expel it externally 

into the atmosphere.

● 

Checks to the refrigeration equipment

Where electrical components are being changed, 

they shall be fit for the purpose and to the correct 

specification. At all times the manufacturer's main- 

tenance and service guidelines shall be followed. If 

in doubt, consult the manufacturer's technical depart- 

ment for assistance.

● 

Checks to electrical devices

– that capacitors are discharged: this shall be done

in a safe manner to avoid possibility of sparking; 

– that no live electrical components and wiring are

exposed while charging, recovering or  purging the 

system.

● 

Repairs to sealed components

During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment 

being worked upon prior to any removal of sealed 

covers, etc. If it is absolutely necessary to have an 

electrical supply to equipment during servicing, then 

a permanently operating form of leak detection shall 

be located at the most critical point to warn of a 

potentially hazardous situation.

Particular attention shall be paid to the following to 

ensure that by working on electrical components, the 

casing is not altered in such a way that the level of 

protection is affected. This shall include damage to 

cables, excessive number of connections, terminals 

not made to original specification, damage to seals, 

incorrect fitting of glands, etc.

– Ensure that the apparatus is mounted securely.

– Ensure that seals or sealing materials have not de- 

graded to the point that they no longer serve the pur- 

pose of preventing the ingress of flammable atmos- 

pheres. Replacement parts shall be in accordance 

with the manufacturer’s specifications.

NOTE:The use of silicon sealant can inhibit the 

effectiveness of some types of leak detection equi- 

pment. Intrinsically safe components do not have to 

be isolated prior to working on them.

● 

2

4

Содержание GWC09ACC-K6DNA1C/I

Страница 1: ...t s Manual 21 Configuration of connection pipe 05 Installation notice Installation of indoor unit 07 Thank you for choosing our product Please read this Owner s Manual carefully before operation and retain it for future reference If you have lost the Owner s Manual please contact the local agent or visit www gree com or send an email to global cn gree com for the electronic version NOTE Actual pro...

Страница 2: ...09ACC K6DNA4A I GWH09ACC K6DNA5A I GWC12ACC K6DNA1D I GWH12ACC K6DNA1D I GWH12ACC K6DNA1F I GWH12ACC K6DNA1X I GWH12ACC K6DNA1Z I GWH12ACC K6DNA2D I GWH12ACC K6DNA3D I GWH12ACC K6DNA4D I GWH12ACC K6DNA5D I GWH12ACC K6DNA5F I GWC18ACD K6DNA1D I GWH18ACD K6DNA1D I GWH18ACD K6DNA1I I GWH18ACD K6DNA2D I GWH18ACD K6DNA3D I GWH18ACD K6DNA4D I GWH18ACD K6DNA5D I GWH18ACD K6DNA5I I GWH18ACD K6DNA1Z I GWH1...

Страница 3: ...g reasons This symbol indicates the possibility of death or serious injury This symbol indicates the possibility of injury or damage to property Indicates important but not hazard related information used to indicate risk of property damage If it needs to install move or maintain the air conditioner please contact dealer or local service center to conduct it at first Air conditioner must be instal...

Страница 4: ...ears the qualification for using the flamm operating electric heater Do not pierce or burn Appliance shall be installed operated and stored in a room with a floor area larger than Xm 2 including children with reduced physical sensory or d n a e c n e i r e p x e f o k c a l r o s e i t i l i b a p a c l a t n e m knowledge unless they have been given superv ision or instruction concerning use of t...

Страница 5: ...gerant If you should cut or weld the refrigerant system pipes in the process of maintaining please foll ow the steps as below c Vacuuming d e Cutting or welding Clean it with N2 gas f Carry back to the service spot for welding Filling the refrigerant The refrigerant should be recycled into the sp ecialized storage tank Make sure that there isn t any naked flame ne ar the outlet of the vacuum pump ...

Страница 6: ...air conditioner Unstable power supply or incorrect wiring may result in electric shock fire haza rd or malfunction Please install proper power supply cables before using the air conditioner The grounding resistance should comply with nation al electric safety regula tions Air Conditioner should be properly grounded Inco rrect grounding may cause electric shock Do not put through the power before f...

Страница 7: ... must be po sitioned so that the plug is accessible For the air conditioner with plug the plug should be re achable after finishing in stallation For the air conditioner with out plug a circuit breaker must be installed in the line The yellow green wire in air conditioner is ground ing wire which can t be us ed for other purposes The air conditioner is the first class electric applian ce It must b...

Страница 8: ... by the manufacturer its ser vice agent or similarly qua lified persons in order to avoid a hazard Do not connect air condi tioner to multi purpose soc ket Otherwise it may cau se fire hazard Do disconnect power supp ly when cleaning air condi tioner Otherwise it may cause electric shock Do not wash the air condi tioner with water to avoid electric shock Do not spray water on in door unit It may c...

Страница 9: ...t It may cause mal function Do not step on top panel of outdoor unit or put heavy objects It may cause dam age or personal injury When below phenomenon occurs please turn off air conditioner and disconnect power immediately and then contact the dealer or qualified professionals for service Power cord is overheat ing or damaged There s abnormal sound during operation Circuit breaker trips off frequ...

Страница 10: ...n serious safety accident Tools for installation 5 Safety precautions for installing and relocating the unit sure that the unit is running in cooling mode Then fully close the valve at high pressure side liquid valve About 30 40 seconds later fully close the valve at low pressure side gas valve immediately stop the unit and disconnect power Please note that the time for refrigerant recovery should...

Страница 11: ...the requirement of air conditioner Unstable power supply or incorrect wiring or malfunction Pl ease install proper power supply cables before using the air conditioner grounding wire of power socket 5 Be sure to cut off the power supply before pr oceeding any work related to electricity and safety 8 2 Select a location where the condensation water 3 Select a location which is convenient to conne c...

Страница 12: ...res when opening the hole bellmouth Pretighten the union nut with hand Please refer to the actual circumstances for the number of screws and the position of screws rear right 1 7 The pipe can be led out in the direction of right Choose the position of piping hole according Adjust the torque force by referring to the wrench on the union nut Tighten the union nut with torque wrench When installation...

Страница 13: ...ue N m NOTE Add insulating pipe in the indoor drain hose in order to prevent condensation The plastic expansion particles are not provided All wires of indoor unit and outdoor unit should be If the length of power connection wire is insufficient For the air conditioner with plug the plug should be NOTICE connected by a professional Make the power connection wire go through the cable cross hole at ...

Страница 14: ...d pipes in the wall pipe and then make them pass through the wall hole Hang the indoor unit on the wall mounting frame Stuff the gap between pipes and wall hole with sealing gum Fix the wall pipe Check if the indoor unit is installed firmly and closed to the wall Remove the wire clip connect the power conn ection wire to the wiring terminal according to the color tighten the screw and then fix the...

Страница 15: ...ng bracket for outdoor unit is damaged or corroded If yes please contact dealer The filter should be cleaned every three months If there is much dust in the operation environme After removing the filter do not touch fins to avoid injury Do not use fire or hair dryer to dry the filter to avoid deformation or fire hazard When air conditioner status is abnormal tempe rature indicator on indoor unit w...

Страница 16: ...nd or contraction of panel or other parts due to the change of temp erature In order to prevent blowing out cold air indoor unit will be started after delaying for several minutes which is a normal phenomenon Phenomenon Heating mode is turned on just now Reinsert the plug Odours are emitted Set tempe Air switch trips off or fuse is burnt out Set temperature Signal receiving range is 8m Whether the...

Страница 17: ... please use aux button to turn on or turn off the air conditioner The operation in details is as below As shown in the figure open panel and press aux button to turn off the air conditioner When the air conditioner is turned on it will operate under auto mode aux button filter air inlet panel horizontal louver air outlet Temp indicator Dry mode Power indicator Heat mode Cool mode R only for heat m...

Страница 18: ...nt temp Sleep mode Clock Health mode I feel Quiet TIMER ON TIMER OFF Auto mode Cool mode Dry mode Fan mode Left right swing Up down swing Child lock Send signal Turbo mode Heat mode Operation mode Set fan speed Temp display type Introduction for icons on display screen Buttons on remote controller Operation and introduction of remote controller ...

Страница 19: ...have turn ed off the unit After energization X FAN OFF is defaulted X FAN is not available in auto fan or heat mode This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to avoid mould NOTE button to adjust fan blowing angle When selecting heat mode the air conditioner operates under heat mode Press or button to adjust set temperature Press FAN...

Страница 20: ...tomat ically swing up down at maximum angle When selecting air condition er is blowing fan at fixed position Horizontal louver will stop at the fixed position When selecting air conditioner is blowing fan at fixed angle Horizontal louver will send air at the fixed angle Hold button above 2s to set your required swing angle When reaching your required angle release the button no display horizontal louv...

Страница 21: ...emperature In Heat mode sleep status after run for one hour the setting tem perature will decrease 1 two hours setting temperature will decrease 2 then the unit will run at this setting temperature Sleep 2 is sleep mode 2 that is air conditioner will run according to the presetting a group of sleep temperature curve Sleep 3 the sleep curve setting under Sleep mode by DIY 1 Under Sleep 3 mode press...

Страница 22: ...status Operation for TIMER ON TIMER OFF is the same Press this button to set clock time icon on remote controller will blink Press or button within 5s to set clock time Each pressing of or button clock time will increase or decrease 1 minute If hold or button 2s later time will change quickly Release this button when reaching your required time Press CLOCK button to confirm the time icon stops bli...

Страница 23: ...t temperature when turning on the unit There is no display in the remote control ler Only for the models whose indoor unit has dual 8 dis play When selecting displaying of indoor or outdoor ambi ent temperature indoor temperature indicator dis plays corresponding temperature and automatically turn to display set temperature after three or five se conds 8 C heating function Under heat mode press TE...

Страница 24: ... along the arrow direction Replace two 7 AAA 1 5V dry batteries and make sure the position of polar and polar are correct Reinstall the cover of battery box 2 1 3 battery remove reinstall Cover of battery box signal sender Auto clean function This function is only available for some models NOTE Under unit off status hold MODE and FAN buttons simultaneously for 5s to turn on or turn off the auto cl...

Страница 25: ...lfunction or damage the parts Is there any obstruction in the air inlet and outlet Is heat insulation of pipe line sufficient It may cause malfunction or damage the parts The gas valve and liquid valve of connection pipe are open completely The dust and sundries caused during installation are removed It may cause condensation and water dripping It may cause electric leakage Is the inlet and outlet...

Страница 26: ...5m and 8m the min length of con nection pipe is 3m Max length of connection pipe is shown as below 4 1 2 The calculation method of additional refrigerant oil and refrigerant charging amount after prolong ing connection pipe After the length of connection pipe is prolonged for 10m at the basis of standard length you should add 5ml of refrigerant oil for each additional 5m of connection pipe The cal...

Страница 27: ...s from getting into the pipe pipe any blemish expand the port again according to the steps above 43 26 Outdoor side Indoor side DB WB C DB WB C 32 23 24 18 Maximum cooling 27 GWH18ACD K6DNA1X I heating For some models Maximum NOTE 48 30 Outdoor side Indoor side DB WB C DB WB C 24 18 Maximum cooling GWC24ACE K6DNA1A I 27 32 23 heating Maximum NOTE NOTE ture for cooling only unit is 15 C 48 C The op...

Страница 28: ...oling NOTE ature for Low temperature cooling only unit is 15 C 50 C for heat pump unit is 15 C 50 C Indoor side DB WB C Outdoor side DB WB C Maximum cooling Maximum heating NOTE Indoor side DB WB C Maximum heating GWH09ACC K6DNA1F I LC GWH12ACC K6DNA1F I LC GWH18ACD K6DNA1I I LC GWH18ACD K6DNA5I I LC GWH09ACC K6DNA1F I LCLH GWH12ACC K6DNA1F I LCLH GWH12ACC K6DNA5F I GWH18ACD K6DNA1I I LCLH GWH18AC...

Страница 29: ...eal ed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted on the refrigera tion equipment or any associated parts appropriate Ventilated area Ensure that the area is in the open or that it is ad equately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carri ed out The...

Страница 30: ...e and being used correctly the recovery process is supervised at all times by a competent person d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refrigerant can be removed from various parts of the system f Make sure that cylinder is situated on the scales before recovery takes place g Start the recovery machine and operate in accor dance with manuf...

Страница 31: ...d refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant waste transfer note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be remov ed ensure that they have been evacuated to an ac ceptable level to make certain that flammable refri gerant does not remain within the lu...

Страница 32: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI 600005060453 Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail global cn gree com Web www gree com ...