Multi Variable Air Conditioners Cassette Type Indoor Unit

 

12 

Torque for tightening nut 

Pipe diameter (mm) 

Torque (N·m) 

Φ6.35

 

15~30 

Φ9.52

 

35~40 

Φ12.7

 

45~50 

Φ15.9

 

60~65 

Φ

19.05 

70~75 

(3) Use pipe bend when bending the pipe and the bending angle should not be too small.   
(4) Wrap the connection pipe and joint with sponge and then tie them firmly with tape. 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notice for Installation of Drain Pipe 

(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which 

are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or 
corrupt the unit. 

(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from 

pouring in and cause property loss or personal injury. 

(3) Condensate drain pipe should be connected into special drain system for air conditioner. 
(4) The drainage pipe should be short and the gradient downwards should be at least 1%~2% in 

order to drain condensation water smoothly. 

(5) The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe joint. 
(6) Install drainage pipe according to the following fig and arrange insulation to the drainage pipe. 

Improper installation may lead to water leakage and damp the furniture and other things in the 
room.   

(7) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert the end 

of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder. Can’t 
connect the drainage hole and drainage hole with glue. 

(8) When the drainage pipelines are used for several units, the position of pipeline should be about 

100mm lower than the drainage port of each unit. In this case, thicker pipes should be applied. 

 

Fig.4.3.1 

4.3.2 Drainage Pipe Installation 

(1) Drainage pipe should have the same diameter or larger diameter than the connecting pipes 

(PVC pipe, outside diameter 25mm, thickness≥1.5mm)

(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for preventing 

forming air bubbles. 

(3) If the gradient of drainage pipe could not meet the installation requirements, raising pipe should 

be applied.   

(4) Insert the drainage hose into drain socket, tighten the metal clamp securely. 
(5) Warp the sealing pad over drain hose and metal clamp for heat insulation. 

Содержание GMV-ND100T/A-T

Страница 1: ...Multi Variable Air Conditioners Cassette Type Indoor Unit Models GMV ND28T A T GMV ND36T A T GMV ND45T A T GMV ND50T A T GMV ND56T A T GMV ND63T A T GMV ND71T A T GMV ND80T A T GMV ND90T A T GMV ND100...

Страница 2: ...used for long cut off the power supply please energize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual using environment otherwise it may impac...

Страница 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Страница 4: ...allation and Drainage System Testing 12 4 4 Panel Installation 15 4 5 Wired Controller Installation 16 5 Wiring Work 17 5 1 Connection of Wire and Patch Board Terminal 17 5 2 Power Cord Connection 18...

Страница 5: ...to other units that have been confirmed as complying to corresponding partial unit requirements of this international standard The electrical interface shall comply with electrical security requiremen...

Страница 6: ...objects into air outlet or air return grille If you use gas heater or petroleum heater in the same room please open the door or window to maintain good air circulation in case the room may lack of ox...

Страница 7: ...onditioner by yourself Improper repair will cause electric shock or fire hazard Please contact GREE service center and have it repaired by professional technicians Any personal injury or property loss...

Страница 8: ...d Cooling 27 19 35 24 Rated Heating 20 15 7 6 3 Preparations for Installation NOTE This picture is for reference only please refers to the actual product the unit of dimension is mm 3 1 Standard Fitti...

Страница 9: ...The appliance shall not be installed in the laundry 2 The location should be able to withstand the weight of unit 3 The water can be drained conveniently from drainage pipe 4 There should be no obstru...

Страница 10: ...f Communication Wire Selection NOTE If air conditioner used under strong electronic magnetic interference circumstance STP shielded twisted pair communication cable must be adopted 3 3 1 Selection of...

Страница 11: ...power cord and capacity of air switch Model Power Cord Size Air Switch Capacity A Minimum Sectional Area of Ground Wire mm Minimum Sectional Area of Power Cord mm GMV ND28T A T 220 240V 1ph 50Hz 208...

Страница 12: ...der to avoid a hazard The circuit breaker specification in above sheet is based on ambient temperature of 40 C If the working condition is different please adjust it according to the specification she...

Страница 13: ...on position Drill 4 holes according to the hole site on the cardboard as shown in Fig 4 1 3 diameter of drilling hole is according to the diameter of expansion bolt and the depth is 60 70mm as shown i...

Страница 14: ...pattern Refer to paper pattern of installation for ceiling opening dimension The center of ceiling opening is indicated on the paper pattern Fix the paper pattern to the unit with 4 screws and fix th...

Страница 15: ...e Indoor Unit 11 Fig 4 1 6 4 2 Refrigerant Pipe Connection 1 Aim the flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut with hand as shown in Fig 4 2 2 Tighten...

Страница 16: ...e should be bigger or equal to the diameter of drainage pipe joint 6 Install drainage pipe according to the following fig and arrange insulation to the drainage pipe Improper installation may lead to...

Страница 17: ...shaped joints 8 The installation height of raising pipe for drainage should be lower than B The gradient from raising pipe towards drainage direction should be at least 1 2 If the raising pipe is vert...

Страница 18: ...over the electrical components e g water pump etc 1 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check the dra...

Страница 19: ...r decorative panel installation could cause the following problems Fig 4 4 1 2 Ensure that its clearance free between decoration panel and ceiling board after installation if not please adjust the bod...

Страница 20: ...ing connection of signal receiver Notices that the connection wire not stuck in the middle of body and panel or may cause air leakage and lead to condensation water drop 4 Tighten 4 screws at each cor...

Страница 21: ...munication wires should be separated from power cord and connection wire between indoor unit and outdoor unit Adjust the static pressure via wired controller according to site circumstance 5 1 Connect...

Страница 22: ...holes 3 Connect the power cord to terminal L N 4 Fix the power cord with wiring clamp 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or indoor unit 1 Detach the electric bo...

Страница 23: ...reless controller is shown as Fig 5 4 2 signal receiver is provided with panel as standard accessory Fig 5 4 1 Fig 5 4 2 2 Both IDU and wired controller are equipped with signal receiver and available...

Страница 24: ...Multi Variable Air Conditioners Cassette Type Indoor Unit 20 Fig 5 5...

Страница 25: ...the filter with a wet cloth dipped in neutral detergent Please contact after sales service staff if there is abnormal situation 6 1 Cleaning of Filter 1 Remove the filters from inlet of IDU Use a vac...

Страница 26: ...repair may cause electric shock or fire so please contact an authorized service center for professional service The following checks prior to contact may save your time and money Phenomenon Troublesho...

Страница 27: ......

Отзывы: