Photovoltaic Multi VRF 

29 

 

No 

Debug item 

Parameter name 

Unit 

Reference 

Compressor’s IPM 

temp 

 

When  ambient  temp  is  below  35

,  IPM  temp  is 

lower  than  80

 

and  the  highest  temp  won’t  be 

above 95

10 

Fan motor’s operating 

freq 

HZ 

Changes  in  0~49Hz  according  to  system’s 
pressure. 

11 

IDU 

parameters 

IDU ambient temp 

 

—— 

12 

Indoor heat 

exchanger’s inlet 

temp 

 

●According  to  ambient  temp,  for  a  same  IDU  in 
cool  mode,  the  inlet  temp  will  be  1

~7

  lower 

than  the  outlet  temp,  and  4~9

  higher  than  the 

low pressure value. 
●For a same IDU in heat mode, the inlet temp will 
be 10

~20

  lower than the outlet temp. 

13 

Indoor heat 

exchang

er’s inlet 

temp 

 

14 

Opening angle of 

indoor EXV 

PL

●In  cool  mode,  the  opening  angle  of  indoor  EXV 
varies within 70~480PLS. 
●In  heat  mode,  the  opening  angle  of  indoor  EXV 
varies within 70~480PLS. 

15 

Communication 

parameters 

Communication data 

— 

Number of IDUs detected by software is the same 
with the actual number. No communication error. 

16 

Drainage system 

—— 

— 

Indoor  unit  can  drain  water  out  completely  and 
smoothly.  Condensate  pipe  has  no  backward 
slope  of  water;  Water  of  outdoor  unit  can  be 
drained  completely  through  drainage  pipe.  No 
water drop from unit base. 

17 

Others 

—— 

— 

Compressor  and  indoor/outdoor  fan  motor  do  not 
have strange noise. Unit can operate normally. 

6 Common Malfunctions and Troubleshooting

 

Warning: 

 If there is abnormal condition (e.g. unpleasant smell), turn unit off and disconnect power 

immediately. Then contact Gree authorized service center. If unit continues operation 

despite the abnormal condition, it may get damaged and lead to electric shock or fire hazard. 

 Do not repair the air conditioner by yourself. Improper maintenance may lead electric shock 

or fire hazard. Please contact Gree authorized service center for maintenance. 

(1) Please check the items below before calling for maintenance. 

Problems 

Causes 

What to do 

Unit doesn’t work. 

Fuse or circuit breaker is cut off. 

Replace fuse or reset the 
circuit breaker. 

Power failure 

Restart unit when power is 
restored. 

Power is not connected. 

Connect the power. 

Remote controller’s power is not enough 

Replace new battery. 

Remote controller is out of the control range. 

Control range is within 8m. 

Unit runs but stops 

immediately. 

Air inlet or air outlet of indoor and outdoor units is 
blocked. 

Clear obstructions. 

Abnormal cooling or 

heating 

Air inlet or air outlet of indoor and outdoor units is 
blocked. 

Clear obstructions. 

Improper temp setting 

Adjust setting at remote 
controller or wired 
controller 

Fan speed is set too low. 

Adjust setting at remote 
controller or wired 
controller 

Wind direction is not correct. 

Adjust setting at remote 
controller or wired 
controller 

Содержание GMV-Y120WL/A-T

Страница 1: ...Owner s Manual Original Instructions Commercial Air Conditioners Photovoltaic Multi VRF Models GMV Y120WL A T GMV Y140WL A T GMV Y160WL A T...

Страница 2: ...rough strict inspection and operational test before leaving the factory In order to avoid damage due to improper disassembly and inspection which may impact the normal operation of unit please do not...

Страница 3: ...Adding 14 4 5 Electric Wiring 16 4 6 Installation project of photovoltaic system 19 5 CHECK ITEMS AFTER INSTALLATION AND TEST OPERATION 22 5 1 Check Items after Installation 22 5 2 Test operation and...

Страница 4: ...Installation should be performed by distributor or qualified technicians Do not install the product by yourself Improper installation may result in water leakage electric shock or fire hazard Before i...

Страница 5: ...r at least 5 minutes Otherwise oil return of the compressor will be affected Children are not allowed to operate the air conditioner Do not operate the air conditioner with wet hands Please turn off a...

Страница 6: ...nstall units according to national wiring codes If the supply cord is damaged it musr be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard An...

Страница 7: ...ne of the indoor units receives operating command outdoor unit will start operation as per required capacity When all indoor units stop outdoor unit will be shut off 2 3 Operating Range Cooling Outdoo...

Страница 8: ...plosive and corrosive gas or waste gas Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with good ventilation ODU and IDU should stay as close as po...

Страница 9: ...re only for reference Please refer to actual products Unspecified dimensions are all in mm 4 1 Dimension of Outdoor Unit and Mounting Hole Unit Outline and Installation Dimension mm Unit mm Model A B...

Страница 10: ...Diagram of Piping Connection 4 2 2 Allowable Length and Height Difference of Connection Pipe Y type branch joint is adopted to connect indoor and outdoor units Connecting method is shown in the figur...

Страница 11: ...ngth of farthest fitting pipe m Actual length 120m L1 L2 L3 d Equivalent length 150m From the 1st branch to the farthest indoor pipe 40m L2 L3 d Height difference between ODU and IDU ODU at upper side...

Страница 12: ...f downstream indoor units If the capacity exceeds that of the outdoor unit capacity of outdoor unit prevails R410A Refrigerant system Total capacity of downstream indoor units X kW Model Y type branch...

Страница 13: ...h and IDU Dimension of pipe between indoor branch and IDU should be consistent with the dimension of indoor pipe Rated capacity of IDU C kW Gas pipe mm Liquid pipe mm C 2 8 9 52 6 35 2 8 C 5 0 12 7 6...

Страница 14: ...imes at the same position 4 3 2 Flaring Process 1 Use pipe cutter to cut the connection pipe in case it is unshaped 2 Keep the pipe downward in case cutting scraps get into the pipe Clear away the bur...

Страница 15: ...e tightly with plastic tape 5 Connection pipe should be supported by a bearer rather than the unit 6 The bending angle of piping should not be too small otherwise the piping might have cracks Please u...

Страница 16: ...3 7 Thermal Insulation for Pipeline 1 For multi VRF system every copper pipe should be labeled so as to avoid misconnection 2 At the branch inlet leave at least 500mm straight pipe section 3 Thermal i...

Страница 17: ...to completely seal the hole on the wall 4 3 8 Support and Protection of Pipeline 1 Support should be made for hanging connection pipe Distance between each support cannot be over 1m 2 Protection again...

Страница 18: ...rant When the ODU is GMV Y WL A T adding refrigerant method includes 3 steps as follow 1 Amount of additional refrigerant depending on the pipe size X 2 Amount of additional refrigerant depending on Q...

Страница 19: ...of additional refrigerant depending on Quantity of IDU Y Quantity of indoor unit 4 sets 3 Amount of additional refrigerant depending on certain model of IDU Z IDU includes GMV NDR40PH B1 T Therefore...

Страница 20: ...ure it is securely grounded It s a must to install air switch and current circuit breaker that can cut off the power of the entire system The circuit breaker should include magnetic trip function and...

Страница 21: ...with master circuit breaker for connecting or cutting off general power supply of IDU and ODU For AC public power grid selection of power cord diameter and air switch are as below Model Power Supply C...

Страница 22: ...core cross linked polyethylene insulated PVC cable laying in wire slot under using ambient temperature of 40 and cable working temperature of 90 if the using conditions are different please calculate...

Страница 23: ...ly Calculate the correct quantity of each row according to the quantity of photovoltaic sub assy of each row including the quantity of bolt and other accessories Firstly fix the transition unit in the...

Страница 24: ...ad The pipe port shall be deburred to avoid cutting the cable during pulling During laying wire make sure the wire size according to the diagram Before laying check if the insulation resistance is in...

Страница 25: ...eplate Unit may have malfunction or components may get damaged is the electric wiring and pipe connection installed correctly Unit may have malfunction or components may get damaged Unit is securely g...

Страница 26: ...he unit to check whether it s normally preheated If yes start test operation Otherwise compressor might be damaged 5 2 2 Test Operation and Debugging Description of test operation procedures and main...

Страница 27: ...debugging from progress 01 If the number is then correct press main board s SW7 button to confirm Then the display is as below db On 04 On OC On System has confirmed the quantity 2s later next step st...

Страница 28: ...r code On Outdoor component s error LED3 will display the related error code After errors are eliminated system will start next step automatically If power is off during troubleshooting then restart d...

Страница 29: ...at time db On 08 On OC On Compressor has been preheated for 8 hours 2s later next step starts 09_ Refrigerant judgments before startup db On 09 On U4 On System is lack of refrigerant and display will...

Страница 30: ...hen start next step 12_ Confirm debugging startup db On 12 On AP Blink Ready for units to start debugging Press main board s SW7 button to confirm startup of debugging 2s later main board will display...

Страница 31: ...than the high pressure saturation temp 3 Defrosting temp In cool mode defrosting temp is 4 10 lower than system s high pressure value In heat mode defrosting temp is about 2 different from system s l...

Страница 32: ...not have strange noise Unit can operate normally 6 Common Malfunctions and Troubleshooting Warning If there is abnormal condition e g unpleasant smell turn unit off and disconnect power immediately Th...

Страница 33: ...unning or after running This is the sound of drainage operation Cracking sound is heard when unit is running or after running This is the sound caused by the expansion of panel and other parts of the...

Страница 34: ...ir intake temperature sensor y8 Main error of indoor air box sensor yA IFD malfunction Outdoor Error Code Content Error Code Content F0 Main board of ODU is poor E0 Malfunction of ODU uniform F1 Malfu...

Страница 35: ...bF Malfunction of outlet tube temperature sensor of condenser PA Malfunction of drive storage chip of compressor bJ High pressure sensor and low pressure sensor are connected reversely PH High voltag...

Страница 36: ...n C2 Communication malfunction between main control and inverter compressor driver U4 Refrigerant lacking protection C3 Communication malfunction between main control and inverter fan driver U5 Wrong...

Страница 37: ...peration nn Length modification of connection pipe of ODU An Child lock status Ay Shielding status 8 Function Setting of Outdoor Unit When debugging is finished press SW3 on the master unit and unit w...

Страница 38: ...t can t be cancelled even when power is on or off Then press SW6 on the master unit to return to the previous step If this button is pressed when function is being set system will return to the previo...

Страница 39: ...o return to the previous step If then no motion is taken to the master unit for 5min unit will exit and resume displaying the current status If this button is pressed when function is being set system...

Страница 40: ...debugging remains the same iii When you only want to restore the default functions hold SW5 and SW8 button for more than 10s then all LED will blink for 7s All function settings are cleared out but I...

Страница 41: ...its 3 Clean away the dust and obstacles on indoor and outdoor units 4 If outdoor unit has rust please apply some paint to it so as to prevent the rust from growing 9 5 Parts Replacement Parts and comp...

Страница 42: ......

Отзывы: