Photovoltaic Direct-driven Inverter VRF
22
Total rated capacity of outdoor
modules (multi-modular system)
Pipe between ODU and the first branch of IDU
Gas pipe size mm(in.)
Liquid pipe size mm(in.)
GMV-Y216WM/C-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
GMV-Y240WM/C-F(U)
Ф34.9(1-3/8)
Φ15.9(5/8)
GMV-Y264WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y288WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y312WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y336WM/C-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
GMV-Y360WM/C-F(U)
Ф41.3(1-5/8)
Ф19.05(3/4)
4.2.5.5 Manifold at indoor unit side
Manifold at indoor unit side can be selected as per total capacity o f downstream indoor
unit(s). Refer to the following table.
Fig. 4.2.12(a)
Fig. 4.2.12(b)