Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit
12
(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage
pipe joint.
(6) Install drainage pipe according to the following Fig.4.3.1.1 and arrange insulation tow
the drainage pipe. Improper installation may lead to water leakage and damp the
furniture and other things in the room.
(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection,
insert the end of PVC pipe into the drainage hole and then tighten it with drainage hose
and wire binder. Never connect the drainage hole and drainage hose with glue.
(8) When the drainage pipelines are used for several units, the position of pipeline should
be about 100mm lower than the drainage port of each unit. In this case, thicker pipes
should be applied.
Fig.4.3.1.1
(9) Connect the drainage pipe properly, as shown in Fig.4.3.1.2.
Fig.4.3.1.2
4.3.2 Drainage Pipe Installation
(1) Drainage pipe should have the same diameter or larger diameter than the connection
pipes (PVC pipe, outside diameter 17mm, thickness
≥
1.75mm).
(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for
preventing forming air bubbles.
(3) Insert the drainage hose into drain socket, tighten the metal clamp securely.
(4) Warp the sealing pad over drain hose and metal clamp for heat insulation.
(5) Make sure to perform insulation work for all drainage piping in order to prevent any
possible water drop due to dew condensation.
(6) Apply the suitable diameter for converging drainage pipe according to the operating
capacity of the unit, as shown in Fig.4.3.2.1.