Photovoltaic Direct-driven Inverter VRF
43
Fig.4.7.6 Two wired controllers control multiple IDUs
When two wired controllers control multiple IDUs, the wired controller can be connected to
any one IDU, provided that the connected IDU is of the same series. Meanwhile, one and only
one of the wired controllers must be set as a slave controller. At most 16 IDUs can be
controlled by wired controllers and the connected IDUs shall be within a same IDU network.
No matter when unit is turned on or off, slave controller can be set.
How to set a slave controller: hold “function” button on the designated controller f or 5s, and
temperature zone displays C00. Continue holding “function” button for 5s and setting screen of
controller parameter will come out. Default temperature zone displays P00.
Press
button or
button to select parameter code P13. Press “mode” button to
switch to setup of parameter values. Then the parameter value will blink. Press
button or
button to select code 02. And then press “confirm/cancel” to finish setting.
Press “confirm/cancel” to return to the previous display until you exit from the setup of
parameter values.
Below are user’s parameter settings:
Parameter
code
Parameter
name
Parameter scope
Default
value
Remark
P13
Set up
address for
wired
controller
01: master wired
controller
02: slave wired
controller
01
When 2 wired controllers control one or
more IDUs, they shall have different
addresses. Slave wired controller (02) can’t
set up units’ parameters except its own
address.
4.7.3 Communication connection of central controlling units
NOTICE!
The centralized controller can be installed when it is necessary.
Port connection G1 and G2 on the wiring board XT2 of master unit among each multi VRF
system (see below)